background image

AI097986404620en-010102 | 3

© Danfoss | 2022.05

Data sheet 

REPI Series Digital Thermostat Manual

30

Override output value when bypass PID control

Display output value when enable PID control

0 - 255

31

Input signal management: 0: Input valid

1: Override Input: open

2: Override Input: close

0

0-2

32

Display room temperature or set-point

0: Room temperature 1: Set-Point

0

0-1

33

Configuration external sensor

0: B = 3950; 1: B = 3450; 2: B = 3900

3: User define (via network. default B = 3950)

0

0-3

34-38

N/A

39

Start temperature of Low temperature protection

5 °C/42 °F

0-15 °C/42-62 °F

1 °C/2 °F

40

Stop temperature of Low temperature protection

7 °C/46 °F

2-17 °C/46-66 °F

1 °C/2 °F

It will confirm itself 20 seconds later after setting and return to Off state.

Parameter table 

(continuous)

Specification

There is a 5 poles switch on PCB. The meaning is below:

Location

ON

OFF

1

120 ohm Resistance between AB wires

No Resistance between AB wires

2

Port 1 Modulation 0 - 20mA

Off

3

Port 1 Modulation 0 - 10VDC

Off

4

Port 2 Modulation 0 - 20mA

Off

5

Port 3 Modulation 0 - 10VDC

Off

40

Stop temperature of Low temperature protection

7 °C/46 °F

Mounting

1. Open the back panel with screwdriver.

2. Connect the wires follow the diagram.

3. Fix the base with screw.

4. Fix the front panel and finish the installation.

Summary of Contents for REPI Series

Page 1: ...mperature setting Fahrenheit or Celsius degree display Timing sleep Control On Off of cooling and heating equipment Selectable single speed or three speed fan control Order Guide Model Output signal Fan Single 3 speed RS485 Network Input Control Remote Sensor Floating Modulation REPI 2 Cooling Heating REPI 2N Cooling Heating REPI 4 Cooling Heating REPI 4N Cooling Heating Fan thermostat with fan fu...

Page 2: ...isappear to quit the function Set Parameters With thermostat off press for 10 seconds to enter menu to set the parameters Parameter table Parameter Description Default Range Step 1 Power on status 0 Off 1 On 2 Hold 2 0 2 2 Fan speed 0 Single Speed 1 Three Speed 1 0 1 3 Fan mode DA DB 0 4 Sensor selection 0 Internal 1 Remote 1 0 1 5 Temperature format 0 Celsius 1 Fahrenheit 0 0 1 0 1 6 Temperature ...

Page 3: ...ction 5 C 42 F 0 15 C 42 62 F 1 C 2 F 40 Stop temperature of Low temperature protection 7 C 46 F 2 17 C 46 66 F 1 C 2 F It will confirm itself 20 seconds later after setting and return to Off state Parameter table continuous Specification There is a 5 poles switch on PCB The meaning is below Location ON OFF 1 120 ohm Resistance between AB wires No Resistance between AB wires 2 Port 1 Modulation 0 ...

Page 4: ...986404620en 010102 Data sheet REPI Series Digital Thermostat Manual Wiring diagram Note Be sure to connect all the wires as per the wiring diagrams and keep it away from water mud and other material so as to prevent the unit being spoiled ...

Reviews: