background image

1 - Introduction

These instructions pertain to the Maneurop® 

MT, MTZ & NTZ compressors used for refrigera-

tion systems. They provide necessary informa-

tion regarding safety and proper usage of this 

product.

2 – Handling and storage 

 •  Handle the compressor with care. Use the 

dedicated handles in the packaging. Use the 

compressor lifting lug and use appropriate 

and safe lifting equipment.

 •  Store and transport the compressor in an 

upright position.

 •  Store the compressor between -35°C and 

50°C.

 •   Don’t expose the compressor and the packa-

ging to rain or corrosive atmosphere.

3 – Safety measures before assembly

 Never use the compressor in a flammable 

atmosphere.

 •  The compressor ambient temperature may 

not exceed 50°C during off-cycle.

 •  Mount the compressor on a horizontal flat 

surface with less than 3° slope.

  •   Verify that the power supply corresponds to 

the compressor motor characteristics (see 

nameplate).

 •   When installing MTZ or NTZ, use equipment 

specifically reserved for HFC refrigerants 

which was never used for CFC refrigerants.

 •  

Use clean and dehydrated refrigeration-

grade copper tubes and silver alloy brazing 

material.

  •   Use clean and dehydrated system components.

 •  The piping connected to the compressor must 

be flexible in 3 dimensions to dampen vibrations.

4 - Assembly

 •  Slowly release the nitrogen holding charge 

through the schrader port.

 •  Remove the gaskets when brazing rotolock 

connectors.

  •   Always use new gaskets for assembly.

 •  Connect the compressor to the system as 

soon as possible to avoid oil contamination 

from ambient moisture.

  •   Avoid material entering into the system while 

cutting tubes. Never drill holes where burrs 

cannot be removed.

  •   Braze with great care using state-of-the-art tech-

nique and vent piping with nitrogen gas flow.

 •  Connect the required safety and control de-

vices. When the schrader port is used for this, 

remove the internal valve.

5 – Leak detection

 Never pressurize the circuit with oxygen or 

dry air. This could cause fire or explosion.

  •   Do not use dye for leak detection.

  •   Perform a leak detection test on the complete 

system.

 •   The low side test pressure must not exceed 25 

bar.

  •   When a leak is discovered, repair the leak and 

repeat the leak detection.

6 – Vacuum dehydration

 •  Never use the compressor to evacuate the 

system.

  •   Connect a vacuum pump to both the LP & HP 

sides.

 •   Evacuate the system to a pressure of 500 µm 

Hg (0.67 mbar) absolute.

  •   Do not use a megohmmeter nor apply power 

to the compressor while it is under vacuum as 

this may cause internal damage.

7 – Electrical connections

  •   Switch off and isolate the main power supply. 

See overleaf for wiring details.

 •  The compressor is protected against excess 

current and temperature by an internal over-

load protector. Follow local regulations regar-

ding power line protection. The compressor 

must be connected to earth.

  •   All electrical components must be selected as per 

local standards and compressor requirements.

8 – Filling the system

  •   Keep the compressor switched off.

 •  Fill the refrigerant in liquid phase into the 

condenser or liquid receiver. The charge must 

be as close as possible to the nominal system 

charge to avoid low pressure operation and 

excessive superheat.

 •   Keep the refrigerant charge below 2.5 kg per 

compressor cylinder if possible. Above this 

limit; protect the compressor against liquid 

flood-back with a pump-down cycle or suc-

tion line accumulator.

 •   Never leave the filling cylinder connected to 

the circuit to avoid overfilling.

9 – Verification before commissioning

 Use safety devices such as safety pressure 

switch and mechanical relief valve in com-

pliance with both generally and locally appli-

cable regulations and safety standards. Ensure 

that they are operational and properly set. 

  Check that the settings of high-pressure 

switches and relief valves don’t exceed the 

maximum service pressure of any system com-

ponent.

 •  A low-pressure switch is recommended to 

avoid vacuum operation. Minimum setting 

0.1 bar.

 •   Verify that all electrical connections are pro-

perly fastened and in compliance with local 

regulations.

  •   When a crankcase heater is required, it must be 

energized at least 12 hours before initial start-

up and start-up after prolonged shutdown.

10 – Start-up

  •   All service valves must be in the open position.

  •   Balance the HP/LP pressure.

 •  

Energize the compressor. It must start 

promptly. If it does not, switch it off 

immediately. Possible single phase miswiring 

can cause burn-out within seconds.

  •   If the compressor does not start, check wiring 

conformity and voltage on terminals.

 •   If the internal overload protector trips out, it 

must cool down to 60°C to reset. Depending 

on ambient temperature, this may take up to 

several hours.

11 – Check with running compressor

  •   Check current draw and voltage.

 •  Check suction superheat to reduce risk of 

slugging.

  •   When a sight glass is provided observe the oil 

level at start and during operation to confirm 

that the oil level remains visible.

  •   Respect the operating limits as printed overleaf.

  •   Check all tubes for abnormal vibration. Move-

ments in excess of 1.5 mm require corrective 

measures such as tube brackets.

 •  

When needed, additional refrigerant in 

the liquid phase may be added in the 

low-pressure side as far as possible from 

the compressor. The compressor must be 

operating during this process.

  •   Do not overcharge the system.

  •   Never release refrigerant to the atmosphere.

 •  Before leaving the installation site, carry out 

a general installation inspection regarding 

cleanliness, noise and leak detection.

  •   Record type and amount of refrigerant charge 

as well as operating conditions as a reference 

for future inspections.

12 - Maintenance

 Internal pressure and surface temperature 

are dangerous and may cause permanent injury.

Maintenance operators and installers require 

appropriate skills and tools. Tubing temperature 

may exceed 100°C and can cause severe burns.

 Ensure that periodic service inspections to 

ensure system reliability and as required by local 

regulations are performed.

To prevent system related compressor pro-

blems, following periodic maintenance is recom-

mended:

 •   Verify that safety devices are operational and 

properly set.

  •   Ensure that the system is leak tight.

  •   Check the compressor current draw.

  •   Confirm that the system is operating in a way 

consistent with previous maintenance re-

cords and ambient conditions.

 •  Check that all electrical connections are still 

adequately fastened.

  •   Keep the compressor clean and verify the ab-

sence of rust and oxidation on the compres-

sor shell, tubes and electrical connections.

13 - Warranty

Always transmit the model number and serial num-

ber with any claim filed regarding this product.

The product warranty may be void in following 

cases:

  •   Absence of nameplate.

 •  External modifications; in particular, drilling, 

welding, broken feet and shock marks.

  •   Compressor opened or returned unsealed.

 •  Rust, water or leak detection dye inside the 

compressor.

  •   Use of a refrigerant or lubricant not approved 

by Danfoss.

 •  Any deviation from recommended instruc-

tions pertaining to installation, application or 

maintenance.

  •   Use in mobile applications.

  •   Use in explosive atmospheric environment.

 •   No model number or serial number transmit-

ted with the warranty claim.

14 – Disposal

Danfoss recommends that compressors 

and compressor oil should be recycled 

by a suitable company.

Instructions

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on 

order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.

All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

FRCC.EI.002.A3.02 - May 2014 

Copyright Danfoss Commercial Compressors - DSS - 05/14

Reviews: