Specific application recommendations
Brazed plate heat
exchangers
A brazed plate heat exchanger needs very little
internal volume to satisfy the set of heat transfer
requirements. Consequently, the heat exchanger
offers very little internal volume for the
compressor to draw vapour from on the suction
side. The compressor can then quickly enter into
a vacuum condition; it is therefore important
that the expansion device be sized correctly
and that a sufficient pressure differential across
the expansion device be available to ensure
adequate refrigerant feed into the evaporator.
This aspect is of special concern when operating
the unit under low ambient and load conditions.
For further information on these conditions,
please refer to the previous sections.
Due to the small volume of the brazed plate heat
exchanger, no pump-down cycle is normally
required. The suction line running from the heat
exchanger to the compressor must be trapped to
avoid refrigerant migration to the compressor.
When using a brazed plate heat exchanger as
the condensing coil, a sufficient free volume for
the discharge gas to accumulate is required in
order to avoid excess pressure buildup. At least 1
meter of discharge line is necessary to generate
this volume. To help reduce the gas volume
immediately after start-up even further, the
supply of cooling water to the heat exchanger
may be opened before the compressor starts
up so as to remove superheat and condense the
incoming discharge gas more quickly.
Reversible heat pump
systems
Transients are likely to occur in reversible heat
pump systems, i.e. a changeover cycle from
cooling to heating, defrost or low-load short
cycles. These transient modes of operation
may lead to liquid refrigerant carryover (or
floodback) or excessively wet refrigerant return
conditions. As such, reversible cycle applications
require specific precautions for ensuring a long
compressor life and satisfactory operating
characteristics. Regardless of the refrigerant
charge in the system, specific tests for repetitive
floodback are required to confirm whether
or not a suction accumulator needs to be
installed. A crankcase heater and discharge gas
thermostat are required for reversible heat pump
applications.
The following considerations cover the most
important issues when dealing with common
applications. Each application design however
should be thoroughly tested to ensure
acceptable operating characteristics.
Sump heaters
Sump heaters are mandatory on reversible
cycle applications given the high probability of
liquid migration back to the compressor sump
during off-cycles due to the outdoor location of
most units and operations during low ambient
conditions.
Electronic expansion
valve
The use of an electronic expansion valve requires
a specific compressor start / stop control.
A specific compressor start sequence control has
to be set when an electronic expansion valve
(EXV) is used. The sequence must be adjusted
according to the EXV step motor speed to allow
time for the EXV to open before the compressor
starts to avoid running under vacuum conditions.
The EXV should be closed at compressor stop
not to let refrigerant in liquid phase entering the
compressor. Ensure that the EXV closes when the
supply voltage to the controller is interrupted (ie
power cut off) by the use of a battery back-up.
Low load operations
The compressors should be run for a
minimum period in order to ensure that the
oil has sufficient time to properly return to the
compressor sumps and that the motor has
sufficient time to cool under conditions of lowest
refrigerant mass flows.
EXV Opened
Closed
Compressor On
Off
Discharge temperature
thermostat
Heat pumps frequently utilize high condensing
temperatures in order to achieve a sufficient
temperature rise in the medium being heated. At
the same time, they often require low evaporator
pressures to obtain sufficient temperature
differentials between the evaporator and the
outside temperature. This situation may result
in high discharge temperature; as such, it is
mandatory that a discharge gas thermostat
be installed on the discharge line to protect
the compressor from excessive temperatures.
Operating the compressor at too high discharge
temperatures can result in mechanical damage
to the compressor as well as thermal degradation
of the compressor lubricating oil and a lack of
sufficient lubrication.
The discharge gas thermostat should be set to
shut down the compressor in the event discharge
gas rises above 135°C.
38
AB237986441643en-010801
Application Guidelines
Summary of Contents for R134a
Page 2: ......