© Danfoss | Climate Solutions | 2022.03
Technical specifications
50 Hz
Model
HP
Nominal
cooling capacity
Power
input
Efficiency
Swept volume
Displacement
Oil charge
Net weight
(with oil)
COP
EER
W
Btu/h
kW
W/W
Btu/h/W
cm3/rev
m3/h
Litres
kg
MLM090
12
19226
65599
7928
2.43
8.27
193.5
33.7
3.3
67
MLZ090
12
19301
65855
9152
2.11
7.2
193.5
33.7
3.3
67
MLM116
15
24451
83427
10789
2.27
7.73
249.9
43.5
6.7
100
MLZ116
15
26865
91664
12127
2.22
7.56
249.9
43.5
6.7
100
MLM130
18
27411
93526
13044
2.43
8.29
276.2
48.1
6.7
111
MLZ130
18
27568
94062
11286
2.11
7.21
276.2
48.1
6.7
111
MLM160
22
32707
111596
14636
2.23
7.62
347.8
60.5
8.0
150
MLZ160
22
32943
112402
17124
1.92
6.56
347.8
60.5
8.0
150
MLM200
25
40833
139322
17835
2.29
7.81
437.5
76.1
8.0
157
MLZ200
25
41312
140957
20819
1.98
6.77
437.5
76.1
8.0
157
MLM240
30
50562
172518
21818
2.32
7.91
531.2
92.4
8.4
158
MLZ240
30
50440
172101
25460
1.98
6.76
531.2
92.4
8.4
158
Note: EN12900 conditions: To= -10°C, Tc= 45°C, RGT= 20°C, SC= 0K
* For MLZ090-130-160-200-240 R507 performance data are nearly identical to R404A performance data
**MLM/Z116’s rating condition is EN12900@SH10K