REPI series thermostats are used to control room temperature in industrial, commercial 

and residential environment via controlling electric modulating valve with 0-10VDC (4-20mA) 

control signal or floating control as well as damper actuator of VAV system.   

Electronic control technology is adopted, with green backlit LCD display of: working mode 

(cooling “ ”, heating “ ”, ventilating “ ”, auto “ ” ); fan speed (low “ ”, med “ ”, high “ ”, 

auto “

”); room temperature; setting temperature etc. push button: On/Off “

”; mode 

changeover “

”; fan speed choose “

” and temperature adjustment “ ” and “ ”. 

Shell: PC + ABS retardant material.

 

 

Function : 

 

 Detect and Display room temperature 

 Room temperature setting 

 Fahrenheit or Celsius degree display 

 Timing sleep 

 Control On/Off of cooling and heating equipment 

 Selectable single speed or three speed fan control 

Order Guide: 

Output signal 

Model 

Floating Modulation 

Fan 

(Single/3-speed) 

RS485 

Network 

Input 

Control 

Remote 

Sensor 

REPI-2 

 Cooling/Heating 

 

 

 

 

REPI-2N 

 Cooling/Heating 

 

 

 

 

REPI-4 

 Cooling&Heating 

 

 

 

 

REPI-4N 

 Cooling&Heating 

 

 

 

 

Fan: thermostat with fan functions, can be selected with single speed fan or three speed fan by setting parameter. 

Remote Control: input signal can be selected by setting parameter. 

Specification : 

 Set temperature range: 0 - 99.5

 adjustable   

 Accuracy displayed:

       

0.1

 

 Accuracy:                       

±

0.5

 

 Rated Power:

                   

<

 1 W 

 Sensor type:

   

                NTC 

 Display:

                         

      LCD 

 Power:

             

            AC 24V

±

10

,  50Hz/60Hz 

 Output signal:

     

      AC 24V

×

2 (0.5A 

resistive

) , 

0 - 10VDC(5mA) / 4 - 20mA (600

 Input signal:       dry contact (NO) 

 Dimensions:       86

×

86

×

23mm (W

×

H

×

D)  

 Fixing screw width : 60mm (Standard) 

Operations: 

"

 

On/Off: 

Press “ ” buttons to turn on; press “ ” again to turn off. 

"

 Setpoint: 

With thermostat on, press “ ” to reduce the setpoint, press “ ” to increase the setpoint, the setpoint step is 

0.5

, the setpoint will be confirmed automatically after 5 seconds, and then return to dispay status, press “ ” or “ ” to 

check setpoint. 

"

 

Mode: 

With thermostat on, press “

” to change the working mode – Cooling “ ”

 Heating “ ”, Vent " ", Auto “ ” 

( Auto is available REPI-4/ REPI-4N). 

"

 

Fan Speed: 

With thermostat on, press “

” to select the desired speed – low speed “ ”, Med speed “ ”, High speed 

“ ”, auto “ ”. If single speed fan available, there’s only med speed “ ”. 

Under auto speed fan, the fan speed will be changed automatically as below: in low speed when room temperature 

is 1

 difference with setpoint;in med speed when room temperature is 2  difference with setpoint

; in High speed when 

room temperature is 3  difference with setpoint. 

 

"

 

Sleep: 

Thermostat will get into sleep function after programming.The set Temperature should to be. 