1 – Introduction

These instructions pertain to Optyma 
Commercial D48 Version used for 
refrigeration systems. They provide 
necessary information regarding safety and 
proper usage of this product.
The condensing unit includes following:
•  Liquid Receiver
•  Filter Drier
•  Sight Glass
•  Low / High Pressure Switch - KP15
•  Suction Filter
•  Oil Separator
•  Solenoid Valve
•  Crankcase Heater
•  Quick connections - Suction / Discharge 

Valve

•  Electrical Box - IP65 with LED signal
•  2 X Fan Speed Controler
•  Housing

2 – Handling and storage

•  It is recommended not to open the 

packaging before the unit is at the final 
place for installation.

•  Handle the unit with care. The packaging 

allows for the use of a forklift or pallet jack. 
Use appropriate and safe lifting equipment.

•  Store and transport the unit in an upright 

position.

•  Don’t expose the packaging to rain or 

corrosive atmosphere.

•  Store the unit between -35°C and 50°C.
•  After unpacking, check that the unit is 

complete and undamaged.

3 – Installation precautions

 Do not braze as long the condensing unit 

is under pressure.

 Never place the unit in a flammable 

atmosphere.

 IPlace the unit in such a way that it is not 

blocking or hindering walking areas, doors, 
windows or similar.
•  Ensure adequate space around the unit for 

air circulation and to open doors. 

•  Avoid installing the unit in locations which 

are daily exposed to direct sunshine for 
longer periods.

•  Avoid installing the unit in aggressive and 

dusty environments.

•  Ensure a foundation with horizontal surface 

(less than 3° slope), strong and stable 
enough to carry the entire unit weight and 
to eliminate vibrations and interference.

•  The unit ambient temperature may not 

exceed 50°C during off cycle.

•  Ensure that the power supply corresponds 

to the unit characteristics (see nameplate).

•  When installing units for HFC refrigerants, 

use equipment specifically reserved for 
HFC refrigerants which was never used for 
CFC or HCFC refrigerants.

•  Use clean and dehydrated refrigeration-

grade copper tubes and silver alloy brazing 
material.

•  Use clean and dehydrated system 

components.

•  The suction piping connected to 

the compressor must be flexible in 
3 dimensions to dampen vibrations. 
Furthermore, piping has to be done in such 
a way that oil return for the compressor is 
ensured and the risk of liquid slug over in 
compressor is eliminated.

4 – Installation

•  The unit must be securely installed on a 

stable and rigid support and fixed from the 
beginning.

•  It is recommended to install the unit on 

rubber grommets or vibration dampers 
(not supplied).

•  Slowly release the nitrogen holding charge 

through the schrader port.

•  Connect the unit to the system as soon as 

possible to avoid oil contamination from 
ambient moisture.

•  Avoid material entering into the system 

while cutting tubes. Never drill holes where 
burrs cannot be removed.

•  Braze with great care using state-of-the-art 

technique and vent piping with nitrogen 
gas flow.

•  Connect the required safety and control 

devices. When the schrader port is used for 
this, remove the internal valve.

•  It is recommended to insulate the suction 

pipe up to the compressor inlet with 19mm 
thick insulation.

Instructions

Optyma™ Commercial D48 Version

OP-HGZXXXD48E

    OP-HGZ  

080           D48     E

1 2 3

4

5 6

7

1

Application

 

H = HBP/Universal

2

Design

 

G = Condensing unit with hermetic compressor, two fans

3

Compressor Oil

 

Z = Polyolester oil (POE) 175PZ, Reciprocating Compressor MTZ

4

Compressor type and model

MTZ Series for hermetic MBP

5

Platform

 

D = Micro-channel technology

6

Product configuration

48

7

Electrical code:

E = 400V 3Ph 50Hz Comp. & 230V 1Ph Fan Motor

 The condensing unit must only be used for its designed purpose(s) and 

within its scope of application.

 Under all circumstances, the EN378 (or other applicable local safety 

regulation) requirements must be fulfilled.

 The condensing unit is delivered under nitro- gen gas pressure (1 bar) 

and hence it cannot be connected as it is; refer to the «installation» section 
for further details.

 The condensing unit must be handled with caution in the vertical posi-

tion (maximum offset from the vertical: 15°)