background image

© Danfoss | 2022.05

AI097986404620en-010102 | 1 

REPI Series Digital Thermostat Manual

Data sheet

Description

REPI series thermostats are used to control 

room temperature in industrial, commercial and 

residential environment via controlling electric 

modulating valve with 0-10VDC (4-20mA) control 

signal or floating control as well as damper 

actuator of VAV system.

Electronic control technology is adopted, with 

green backlit LCD display of: working mode 

(cooling “ ”, heating “ ”, ventilating “ ”, auto 

“ ” ); fan speed (low “ ”, med “ ”, high “ ”, auto 

“ ”); room temperature; setting temperature 

etc. push button: On/Off “ ”; mode changeover 

“ ”; fan speed choose “ ” and temperature 

adjustment “ ” and “ ”.

Shell: PC + ABS retardant material.

Function

 Detect and Display room temperature

 Room temperature setting

 Fahrenheit or Celsius degree display

 Timing sleep

  Control On/Off of cooling and heating 

equipment

  Selectable single speed or three speed fan 

control

Order Guide

Model

Output signal

Fan

(Single/3-speed)

RS485

Network

Input

Control

Remote

Sensor

Floating

Modulation

REPI-2

Cooling/Heating

REPI-2N

Cooling/Heating

REPI-4

Cooling/Heating

REPI-4N

Cooling/Heating

Fan: thermostat with fan functions, can be selected with single speed fan or three speed fan by setting parameter.

Remote Control: input signal can be selected by setting parameter.

Specification

 Set temperature range: 0 - 99.5 °C adjustable

 Accuracy displayed: 0.1 °C

 Accuracy: ±0.5 °C

 Rated Power: < 1 W

 Sensor type: NTC

 Display: LCD

 Power: AC 24V±10%, 50Hz/60Hz

  Output signal: AC 24V×2 (0.5A resistive) , 

0 - 10VDC(5mA) / 4 - 20mA (600Ω)

  Relay load: 2A (resistive load), 1A (inductive 

load)

 Input signal: dry contact (NO)

 Dimensions: 86×86×23mm (W×H×D)

 Fixing screw width : 60mm (Standard)

Summary of Contents for REPI Series

Page 1: ...mperature setting Fahrenheit or Celsius degree display Timing sleep Control On Off of cooling and heating equipment Selectable single speed or three speed fan control Order Guide Model Output signal Fan Single 3 speed RS485 Network Input Control Remote Sensor Floating Modulation REPI 2 Cooling Heating REPI 2N Cooling Heating REPI 4 Cooling Heating REPI 4N Cooling Heating Fan thermostat with fan fu...

Page 2: ...isappear to quit the function Set Parameters With thermostat off press for 10 seconds to enter menu to set the parameters Parameter table Parameter Description Default Range Step 1 Power on status 0 Off 1 On 2 Hold 2 0 2 2 Fan speed 0 Single Speed 1 Three Speed 1 0 1 3 Fan mode DA DB 0 4 Sensor selection 0 Internal 1 Remote 1 0 1 5 Temperature format 0 Celsius 1 Fahrenheit 0 0 1 0 1 6 Temperature ...

Page 3: ...ction 5 C 42 F 0 15 C 42 62 F 1 C 2 F 40 Stop temperature of Low temperature protection 7 C 46 F 2 17 C 46 66 F 1 C 2 F It will confirm itself 20 seconds later after setting and return to Off state Parameter table continuous Specification There is a 5 poles switch on PCB The meaning is below Location ON OFF 1 120 ohm Resistance between AB wires No Resistance between AB wires 2 Port 1 Modulation 0 ...

Page 4: ...986404620en 010102 Data sheet REPI Series Digital Thermostat Manual Wiring diagram Note Be sure to connect all the wires as per the wiring diagrams and keep it away from water mud and other material so as to prevent the unit being spoiled ...

Reviews: