background image

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products 

already on order provided that such alterations can be made without subsequential changes being necessary

eady agreed.

All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

2 |  © Danfoss | DCS (CC) | 2018.04

8510287P01B - FRCC.PI.054.A2.02



Danfoss A/S

6430 Nordborg

Denmark

4 – Assembly

 •  

Slowly release the nitrogen holding charge 

through the schrader port.

 •  

Remove the gaskets when brazing rotolock 

connectors.

 •  Always use new gaskets for assembly.

 •  Connect the compressor to the system as soon 

as possible to avoid oil contamination from am-

bient moisture. 

 •  The PCH065 is dedicated for heat pump system 

and has been designed to work with an econo-

mizer system. The compressor injection port 

must be connected to the outlet of the interme-

diated exchanger. A solenoid must be installed 

on the injection line: this injection port must be 

closed when the compressor is stopped, while it 

is running in the non-injection area of the appli-

cation map and during inversed cycle (cooling 

mode and defrost).

 •  Avoid material entering into the system while 

cutting tubes. Never drill holes where burrs can-

not be removed.

 •  Braze with great care using state-of-the-art tech-

nique and vent piping with nitrogen gas flow.

 •  Connect the required safety and control devices. 

When the schrader port is used for this, remove 

the internal valve. Do not exceed the maximum 

tightening torque for rotolock connections:

Rotolock connections

Tightening torque

1" rotolock

80 Nm

1 1/4" rotolock

90 Nm

1 3/4" rotolock

110 Nm

2 1/4" rotolock

130 Nm

5 – Leak detection

 Never pressurize the circuit with oxygen or dry 

air. This could cause fire or explosion.

 •  Do not use dye for leak detection.

 •  Perform a leak detection test on the complete 

system.

 •  The test pressure must not exceed 1.1 x Ps value for  

LP side and PS value for HP side indicated on com-

pressor nameplate

 •  When a leak is discovered, repair the leak and 

repeat the leak detection.

6 – Vacuum dehydration

 •  Never use the compressor to evacuate the sys-

tem.

 •  Connect a vacuum pump to both the LP & HP 

sides.

 •  Pull down the system under a vacuum of 500 

µm Hg (0.67 mbar) absolute.

 •  Do not use a megohmmeter nor apply power to 

the compressor while it is under vacuum as this 

may cause internal damage.

7 – Electrical connections

 •  Switch off and isolate the main power supply. 

See overleaf for wiring details.

 •  All electrical components must be selected as 

per local standards and compressor require-

ments.

 •  Refer to page   for electrical connections details.

 •  The Danfoss scroll compressor only works cor-

rectly in one rotation direction. Line phases L1, 

L2, L3 must absolutely be connected to com-

pressor terminals T1, T2, T3 to avoid reverse 

rotation.

 •  Use ø 4.8 mm (3/16») screws and ¼» ring termi-

nals for the power connection. Fasten with 3 Nm 

torque.

 •  The compressor must be connected to earth 

with the 5 mm earth terminal screw.

8 – Filling the system

 •  Keep the compressor switched off.

 •  Fill the refrigerant in liquid phase into the conden-

ser or liquid receiver. The charge must be as close 

as possible to the nominal system charge to avoid 

low pressure operation and excessive superheat. 

Never let the pressure on LP side exceed the pres-

sure on HP side with more than 5 bar. Such pres-

sure difference could cause internal compressor 

damage.

 •  Keep the refrigerant charge below the indicated 

charge limits if possible. Above this limit; protect 

the compressor against liquid flood-back with a 

pump-down cycle or suction line accumulator.

 •  Never leave the filling cylinder connected to the 

circuit.

Compressor models Refrigerant charge limit (kg)

PCH065

13.5

9 – Verification before commissioning

 Use safety devices such as safety pressure 

switch and mechanical relief valve in compliance 

with both generally and locally applicable regu-

lations and safety standards. Ensure that they are 

operational and properly set. 

 Check that the settings of high-pressure swit-

ches and relief valves don’t exceed the maximum 

service pressure of any system component.

 • 

 

A low-pressure switch is recommended to 

avoid vacuum operation. Minimum setting for 

PCH065 is 1.7 bar g.

 •  Verify that all electrical connections are properly 

fastened and in compliance with local regula-

tions.

 •  When a crankcase heater is required, it must be 

energized at least 12 hours before initial start-

up and start-up after prolonged shutdown for 

belt type crankcase heaters (6 hours for surface 

sump heaters).

10 – Start-up

 •  Never start the compressor when no refrigerant 

is charged.

 •  All service valves must be in the open position.

 •  Balance the HP/LP pressure.

 •  Energize the compressor. It must start promptly. 

If the compressor does not start, check wiring 

conformity and voltage on terminals.

 •  Eventual reverse rotation can be detected by 

following phenomena; the compressor doesn’t 

build up pressure, it has abnormally high sound 

level and abnormally low power consumption. 

In such case, shut down the compressor imme-

diately and connect the phases to their proper 

terminals. Danfoss scroll compressor PCH065 is 

protected against reverse rotation by the exter-

nal electronic protection module. They will shut 

off automatically. 

11 – Check with running compressor

 •  Check current draw and voltage.

 •  Check suction superheat to reduce risk of slug-

ging.

 •  Observe the oil level in the sight glass for about 

60 minutes to ensure proper oil return to the 

compressor.

 •  Respect the operating limits.

 •   Check all tubes for abnormal vibration. Move-

ments in excess of 1.5 mm require corrective 

measures such as tube brackets.

 •  

When needed, additional refrigerant in liquid 

phase may be added in the low-pressure side as 

far as possible from the compressor. The compres-

sor must be operating during this process. 

 •  A minimum injection superheat of 5 K must be 

respected.

 •  Do not overcharge the system.

 •  Never release refrigerant to atmosphere.

 •  Before leaving the installation site, carry out a 

general installation inspection regarding clean-

liness, noise and leak detection.

 •  Record type and amount of refrigerant charge 

as well as operating conditions as a reference for 

future inspections.

12 – Maintenance

 Internal pressure and surface temperature 

are dangerous and may cause permanent injury.

Maintenance operators and installers require 

appropriate skills and tools. Tubing temperature 

may exceed 100°C and can cause severe burns.

 Ensure that periodic service inspections to 

ensure system reliability and as required by local 

regulations are performed.

To prevent system related compressor problems, 

following periodic maintenance is recommended:

 •   Verify that safety devices are operational and 

properly set.

 •   Ensure that the system is leak tight.

 •   Check the compressor current draw.

 •   Confirm that the system is operating in a way 

consistent with previous maintenance records 

and ambient conditions.

 •   Check that all electrical connections are still 

adequately fastened.

 •   Keep the compressor clean and verify the ab-

sence of rust and oxidation on the compressor 

shell, tubes and electrical connections.

13 - Warranty

Always transmit the model number and serial number 

with any claim filed regarding this product.

The product warranty may be void in following cases:

  •   Absence  of  nameplate.

 •  

 

External modifications; in particular, drilling, 

welding, broken feet and shock marks.

 •   Compressor opened or returned unsealed.

 •   Rust, water or leak detection dye inside the 

compressor.

 •   Use of a refrigerant or lubricant not approved by 

Danfoss.

 •   Any deviation from recommended instructions 

pertaining to installation, application or mainte-

nance.

 •   Use in mobile applications.

 •   Use in explosive atmospheric environment.

 •   No model number or serial number transmitted 

with the warranty claim. The compressor is not 

designed to withstand natural disasters such 

as earthquakes, cyclones, floods…. or extreme 

events such as fires, terrorist attacks, military 

bombardments, or explosions of any kind.

Danfoss Commercial Compressor is not liable 

for any malfunction of its product resulting from 

such events

14 – Disposal

Danfoss recommends that compressors 

and compressor oil should be recycled 

by a suitable company at its site.

Reviews: