background image

© Danfoss | DCS (CC) | 2022.11

Instructions

2 | AN433834055224en-010101

5 – Leak detection

 Never pressurize the circuit with oxygen 

or dry air. This could cause fire or explosion.
•  Do not use dye for leak detection.
•  Perform a leak detection test on the 

complete system.

•  The maximum test pressure is 32 bar.
•  When a leak is discovered, repair the leak 

and repeat the leak detection.

6 – Vacuum dehydration

•  Never use the compressor to evacuate the 

system.

•  Connect a vacuum pump to both the LP & 

HP sides.

•  Pull down the system under a vacuum of 

500 μm Hg (0.67 mbar) absolute.

•  Do not use a megohmmeter nor apply 

power to the compressor while it is under 
vacuum as this may cause internal damage.

7 – Electrical connections

•  Switch off and isolate the main power 

supply.

•  Ensure that power supply cannot be 

switched on during installation.

•  All electrical components must be 

selected as per local standards and unit 
requirements.

•  Refer to wiring diagram for electrical 

connections details.

•  Ensure that the power supply corresponds 

to the unit characteristics and that the 
power supply is stable (nominal voltage 
±10% and nominal frequency ±2,5 Hz).

•  Dimension the power supply cables 

according to unit data for voltage and 
current.

•  Protect the power supply and ensure 

correct earthing.

•  Make the power supply according to local 

standards and legal requirements.

•  The unit is equipped with high and low 

pressure switches, which directly cut the 
power supply to the compressor in case of 
activation. 

•  For units with a 3-phase compressor, 

correct phase sequence for compressor 
rotation direction shall be observed.

•  Determine the phase sequence by using a 

phase meter in order to establish the phase 
orders of line phases L1, L2 and L3.

•  Connect line phases L1, L2 and L3 to main 

switch terminals T1, T2 and T3 respectively.

8 – Filling the system

•  Wear protective stuff like goggles and 

protective gloves.

•  Never start the compressor under vacuum. 

Keep the compressor switched off.

•  Before charging the refrigerant, verify that 

the oil level is between ¼ and ¾ on the 
compressor oil sight glass. If additional oil 
is required please refer to the compressors 
label for type of oil.

•  Use only the refrigerant for which the unit 

is designed for.

•  Fill the refrigerant in liquid phase into the 

condenser or liquid receiver. Ensure a slow 
charging of the system to 4 – 5 bar.

•  Do not put liquid refrigerant through 

suction line.

•  It is not allowed to mix additives with the 

oil and/or refrigerant

•  The remaining charge is done until the 

installation has reached a level of stable 
nominal condition during operation.

•  Never leave the filling cylinder connected 

to the circuit.

9 – Verification before commissioning

 Use safety devices such as safety pressure 

switch and mechanical relief valve in 
compliance with both generally and locally 
applicable regulations and safety standards. 
Ensure that they are operational and 
properly set.

 Check that the settings of high-pressure 

switches and relief valves don’t exceed the 
maximum service pressure of any system 
component.
•  Verify that all electrical connections are 

properly fastened and in compliance with 
local regulations.

•  When a crankcase heater is required, it 

must be energized at least 12 hours before 
initial start- up and start-up after prolonged 
shut-down period.

10 – Start-up

•  Never start the unit when no refrigerant is 

charged.

•  All service valves must be in the open 

position.

•  Check compliance between unit and 

power supply.

•  Check that the crankcase heater is working.
•  Check that the fan can rotate freely.
•  Check that the protection sheet has been 

removed from the backside of condenser.

•  Balance the HP/LP pressure.
•  Energize the unit. It must start promptly.  

If  the compressor does not start, check 
wiring conformity, voltage on terminals 
and sequence phase.

•  Eventual reverse rotation of a 3-phase 

compressor can be detected by following 
phenomena; unit doesn’t start, the 
compressor doesn’t build up pressure, 
it has abnormally high sound level and 
abnormally low power consumption. In 
such case, shut down the unit immediately 
and connect the phases to their proper 
terminals.

•  If the rotation direction is correct the low 

pressure indication on the low pressure 
gauge shall show a declining pressure and 
the high pressure indication on the high 
pressure gauge shall show an increasing 
pressure.

11 – Check with running unit

•  Check the fan rotation direction. Air must 

flow from the condenser towards the fan.

•  Check current draw and voltage.
•  Check suction superheat to reduce risk of 

slugging.

•  When a sight glass is provided observe the 

oil level at start and during operation to 
confirm that the oil level remains visible.

•  Respect the operating limits.
•  Check all tubes for abnormal vibration. 

Movements in excess of 1.5 mm require 
corrective measures such as tube brackets.

•  When needed, additional refrigerant in 

liquid phase may be added in the low-
pressure side as far away as possible from 
the compressor. The compressor must be 
operating during this process.

•  Do not overcharge the system.
•  Never release refrigerant to atmosphere.
•  Before leaving the installation  site,  carry 

out a general installation inspection 
regarding cleanliness, noise and leak 
detection.

•  Record type and amount of refrigerant 

charge as well as operating conditions as a 
reference for future inspections.

12 – Maintenance

 Always switch off the unit at main switch 

before remove fan panel.

 Internal pressure and surface temperature 

are dangerous and may cause permanent 
injury. Maintenance operators and installers 
require appropriate skills and tools. Tubing 
temperature may exceed 100°C and can 
cause severe burns.

 Ensure that periodic service inspections to 

ensure system reliability and as required by 
local regulations are performed.
To prevent system related problems, 
following Periodic maintenance is 
recommended:
•  Verify that safety devices are operational 

and properly set.

•  Ensure that the system is leak tight.
•  Check the compressor current draw.
•  Confirm that the system is operating in a 

way consistent with previous maintenance 
records and ambient conditions.

•  Check that all electrical connections are still 

adequately fastened.

•  Keep the unit clean and verify the absence of 

rust and oxidation on the unit components, 
tubes and electrical connections.

The condenser must be checked at least 
once   a year for clogging and be cleaned if 
deemed necessary. Access to the internal 
side of the condenser takes place through 
the fan panel. Microchannel coils tend to 
accumulate dirt on the surface rather than 
inside, which makes them easier to clean 
than fin-&-tube coils.

Reviews: