background image

Installation guide

Thermostat

 

RT 103, RT 140, RT 141 

017

R9

31

9

017

R9

31

9

© Danfoss | DCS (jmn) | 2011.15

IC.PI.P10.P2.53 | 520B6827 | 1

RT 101

Danfos

s

17-5027.10

Fig. 1

Fig. 2

Fig. 3

RT 103

RT 140

RT 141

Fig. 4

ENGLISH

Thermostats Types RT 103, RT 140, RT 141

Fig. 1, 2 and 4

Ambient temperature: -50 °C – 70 °C 
Maximum sensor temperature: 

RT 103:

 100 °C 

RT 140:

 240 °C 

RT 141:

 250 °C

INSTALLATION

A set of Pg13.5 cable gland is attached to 
the RT in a separate bag. To ensure IP66 
(units with automatic reset) or IP54 (units 
with external reset) grade of RT enclosure 
it is necessary to assemble this gland as 
shown in the fig. 3. If this gland is not used 
with a cable, a metal blinding should be 
also assembled. 

SETTING

Fig. 4

A. Range setting   
B. Differential obtained   
C. Differential setting

   

The thermostat is set by rotating the knob 
(5), at the same time reading the main 
scale (9).  
The differential is set by rotating the 

differential adjusting nut (19) to the value 
indicated by the use of the nomogram in 
fig. 4. The maximum operating pressure is 
thus the sum of the setting temperature 
and the differential.

Example

It is desired to control an air heater by the 
use of an 

RT 103

Maximum discharge temperature: 32 °C
Minimum discharge temperature: 30 °C
Differential: 32 °C - 30 °C = 2 °C

1.  Connect the heater to terminals 1-2 of 
  the thermostate
2.  Set the thermostate for 30 °C by 
  rotating the knob (5)
3.  Set the differential adjusting nut (19) at 
  the figure 4 which is found by reading 
  the nomogram for 

RT 103

 in fig. 4.

DANSK

Termostater Type RT 103, RT 140, RT 141

Fig. 1, 2 og 4 

Omgivelses temperatur: -50 °C – 70 °C 
Max. følertemperatur:

 

RT 103:

 100 °C 

RT 140:

 240 °C 

RT 141:

 250 °C

INSTALLATION

Et sæt Pg13,5 kabelforskruning er vedlagt
produktet i en separat pose. For at sikre
kapslingsgrad IP66 (enheder med automa-
tisk reset) eller IP54 (enheder med ekstern
DANSK RESET) er det nødvendigt at mon-
tere denne kabelforskruning som vist i fig. 3. 
Hvis denne kabelforskruning ikke bruges
sammen med et kabel, bør der monteres
en blindprop (metal skive).

INDSTILLING

Fig. 4

A. Områdeindstilling
B. Opnået differens
C. Differensindstilling

Termostaten indstilles efter den funktion 
- slutte eller bryde - som skal ske ved 
faldende temperatur (områdeindstilling). 
Selve indstillingen udføres med håndknap-
pen (5) under samtidig aflæsning af 
hovedskalaen (9).
Differensen indstilles med differensrullen 
(19) efter nomogrammet i figur 4. Højeste 
funktionstemperatur er således lig summen 
af indstillingstemperatur og differens.

Eksempel

En varmluftovn ønskes styret af en 

RT 103

Max. afgangstemperatur: 32 °C

Reviews: