![Danfoss Termix BL Operating Manual Download Page 9](http://html1.mh-extra.com/html/danfoss/termix-bl/termix-bl_operating-manual_3482145009.webp)
Operating Guide
Termix BL
5.2 Schematic diagram
Schematic diagram type 2-5 (example)
DHW
DH
Supply
DH
Return
DCW
HWC
Your substation might look different than the schematic diagram shown.
Schematic description
B
Heat exchanger, DHW
4
Safety valve
27 Actuator
D Hot water tank
11 Domestic hot water pump
30 Flow control with control valve
G Electronic controller, DHW
13 Charging pump
36 Balancing valve
L
Border of delivery
18 Thermometer
40 Immersion sensor
1
Ball valve
19 Surface sensor
43 Ball valve closed
2
Single check valve
24 Delivered loose with unit
44 Immersion sensor
DHW:
Domestic Hot Water
DCW:
Domestic Cold Water
HWC:
Hot Water Circulation
DH Supply:
District Heating Supply
DH Return:
District Heating Return
5.2.1 Technical parameters
Technical parameters
Nominal pressure:
PN 16
Max. DH supply temperature:
120 °C
Min. DCW static pressure:
0.5 bar
Brazing material (HEX):
Copper
Heat exchangers test pressure:
30 bar
Sound level:
≤ 55 dB
Danfoss District Energy
VI.EH.D4.02 / LUK41570
DEN-GT
9