Commissioning (RF models only)
If the thermostat and the receiver have been supplied together
in a combined pack, the units have been paired in the factory
and no commissioning is required (RX1 only).
To tune the RX receiver to the frequency of the thermostat signal,
follow steps 1-5 below.
Step 1 RT51/52-RF
Reset the unit by removing the
batteries for 2 minutes, then replace.
Step 2
Press and hold
V and
+
buttons for 3 seconds (Thermostat now
transmits unique signal continuously
for 5 minutes).
Step 3 RX1
Press and hold buttons
PROG and CH1
for 3 seconds until green light fl ashes
once.
Step 4 RX2 (if applicable)
Stat 1 - perform steps 1-3.
Stat 2 - wait 5 mins, perform steps 1-2 and
then press
PROG and CH2 on RX2.
RX3 (if applicable)
Stat 1 - perform steps 1-3.
Stat 2 - wait 5 mins, perform steps 1-2 and then press
PROG and
CH2 on RX3.
Stat 3 - wait 5 mins, perform steps 1-2 and then press
PROG and
CH3 on RX3.
Step 5 RT51/52-RF
Press
Λ
or V
to select temperature - unit will revert back to operating
mode.
Installa
tion Instruc
tions
GB
Summary of Contents for RT51-RF
Page 59: ...59 140 mm 15 mm 30 mm 100 mm GR...
Page 60: ...60 ON OFF 1 ON OFF ON OFF 2 RT51 52 RT51 52 RT51 52 1 ON OFF 2 CHRONO GR...
Page 63: ...63 RT51 RT51 2 RT52 RT52 RT51 RF RT51 RF RT52 RF RX 30 m 22 C 20 0 22 C n 20 0 DAY NIGHT GR...
Page 64: ...64 2 DAY s t s t n s t 5 30 C Off 22 C 20 0 22 C n 20 0 GR...
Page 65: ...65 i2 00 d n PROG PROG RUN RT52 52 RF PROG GR...
Page 66: ...66 22 C 20 0 LCD 15 GR...
Page 94: ...94...
Page 95: ...95...
Page 96: ...96 www danfoss com BusinessAreas Heating Part No 61076v07 07 07...