MPCAN Receiver Faceplates

400-900 MHz and 2.4GHz Faceplates

MPCAN400-900MHz LED troubleshooting

LED

Characteristic

Description

Action

POWER

Green; pulsing

Receiver is starting up

Wait until start-up process is

finished

HARDOK

Green; continuous

Receiver hardware OK

Operate

Red; pulsing

EEPROM error; data corruption; CAN bus error (if CANERR

activates)

Reprogram EEPROM

Red; other

Electronic board hardware breakdown

Replace electronic board

SIGNAL

LED off

No radio signal detected

-

LED on + transmitter switched

off

Radio channel occupied

Change transmitter's frequency

channel

LED on + DATA switched off

Radio channel occupied by non Danfoss system

Change transmitter's frequency

channel

DATA

Green; pulsing

Receiving good frames

OK

ID

LED off + DATA LED on

No valid ID; Danfoss system nearby

If channel not occupied, check

chosen ID in the transmitter or

reset the receiver

LED on + SIGNAL LED on +

DATA LED on

Valid frames received from the transmitter; correct link

OK

RELAY

Green

STOP relay activated

-

ORDER

Green

-

-

CAN_RUN

Green; switched on

Operational state

OK

Green; pulsing

Activating operational state

-

CAN_ERR

Red; switched on

CAN bus error

Check CAN connection

Red; pulsing

No bus connection

Check bus termination

resistance

LED off

Correct communication

OK

User Manual

MPCAN Receiver

Troubleshooting

 

12 | 

©

 Danfoss | March 2022

BC292573933619en-000201

Summary of Contents for MPCAN

Page 1: ...User Manual Remote Control MPCAN Receiver www danfoss com...

Page 2: ...revisions Date Changed Rev March 2022 Updated safety instructions and technical descriptions 0201 January 2019 Rebranded to Danfoss Power Solutions 0101 User Manual MPCAN Receiver 2 Danfoss March 202...

Page 3: ...detailed description 7 Installation Receiver installation 9 Input and output configuration 10 STOP category 3 PLe 10 Pinout 11 Troubleshooting MPCAN Receiver Faceplates 12 MPCAN400 900MHz LED troubles...

Page 4: ...e brouillage et 2 l utilisateur de l appareil doit accepter tout brouillage radio lectrique subi m me si le brouillage est susceptible d en compromettre le fonctionnement MPCAN General Safety The foll...

Page 5: ...use Always press STOP before plugging in tether cable if applicable Remove the Tether connection on the transmitter First if applicable Do not operate product when visibility is limited Make sure prod...

Page 6: ...MPCAN dimensions Dimensions in mm 15 75 35 99 29 20 133 03 R 3 70 42 27 118 73 101 60 324 52 92 25 User Manual MPCAN Receiver Technical description 6 Danfoss March 2022 BC292573933619en 000201...

Page 7: ...10 Internal fuse 7 5A MPCAN detailed description Technical data Specification Value Stop function 400 900 MHz Cat 3 PLd Stop Function 2 4 GHz Cat 4 PLe Ingress protection IP65 NEMA4 Frequency band ER...

Page 8: ...uts 4 Proportional inputs N A Reponse time 100ms Maximum Total output current 7 5A Operating temperature range 20 C to 70 C 4 F to 158 F Storage Temperature Range 24h 25 C to 75 C 13 F to 167 F Storag...

Page 9: ...is recommended to use an extended antenna in a clear location only for models that allow an antenna In areas of high vibration the use of dampers is advised 7 8 9 10 11 CANL 12 GND 6 5 K4 IN4 4 3 2 C...

Page 10: ...ther at the same time The MPCAN includes a 7 5A internal fuse A1 A7 A8 A6 A5 IN1 IN2 IN3 IN4 Internal Vcc MPCAN STOP category 3 PLe Stop function is performed by two relays in series or parallel A10 a...

Page 11: ...A3 A9 A4 CM NO STOP2 STOP1 NO CM MPCAN pinout 7 8 9 10 11 12 6 5 4 3 2 1 Pin Description 1 Vin 2 CANH 3 KSTOP 2 2 4 KSTOP 1 2 5 K4 IN4 6 K3 IN3 7 K1 IN1 8 K2 IN2 9 KSTOP 1 1 10 KSTOP 2 1 11 CANL 12 G...

Page 12: ...el LED on DATA switched off Radio channel occupied by non Danfoss system Change transmitter s frequency channel DATA Green pulsing Receiving good frames OK ID LED off DATA LED on No valid ID Danfoss s...

Page 13: ...Blue fast pulses System is starting establishing connection with radio and EEPROM Wait Blue continuous Waiting for transmitter communication coming from ACTIVE STOP Release STOP button and press STAR...

Page 14: ...ON N A RELAY Green continuous STOP relay activated N A CANERR Red slow pulses CAN Error physical Layer Verify Connections Red double pulses One expansion has Stopped working Verify Expansion boards R...

Page 15: ...anfoss Power Solutions US Company 2800 East 13th Street Ames IA 50010 USA Phone 1 515 239 6000 Danfoss Power Solutions Trading Shanghai Co Ltd Building 22 No 1000 Jin Hai Rd Jin Qiao Pudong New Distri...

Reviews: