FRCC.EI.002.A3.02 © Danfoss Commercial Compressors 05/14
The compressor must only be used
for its designed purpose(s) and within
its scope of application (refer to «ope-
rating limits»).
Consult Application guidelines and da-
tasheet available from cc.danfoss.com
The compressor is delivered under
nitrogen gas pressure (between
0.3 and 0.7 bar) and hence can-
not be connected as is; refer to
the «assembly»
section for further
details.
Under all circumstances, the
EN378 (or other applicable local
safety regulation) requirements
must be fulfilled.
The compressor must be han-
dled with caution in the vertical
position (maximum offset from
the vertical : 15°)
Operating limits
MT
MTZ
NTZ
R22
R417A
R407A**
R407C
R407F**
R134a
R404A / R507 R404A / R507
160P
160PZ *
160PZ
160PZ
160PZ
160PZ
160PZ
160PZ
High side pressure range
bar (g)
10.9 - 27.7
9.4 - 25.5
11.6 - 25.8
12.5 - 29.4
12.1 - 24
7.9 - 22.6
13.2 - 27.7
13.2 - 27.7
Low side pressure range
bar (g)
1.0 - 7.0
0.55 - 5.7
0.90 - 5.94
1.4 - 6.6
0.99 - 6.25
0.6 - 4.7
1.0 - 7.2
0.1 - 3.3
Discharge temperature must be kept lower than 130°C
* When MT compressors are used with R417A, the factory charged mineral oil 160P must be replaced by polyolester oil 160PZ.
** R407A and R407F are not used for China Market.
C
E
D
A
B
F
1" :
80 Nm
1"1/4 : 90 Nm
1"3/4 : 110 Nm
Installation and servicing of the compressor by qualified personnel only. Follow these instructions and sound refrigeration engineering
practice relating to installation, commissioning, maintenance and service.
C
R
S
IOL
230 V
RC
TH
C
S
R
IOL
1
~
PSC
1
~
CSR
3
~
230 V
SR
5
2
1
C
S
R
IOL
TH
RC
SC
C
R
S
Never operate compressors without
terminal cover fitted
A
: Model number
D
: Supply voltage, Starting current & Maximum current
B
: Serial number
E
: Housing service pressure
C
: Refrigerant
F
: Factory charged lubricant
TH : Thermostat
SR : Start Relay
SC : Start Capacitor
RC : Run Capacitor
IOL : Motor Protector
HM8-40
15 Nm
15 Nm
HM12-50
INStRuCtIoNS
Mt / MtZ / NtZ CoMPRESSoRS