background image

Installation guide

017

R9

50

4

017

R9

50

4

© Danfoss | DCS (jmn) | 2015.11

DKRCC.PI.CF0.A2.52 | 520H10146 | 1

Pressure switch

 

RT 6W, RT 6B, RT 6S, RT 6AW, RT 6AB, RT 6AS, RT 30AW, RT 30AB, RT 30AS with 

EN 12263 approval and CEmarked acc. to PED (Pressure Equipment Directive) 

Type / 
Typ

Enclosure*

Tæthedsgrad*

Schutzart*

Degré 

d’étanchéité*

Reset

Pressure range

Trykområde

Druckbereich

Plage de pression 

[bar]

Differential (fixed)

Differens (fast)
Differenz (fest)
Différence (fix) 

Δp

[bar]

Refrigerants

Kølemidler
Kältemittel

Réfrigérants

Max. working press.

Till. driftstryk

Zul. Betriebsüberdruck

Press. de service max.

PB / MWP 

[bar] / [psig]

Max. test press.

Max. prøvetryk
Max. Prüfdruck

Press. d’essai 

 

[bar] / [psig]

Ambient temp.

Omgivelsestem.

Umgebungstemp.

Temp. ambiante 

[°C]

RT 6W

IP66

automat.

5 – 25

3.0

fluorinated refrigerants

fluoreded kølemidler

fluorierte Kältemittel

réfrigérants fluorés

28 / 406

38 / 551

-50 – 70

RT 6B

IP54

man. ext.

10 – 28

max. 1.0

RT 6S

IP66

man. int.

RT 6AW

IP66

automat.

5 – 25

3.0

R 717 (NH

3

)

+ fluorinated refrigerants

+ fluorerede kølemidler

+ fluorierte Kältemittel

+ réfrigérants fluorés

RT 6AB

IP54

man. ext.

10 – 28

max. 1.5

RT 6AS

IP66

man. int.

RT 30AW

IP66

automat.

1 – 10

0.8

22 / 319

25 / 363

max. 0.4

RT 30AB

IP54

man. ext.

RT 30AS

IP66

man. int.

Fig. 10 

* according to / i.h.t. / nach / conformément à EN 60529 / IEC 529

Refrigerants:

 

R717 

1)

, HCFC and non-flamable HFC

RT 6AW, RT 6AB, RT 6AS

BSP

G

RT 6W, RT 6B, RT 6S

Fig. 2
RT 30AW, RT 30AB, RT 30AS

BSP

G

Fig. 1

Fig. 3

Danfos

s

17-5027.10

Fig. 4

Fig. 5

Fig. 6

Fig. 7

RT 6, RT 36:

 

1m, ¼ in x ¼ in flare 

Code no. 

060-007166 

RT 6, RT 36:

 

1m, 3/8 in x M10 – 0.75 

Code no. 

060-008266 

Danf

oss

60.9030

Code no. 

017-425166

Danf

oss

17.719

Fig. 8a

Fig. 8b

Fig. 9