background image

6

FRCC.EI.019.A2.02 © Danfoss Commercial Compressors 06/12

Instructions

P

U

B1

P

U

B2

T>

S1

K1

C1

M

1~

M1

K2

M

1~

M2

R5

P<

B4

P>

B3

K2

F1

N

L1

I > I > I >

2

4 6

Q1

CO

M

NC NO

R1 R2 R3

C3

WD1

DI1 DI2

S1

S2

S3

S4

S5

AO1

Display

EKA

S6

+ s

Alarm Comp.

Fan

CCH

AUX

230Vac

230Vac

L

L

N PE

PE

DI3

230Vac

ou

t

Supply

Fan

Optyma Plus Controller

RS

48

5

A+ B-

A1

R4

Code G : OP-LPHM018 & OP-MPHM007-010-012-015

A1 :

 Optyma Plus Controller  

B1 : 

Condensing Pressure Transducer 

B2 :

 Suction Pressure Transducer 

B3 :

 High Pressure Switch

B4 :

 Low Pressure Switch 

C1 :

 Start Capacitor (Compressor) 

C3 :

 Run Capacitor (Fan) 

F1 :

 Fuse (Control Circuit) 

K1 :

 Start Relay 

K2 :

 Contactor 

M1 :

 Compressor 

M2 :

 Fan Motor 

Q1 :

 Main Switch 

R1 :

 Ambient Temp. Sensor 

R2 :

 Discharge Temp. Sensor 

R3 :

 Suction Temp. Sensor

R4 :

 Auxiliary Temp. Sensor (optional) 

R5 :

 Crankcase Heater 

S1 : 

Room Thermostat (optional) 

Supply :

 Supply  

Fan :

 Fan  

Alarm :

 Alarm 

Comp. :

 Compressor

CCH :

 Crankcase Heater  

Aux :

 Auxiliary

a  vacuum  cleaner,  equipped  with  a  brush  or 
other  soft  attachment.  Alternatively,  blow 
compressed air through the coil from the in-
side out, and brush with a soft bristle. Do not 
use a wire brush. Do not impact or scrape the 
coil with the vacuum tube or air nozzle.

  •  Before closing the fan door, turn the fan blade 

in  the  position  shown  in  picture  6,  to  avoid 
that the door hits the fan.

If  the  refrigerant  system  has  been  opened,  the 
system has to be lushed with dry air or nitrogen 
to remove moisture and a new ilter drier has to 
be installed. If evacuation of refrigerant has to be 
done, it shall be done in such a way that no refri-
gerant can escape to the environment.

15 - Warranty

Always  transmit  the  model  number  and  serial 
number with any claim iled regarding this pro-
duct.
The product warranty may be void in following 
cases:
  •  Absence of nameplate.
  •  External  modiications;  in  particular,  drilling, 

welding, broken feet and shock marks.

  •  Compressor opened or returned unsealed.
  •  Rust,  water  or  leak  detection  dye  inside  the 

compressor.

  •  Use of a refrigerant or lubricant not approved 

by Danfoss.

  •  Any  deviation  from  recommended  instruc-

tions pertaining to installation, application or 

maintenance.

  •  Use in mobile applications.
  •  Use in explosive atmospheric environment.
  •  No model number or serial number transmit-

ted with the warranty claim.

16 – Disposal

Danfoss recommends that condensing 
units  and  oil  should  be  recycled  by  a 
suitable company at its site.

Summary of Contents for OP-LPHM018

Page 1: ...1 FRCC EI 019 A2 ML Danfoss Commercial Compressors 06 12 Instructions OP LPHM018 026 OP MPHM007 010 012 015 018 OP LPHM048 068 OP MPHM026 034 OP MPUM034 046 OP MPGM034 ...

Page 2: ...P VIEW 966 UNIT HEIGHT FRONT VIEW 35 SWITCH HEIGHT MOUNTING Ø12 HOLE FOR SIGHT 50 TYP DISPLAY CONTROLLER PORTS CABLE ENTRY LIQUID PORT SUCTION PORT MCHX RH VIEW BACK VIEW ISO VIEW LH VIEW 479 MOUNTING C C 80 GLASS 1702 MOUNTING C C OP LPHM215 271 OP MPUM125 162 Instructions OP LPHM096 136 OP MPUM068 080 107 ...

Page 3: ...se instructions and sound refrigeration engineering practice relating to installation commissioning maintenance and service A Model B Code number C Refrigerant D Supply voltage Locked Rotor Ampere Maxi mum Current Consumption E Application F Protection G Housing Service Pressure H Serial Number and bar code I Mounting holes for stack mounting J Electronic controller display K Main switch L Cable e...

Page 4: ... in picture 2 Slowly release the nitrogen holding charge through the schrader port Connect the unit to the system as soon as pos sible to avoid oil contamination from ambient moisture Avoid material entering into the system while cutting tubes Never drill holes where burrs cannot be removed Braze with great care using state of the art technique and vent piping with nitrogen gas low Connect the req...

Page 5: ...s is provided observe the oil level at start and during operation to conirm that the oil level remains visible Respect the operating limits Check all tubes for abnormal vibration Move ments in excess of 1 5 mm require corrective measures such as tube brackets When needed additional refrigerant in liquid phase may be added in the low pressure side as far as possible from the compressor The com pres...

Page 6: ...stle Do not use a wire brush Do not impact or scrape the coil with the vacuum tube or air nozzle Before closing the fan door turn the fan blade in the position shown in picture 6 to avoid that the door hits the fan If the refrigerant system has been opened the system has to be lushed with dry air or nitrogen to remove moisture and a new ilter drier has to be installed If evacuation of refrigerant ...

Page 7: ...at optional X1 Terminal Supply Supply Fan Fan Alarm Alarm Comp Compressor CCH Crankcase Heater Aux Auxiliary P U B1 P U B2 T S1 M 1 M2 R5 P B4 P B3 K2 F1 N L1 I I I 2 4 6 Q1 COM NC NO K2 C1 C2 M 1 M1 K1 R1 R2 R3 C3 WD2 DI1 DI2 S1 S2 S3 S4 S5 AO1 Display EKA S6 s Alarm Comp Fan CCH AUX 230Vac 230Vac L L N PE PE DI3 230Vac out Supply Fan Optyma Plus Controller RS485 A B A1 R4 Code G OP LPHM026 048 0...

Page 8: ...Plus Controller RS485 A B A1 M 1 M2 M 1 M3 C3 C4 L1 L2 L2 N N X1 S2 0 10V U L N A2 A1 Optyma Plus Controller A2 Fan Speed Controller B1 Condensing Pressure Transducer B2 Suction Pressure Transducer B3 High Pressure Switch B4 Low Pressure Switch C3 Run Capacitor Fan 1 C4 Run Capacitor Fan 2 F1 Fuse Control Circuit K2 Contactor M1 Compressor M2 Fan Motor 1 M3 Fan Motor 2 Q1 Main Switch R1 Ambient Te...

Reviews: