Operating guide

Termix AT BTD

3.0 Safety notes

3.1 Safety Notes – general

The following instructions refer to the standard design of
substation. Special versions of substations are available on
request.

This operating manual should be read carefully before installation
and start-up of the substation. The manufacturer accepts no
liability for damage or faults that result from non-compliance with
the operating manual. Please read and follow all the instructions
carefully to prevent accidents, injury and damage to property.
Assembly, start-up and maintenance work must be performed by
qualified and authorized personnel only.
Please comply with the instructions issued by the system
manufacturer or system operator.

Corrosion protection

All pipes and components are made of stainless steel and brass.
The maximum chloride compounds of the flow medium should not
be higher than 150 mg/l.
The risk of equipment corrosion increases considerably if the
recommended level of permissible chloride compounds is
exceeded.

Energy source

The substation is designed for district heating as the primary
source of energy. However, also other energy sources can be used
where the operating conditions allow it and always are comparable
to district heating.

Application

The substation is designed to be connected to the house
installation in a frost-free room, where the temperature does not
exceed 50 °C and the humidity does not exceed 60%. Do not cover
or wall up the substation or in any other way block the entrance
to the station.

Choice of material

Choice of materials always in compliance with local legislation.

Safety valve(s)

We recommend mounting of safety valve(s), however, always in
compliance with local regulations.

Connection

The substation must be equipped with features that ensure that
the substation can be separated from all energy sources (also
power supply).

Emergency

In case of danger or accidents - fire, leaks or other dangerous
circumstances - interrupt all energy sources to the station if
possible, and seek expert help.
In case of discoloured or bad-smelling domestic hot water, close all
shut-off valves on the substation, inform the operating personnel
and call for expert help immediately.

Storage

Any storage of the substation which may be necessary prior to
installation should be in conditions which are dry and heated.

Authorized personnel only

Assembly, start-up and maintenance work must be performed by
qualified and authorized personnel only.

Please observe instructions carefully

To avoid injury to persons and damage to the device, it is absolutely
necessary to read and observe these instructions carefully.

Warning of high pressure and temperature

Be aware of the installation’s permissible system pressure and
temperature.

The maximum temperature of the flow medium in the substation is
120 °C.

The maximum operating pressure of the substation is 10 bar. PN 16
versions are available on enquiry.

The risk of persons being injured and equipment damaged increases
considerably if the recommended permissible operating parameters

are exceeded.
The substation installation must be equipped with safety valves,

however, always in accordance with local regulations.

Warning of hot surface

The substation has got hot surfaces, which can cause skin burns.

Please be extremely cautious in close proximity to the substation.
Power failure can result in the motor valves being stuck in open

position. The surfaces of the substation can get hot, which can cause
skin burns. The ball valves on district heating supply and return should

be closed.

Warning of transport damage

Before substation installation, please make sure that the substation

has not been damaged during transport.

IMPORTANT - Tightening of connections

Due to vibrations during transport all flange connections, screw joints
and electrical clamp and screw connections must be checked and
tightened before water is added to the system. After water has been
added to the system and the system has been put into operation,
re-tighten

ALL

connections.

Danfoss District Energy

VI.JV.Y3.02 / LUK40692

DEN-GT

3

Summary of Contents for Termix AT BTD

Page 1: ... 6 6 0 Design 8 6 1 Design Termix AT BTD 5 pipes 8 6 2 Schematic diagram Termix AT BTD 5 Pipes 9 6 3 Design Termix AT BTD 4 pipes 10 6 4 Schematic diagram Termix AT BTD 4 Pipes 11 7 0 Controls 12 7 1 DHW temperature control 12 7 2 Other 13 7 3 Maintenance 14 8 0 Troubleshooting 15 8 1 Troubleshooting in general 15 8 2 Troubleshooting DHW 15 8 3 Disposal 16 9 0 Declaration 19 9 1 Declaration of con...

Page 2: ...a complete solution for hot water The Termix AT BTD is applicable for single family houses or apartments Domestic hot water DHW The domestic hot water circuit consists of a hot water tank with coil and self acting thermostatic control valve The hot water tank and coil are enamelled and the tank contains a magnesium anode The substation is delivered with a built in safety valve 2 DEN GT VI JV Y3 02...

Page 3: ... circumstances interrupt all energy sources to the station if possible and seek expert help In case of discoloured or bad smelling domestic hot water close all shut off valves on the substation inform the operating personnel and call for expert help immediately Storage Any storage of the substation which may be necessary prior to installation should be in conditions which are dry and heated Author...

Page 4: ...ken to mean the primary supply Connection sizes All connections G int thread Dimensions mm With cover 100L H 1180 x W 540 x D 520 150L H 1510 x W 540 x D 520 Weight approx 85 100 kg Authorized personnel only Assembly start up and maintenance work must be performed by qualified and authorized personnel only Termix AT BTD 5 pipes The pipe placement can deviate from the shown drawing Please note the ...

Page 5: ...es must be sealed with a plug Should the plugs require removal this must only be done by an authorized service technician Installation Strainer If a strainer is supplied with the station it must be fitted according to schematic diagram Please note that the strainer may be supplied loose Connections Internal installation and district heating pipes connections must be made using threaded flanged or ...

Page 6: ...ix AT BTD wall cabinet 5 1 Mounting Wall bracket Mount the Wall bracket according to the Drawing Use A to center the tank on the bracket B All pipe threads are ISO Mount the container unit in the wall bracket 6 DEN GT VI JV Y3 02 LUK40692 Danfoss District Energy ...

Page 7: ...n the bottom panel onto the 2 bushes in the side plates and fasten the panel with the 2 screws in the front 2 Top plate Mount the top plate 3 Front cover Mount the front cover by lowering the key holes onto the screws in the side plates 4 Clock panel Mount the clock panel by lowering the key holes onto the screws in the side plates Danfoss District Energy VI JV Y3 02 LUK40692 DEN GT 7 ...

Page 8: ...than the substation shown Design description E Hot water tank with coil 4 Safety valve S Siphon 20 Filling drain valve 1A Ball valve DVGW 41A Fitting piece cold water mains 2 Single check valve 59 Differential pressure temperature regulator with flow limiting 8 DEN GT VI JV Y3 02 LUK40692 Danfoss District Energy ...

Page 9: ...t water tank with coil 4 Safety valve 1 Ball valve 20 Filling drain valve 1A Ball valve DVGW 41A Fitting piece cold water mains 2 Single check valve 59 Differential pressure temperature regulator with flow limiting DHW Domestic Hot Water DCW Domestic Cold Water CWM Cold water mains DH Supply District Heating Supply DH Return District Heating Return Danfoss District Energy VI JV Y3 02 LUK40692 DEN ...

Page 10: ... different than the substation shown Design description E Hot water tank with coil 4 Safety valve S Siphon 20 Filling drain valve 1A Ball valve DVGW 59 Differential pressure temperature regulator with flow limiting 2 Single check valve 10 DEN GT VI JV Y3 02 LUK40692 Danfoss District Energy ...

Page 11: ...ty valve 1 Ball valve 20 Filling drain valve 1A Ball valve DVGW 59 Differential pressure temperature regulator with flow limiting 2 Single check valve DHW Domestic Hot Water DCW Domestic Cold Water DH Supply District Heating Supply DH Return District Heating Return 6 4 1 Technical parameters Technical parameters Nominal pressure PN 10 Max DH supply temperature T max 95 C Danfoss District Energy VI...

Page 12: ... temperature control thermostat in one pipe heating systems QT is dedicated to be used with AB QM automatic balancing control valve AB QM DN 10 20 45 60 C QT Sensor setting turns Temperature setting 0 1 2 3 4 5 6 20 48 0 50 5 53 0 55 5 58 0 60 5 63 0 30 47 0 49 5 52 0 54 5 57 0 59 5 62 0 40 46 0 48 5 51 0 53 5 56 0 58 5 61 0 50 45 0 47 5 50 0 52 5 55 0 57 5 60 0 60 44 0 46 5 49 0 51 5 54 0 56 5 59...

Page 13: ...2 Loosen nuts Loosen the nuts on the fitting piece 3 Remove fitting piece Remove the fitting piece and replace it with the cold water meter Do not forget the gaskets 4 Tighten connections After mounting of the cold water meter remember to check and tighten all threaded connections 7 2 2 Siphon Placed the Siphon directly under the Safety valve Ensure that the drainpipe has a minimum internal diamet...

Page 14: ... of all temperatures such as DH supply temperature and DHW temperature Connections Checking all connections for leakages Safety valves The operation of the safety valves should be checked by turning the valve head in the indicated direction Venting Checking that the system is thoroughly vented Inspections should be carried out minimum every two years Spare parts can be ordered from Danfoss Please ...

Page 15: ...tive or clogged non return valve Replace clean No electricity Check Wrong setting of automatic controls if any To adjust an electronic controller for DHW pls note enclosed instructions for electronic controller Scaling of the plate heat exchanger Replace rinse out Defective motorized valve Check use manual function replace Defective temperature sensors Check replace Too little or no DHW Defective ...

Page 16: ...Disposal Disposal This product should be dismantled and its components sorted if possible in various groups before recycling or disposal Always follow the local disposal regulations 16 DEN GT VI JV Y3 02 LUK40692 Danfoss District Energy ...

Page 17: ...Operating guide Termix AT BTD Danfoss District Energy VI JV Y3 02 LUK40692 DEN GT 17 ...

Page 18: ...Operating guide Termix AT BTD 18 DEN GT VI JV Y3 02 LUK40692 Danfoss District Energy ...

Page 19: ...Operating guide Termix AT BTD 9 0 Declaration 9 1 Declaration of conformity Category 0 without electrical equipment Danfoss District Energy VI JV Y3 02 LUK40692 DEN GT 19 ...

Page 20: ...Operating guide Termix AT BTD Produced by Danfoss A S 10 2017 ...

Reviews: