Installation Guide 

Safety thermostats ST-S2

Danfoss Heating 

VI.IA.N1.02 

DH-SMT/SI

ENGLISH

Safety Note

To avoid injury and damage to persons 

and devices, it is absolutely necessary 

these instructions are carefully read 

and observed prior to assembly and 

commissioning. 

Necessary assembly, start-up, and 

maintenance work must be performed 

only by qualified, trained and authorised 

personnel. 

Prior to assembly and maintenance work 

on the controller, the system must be:

-  depressurized 

-  cooled down

-  emptied 

-  cleaned

Please comply with the instructions of the 

system manufacturer or system operator.

This installation procedure describes as 

follow must be performed exclusively 

by qualified personnel in respect to the 

security norms and dispositions of the 

current standards.

Disposal instruction

This product should be 

dismantled and its 

components sorted, if 

possible, in various groups 

before recycling or disposal. 

Always follow the local disposal 

regulations.

Installation

Disconnect the mains before performing 

any operation!

Verify the thermostat technical data 

(power supply, contact rating, etc...) are 

suitable to the installation conditions.

❶ 

Unscrew the three fixing screws and the 

cap 

, then remove the cover.

 Wire the thermostat  according to 

wiring diagram.

Terminals:

1  Opens the circuit when temperature 

increases

2  Closes the circuit when temperature 

increases

C  Common

 Ground

 Adjust the temperature set-point 

thermostat  by rotating the cam 

 Put the cover back in place adjusting 

the knob so that it slides on the control 

thermostat adjustment pin. Then tighten 

the cap 

 and the three screws.

 Place of installation of immersion 

pocket must be chosen in a way that the 

temperature of the medium is directly 

taken without any delay.

 Immerse the temperature sensor into 

the immersion pocket in its full length. 

When using immersion pockets longer 

then 100 mm first carefully pull enough 

capillary tube out of the housing. Capillary 

tube may not be twisted or buckled! After 

inserting temperature sensors lock the 

housing tightening the screw 

 In order to reset the thermostat, 

unscrew the cap 

 and push the reset 

button 

.

 

Note:

Reset allowed for temperature values from 15 

to 25 °C below T

setpoint