background image

condensing unit is mounted/integrated, must 

be in accordance with the PED.

 •  Beware of hot and extremely cold components.

 •  Beware of moving components. Power supply 

should be disconnected while servicing.

9 – Filling the system

 •  Wear protective stuff like goggles and protective 

gloves.

 •  Never start the compressor under vacuum. Keep 

the compressor switched off.

 •  Before charging the refrigerant, verify that the oil 

level is between ¼ and ¾ on the compressor oil 

sight glass. If additional oil is required please refer 

to the compressors label for type of oil.

 •  Use only the refrigerant for which the unit is 

designed for.

 •  

Fill the refrigerant in liquid phase into the 

condenser or liquid receiver. Ensure a slow 

charging of the system to 4 – 5 bar for R404A / 

R507, R22, R452A or R448A/R449A and approx. 2 

bar for R134a and R513A.

 •  Do not put liquid refrigerant through suction line.

 •  It is not allowed to mix additives with the oil 

and/or refrigerant

 

• 

 

The remaining charge is done until the 

installation has reached a level of stable nominal 

condition during operation.

 •  Never leave the filling cylinder connected to the 

circuit.

10 – Verification before commissioning

 Use safety devices in compliance with both 

generally and locally applicable regulations and 

safety standards. 

 •  Verify that all electrical connections are properly 

fastened and in compliance with local regulations.

 •  When a crankcase heater is required, it must be 

energized at least 12 hours before initial start-up 

and start-up after prolonged shut-down period.

11 – Start-up

 •  Never start the unit when no refrigerant is 

charged.

 •  All service valves must be in the open position.

See picture 3.

 •  Check compliance between unit and power 

supply.

 •  Check that the crankcase heater is working.

 •  Check that the fan can rotate freely.

 • 

 

Check that the protection sheet has been 

removed from the backside of condenser.

 •  Balance the High Pressure / Low Pressure.

 •  Energize the unit. It must start promptly. If 

the compressor does not start, check wiring 

conformity, voltage on terminals and sequence 

phase.

 

• 

 

Eventual reverse rotation of  a 3-phase 

compressor can be detected by following 

phenomena; unit doesn’t start, the compressor 

doesn’t build up pressure, it has abnormally 

high sound level and abnormally low power 

consumption. In such case, shut down the unit 

immediately and connect the phases to their 

proper terminals.

 •  

If the rotation direction is correct the low 

pressure indication on the low pressure gauge 

shall show a declining pressure and the high 

pressure indication on the high pressure gauge 

shall show an increasing pressure.

12 – Check with running unit

 •  Check the fan rotation direction. Air must flow 

from the condenser towards the fan.

 •  Check current draw and voltage.

 • 

 

Check suction superheat to reduce risk of 

slugging.

 •  When a sight glass is provided observe the oil 

level at start and during operation to confirm 

that the oil level remains visible.

 •  Respect the operating limits.

 

• 

 

Check all tubes for abnormal vibration. 

Movements in excess of 1.5 mm require 

corrective measures such as tube brackets.

 •  

When needed, additional refrigerant in liquid 

phase may be added in the low-pressure side 

as far away as possible from the compressor. 

The compressor must be operating during this 

process.

 •  Do not overcharge the system.

 •  Never release refrigerant to atmosphere.

 •  Before leaving the installation site, carry out 

a general installation inspection regarding 

cleanliness, noise and leak detection.

 •  Record type and amount of refrigerant charge 

as well as operating conditions as a reference for 

future inspections.

13 – Maintenance

 Always switch off the unit at main switch 

before remove fan panel.

 Internal pressure and surface temperature are 

dangerous and may cause permanent injury.

Maintenance operators and installers require 

appropriate skills and tools. Tubing temperature 

may exceed 100°C and can cause severe burns.

 Ensure that periodic service inspections to 

ensure system reliability and as required by local 

regulations are performed.

To prevent system related problems, following

Periodic  maintenance is recommended:

 •  Verify that safety devices are operational and 

properly set.

 •  Ensure that the system is leak tight.

 •  Check the compressor current draw.

 •  Confirm that the system is operating in a way 

consistent with previous maintenance records 

and ambient conditions.

 •  Check that all electrical connections are still 

adequately fastened.

 •  Keep the unit clean and verify the absence of 

rust and oxidation on the unit components, 

tubes and electrical connections.

The condenser must be checked at least once 

a year for clogging and be cleaned if deemed 

necessary. Access to the internal side of the 

condenser takes place through the fan panel. 

Microchannel coils tend to accumulate dirt on 

the surface rather than inside, which makes them 

easier to clean than fin-&-tube coils.

 •  Switch off the unit at main switch before remove 

any panel from the condensing unit.

 •  Remove surface dirt, leaves, fibres, etc. with 

a vacuum cleaner, equipped with a brush or 

other soft attachment. Alternatively, blow 

compressed air through the coil from the inside 

out, and brush with a soft bristle. Do not use a 

wire brush. Do not impact or scrape the coil with 

the vacuum tube or air nozzle.

If the refrigerant system has been opened, the 

system has to be flushed with dry air or nitrogen 

to remove moisture and a new filter drier has to

be installed. If evacuation of refrigerant has to 

be done, it shall be done in such a way that no 

refrigerant can escape to the environment.

14 - Warranty

Always transmit the model number and serial 

number with any claim filed regarding this product.

The product warranty may be void in following 

cases:

 •  Absence of nameplate.

 •  

External modifications; in particular, drilling, 

welding, broken feet and shock marks.

 •  Compressor opened or returned unsealed.

 •  Rust, water or leak detection dye inside the 

compressor.

 •  Use of a refrigerant or lubricant not approved by 

Danfoss.

 •  Any deviation from recommended instructions 

pertaining to installation, application or 

maintenance.

 •  Use in mobile applications.

 •  Use in explosive atmospheric environment.

 •  No model number or serial number transmitted 

with the warranty claim.

15 – Disposal

Danfoss recommends that condensing 

units and oil should be recycled by a 

suitable company at its site.

16 -  Fan speed controller setting for R134a/R513A refrigerant

FSC type

Fan speed Controller

Spare part number

Refrigerant 

letter

For Refrigerant

Factory 

setting

Action required

XGE-4C

061H3140

Q

R404A/R452A/R507

19 bar

360°=1 turn = Approx 1.5 bar 

(Clockwise rotation = 

Increase pressure setting,

 Counter clockwise rotation =  

Decrease pressure setting)

V

R404A/R507/R448A/R449A/R452A

If refrigerant used is R134a  or R513A

Turn the adjusting screw towards counter-

clockwise (-) by 6 turns to set the pressure 

from 19 bar to 10 bar.

 

Controller will be damaged if this warning is not followed 

When Fan speed Controller is at factory setting (19 bar):  

- Maximum number of turns allowed in clockwise direction (+) = 4.

- Maximum number of turns allowed in anti-clockwise direction (-) = 6

Instructions

 118A0665C - AN238286441930en-001401 | 3

© Danfoss | DCS (CC) | 2020.06

Summary of Contents for Optyma OP-MPME048MTW02E

Page 1: ...number C Application Protection D Refrigerant E Housing Service Pressure F Supply voltage Locked Rotor Ampere Maximum Current Consumption G Serial Number and bar code For exact values please refer name plate in unit Name plate L M N O L mm M mm N mm O mm 250 650 550 550 Picture 1 Minimum mounting distances Designation system for the Optyma Slim Pack range OP MPVE 034 ML W10 E 1 2 3 4 5 6 7 8 1 App...

Page 2: ...ystem as soon as possible toavoidoilcontaminationfromambientmoisture Avoid material entering into the system while cutting tubes Never drill holes where burrs cannot be removed Braze with great care using state of the art technique and vent piping with nitrogen gas flow Connect the required safety and control devices When the schrader port is used for this remove the internal valve It is recommend...

Page 3: ...nt of refrigerant charge as well as operating conditions as a reference for future inspections 13 Maintenance Always switch off the unit at main switch before remove fan panel Internal pressure and surface temperature are dangerous and may cause permanent injury Maintenance operators and installers require appropriate skills and tools Tubing temperature may exceed 100 C and can cause severe burns ...

Page 4: ...d Differential Voltage Use Copper wire only Tightening torque 20lb in When used acc to UL regulations HP LP man reset LP aut reset Manual test Convertible reset Manual reset LP auto HP man LP auto HP auto LP diff Manual reset Test Test Resist Load Pilot duty AC DC Max 50 VA 17 Dual Pressure Switch factory settings Refrigerants High pressure settings bar g Low pressure settings bar g ON OFF ON OFF ...

Page 5: ...84 098 OP MPVE068 080 093 099 108 OP LPQE048 068 OP MPVE034 046 057 OP MPME048 060 Chassis B2 Chassis B3 OptymaTM Slim Pack OptymaTM Slim Pack Instructions 118A0665C AN238286441930en 001401 5 Danfoss DCS CC 2020 06 ...

Page 6: ...Code G version W02 OP MPVE034 046 OP MPME048 060 OP MPZE060 Code G version W02 OP MPVE068 080 093 WD1 WD2 Instructions 6 AN238286441930en 001401 118A0665C Danfoss DCS CC 2020 06 ...

Page 7: ... E version W02 OP MPVE034 046 068 080 099 108 OP MPME048 060 Code G version W04 OP MPVE034 046 057 OP MPME048 060 LPQE048 068 WD3 WD4 Instructions 118A0665C AN238286441930en 001401 7 Danfoss DCS CC 2020 06 ...

Page 8: ... version W04 OP MPVE034 046 057 068 080 099 108 OP MPME048 060 OP LPQE048 067 068 084 098 Code G version W04 OP MPVE068 080 093 WD5 WD6 Instructions 8 AN238286441930en 001401 118A0665C Danfoss DCS CC 2020 06 ...

Page 9: ...Code E version W08 OP MPVE046 068 080 099 108 Code G version W10 OP MPVE034 046 057 OP LPQE048 068 WD7 WD8 Instructions 118A0665C AN238286441930en 001401 9 Danfoss DCS CC 2020 06 ...

Page 10: ...Code E version W10 OP MPVE046 057 OP LPQE048 068 Code G Version W10 OP MPVE068 080 WD9 WD10 Instructions 10 AN238286441930en 001401 118A0665C Danfoss DCS CC 2020 06 ...

Page 11: ... Fuse control circuit H1 Low pressure alarms H2 High pressure alarms M1 Compressor M2 Fan motor K1 K1 Contactor K2 Start relay K2 Compressor contactor K3 Fan contactor Q1 Main switch R1 R2 Bleeder resistor S1 Room thermostat S2 Discharge gas thermostat X1 Terminals Y1 Solenoid valve Legend BK black BU blue BN brown GY grey RD red WH white Code E Version W10 OP LPQE067 084 098 OP MPVE068 080 099 10...

Page 12: ...serves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trade marks in this material are property of the respective companies Danfoss and the Danfoss logotype are trademarks of Danfoss A S All rights reserved ...

Reviews: