Danfoss MCX15B2 Installation Manual Download Page 4

© Danfoss | DCS (vt) | 2020.10

4 | AN320819413085en-000401

Digital
output

Relay

20 (MCX20B2)
15 (MCX15B2)

Concerning the insulation distance there are three groups of relays:
•  group 1: relays 1 to 8
•  group 2: relays 9 to 13
•  group 3: relays 14 to 20

Insulation between relays of the same group: functional

Insulation between relays of different groups: reinforced

Insulation between relays and the extra-low voltage parts: reinforced

Total current load limit: 65 A

C1-NO1 to C13-NO13, C16-NO16 to C20-NO20 on MCX20B2 

C1-NO1 to C13-NO13 on MCX15B2

Normally open contact relays 5 A 

Characteristics of each relay:

 

– 5 A 250 V AC for resistive loads - 100,000 cycles

 

– 3 A 250 V AC for inductive loads - 100,000 cycles with cos(phi) = 0.4

 

– UL: 3 A resistive, 250 V AC, 100,000 cycles; 1/8 hp, 125/250 V AC, 

30,000 cycles; C300 pilot duty, 125/250 V AC, 30,000 cycles

C14-NO14-NC14, C15-NO15-NC15

Changeover contact relays 16 A

Characteristics of each relay:

 

– 7 A 250 V AC for resistive loads - 100,000 cycles

 

– 3.5 A 250 V AC for inductive loads - 230,000 cycles with cos(phi) = 0.4

 

– UL: NO contact: 6 A resistive, 240 V AC, 30.000 cycles; 1/2 hp, 240 

V AC, 30.000 cycles; 470 VA pilot duty, 240 V AC, 30.000 cycles. NC 

contact: 6 A resistive, 6.000 cycles

C3 NO3 to C6 NO6

Optionally they can be solid state relays

Characteristics of each relay:

15-280 Vrms, 0.5 A

UL: 0.5 A resistive, 240 V AC, 30,000 cycles

Interface

Use

Connector label

Technical data

CANbus

Fieldbus for connection to user 
interfaces, MCX controllers, service 
tools etc.

CAN
CAN-RJ

Physical layer according to ISO 11898-2 High 
Speed CAN bus
Frame format according to CAN 2.0B specification
Transceiver not isolated (power supply has 
reinforced isolation)

USB device

Prepared for future use

USB-DEV

Plug: Type Mini B

USB host

For connection to Flash drive 
for application software update, 
datalogging and service

USB-H

Plug: Type A

RS485-1
RS485-2 (MCX20B2 only)

Communication bus to BMS (e.g. 
Modbus slave), service tools, smart 
devices (e.g. Modbus master)
RS485-1 can be polarized as master 
from the application

RS485-1
RS485-2

Physical layer according to EIA 485 Ref3
Provide 500 V peak transient galvanic isolation

Ethernet

For web server functionality, 
integration (e.g. Modbus TCP)
NOTICE! Do not route cable outside 
of buildings.
Connect only to IT equipment 
compliant with EN 60950 or EN 
62368 (Information technology 
equipment. Safety. General 
requirements)

ETHERNET

Interface type: 10 BASE-T and 100 BASE-TX, IEEE 
802.3.
MDI-X (Automatic medium-dependent interface 
crossover)

Communication interface

Wire lengths

Interface 

Max wire length (m)

Max. baudrate (bps)

Min. wire size

Ethernet 

100

10/100 M

CANbus

1000
500
250
80
30

50 K
125 K
250 K
500 K
1 M

AWG18
AWG22
AWG24
AWG26
AWG26

RS485

1000

125 K

AWG22

Signal wiring

30 

Summary of Contents for MCX15B2

Page 1: ...several models with or without graphic LCD display and with 15 or 20 digital output MCX15B2 MCX20B2 ANALOG INPUTS NTC 0 1 V 0 5 V 0 10 V PT1000 selectable via software 4 6 Universal NTC Pt1000 0 1 V 0...

Page 2: ...ntains live electrical components therefore all the service and maintenance operations must be performed by qualified personnel The device can t be used as a safety device Liability for injury or dama...

Page 3: ...outputs All power outputs are protected against short circuit and have an automatic recovery from overload condition Digital inputs Total number 22 Digital Input type selectable via software between...

Page 4: ...racteristics of each relay 15 280 Vrms 0 5 A UL 0 5 A resistive 240 V AC 30 000 cycles Interface Use Connector label Technical data CANbus Fieldbus for connection to user interfaces MCX controllers se...

Page 5: ...INPUT DI1 DI4 24 V 230 V OR OR N L N L N L 24 V VOLTAGE FREE VOLTAGE FREE or 24 V DIGITAL INPUT DI5 DI22 e g DIGITAL INPUT 5 e g DIGITAL INPUT 1 MCX20B2 only TOP BOARD BOTTOM BOARD NOTE connection has...

Page 6: ...tal input 14 17 connector 5 way screw plug in connector type pitch 5 mm section cable 0 2 2 5 mm Digital input 18 22 connector 6 way screw plug in connector type pitch 5 mm section cable 0 2 2 5 mm Bo...

Page 7: ...standard kit connectors LCD Display No Display LCD Display display mode STN blue transmissive back light white LED back light adjustable via software display format 128 x 64 dots active visible area...

Page 8: ...age of the additional NC14 signal of MCX20B2 The Analogue Outputs AO in MCX15 20B2 are internally powered therefore you must not connect the L1 signal 24 V DC power supply is not supported by MCX15 20...

Page 9: ...nection direct connection Phoenix MSTB MCX20B2 connectors Phoenix FKIC Wires Wiring kit MCX20B2 board 1 2 3 4 5 6 7 8 9 10 Danfoss 80G466 1 1 1 1 Phoenix FKIC 1910720 1 C16 1 2 NO16 2 1 NC15 3 C15 3 2...

Page 10: ...FKIC 1910717 1 AO1 1 1 AO1 AO1 6 8 ways 2 AO2 2 2 AO2 3 AO3 3 3 AO3 4 AO4 4 4 AO4 5 L1 5 5 AO5 6 N1 6 6 AO6 7 AOC Phoenix FKIC 1910694 8 AOC 1 AO6 1 2 AO5 2 3 N1 3 4 N1 4 AI15 16 4 ways AI15 16 AO1 4...

Page 11: ...1 NC14 1 5 C14 2 C14 2 6 NO14 3 NO14 3 DIGITAL INPUT DI4 3 ways DI4 DI5 8 5 ways DI5 8 DI2 3 ways DI2 DI3 3 ways DI3 DO13 3 ways DO15 3 ways DO14 15 6 ways DO14 15 DO14 3 ways DI1 3 ways DI1 DO6 8 6 w...

Page 12: ...5 AO5 6 N1 6 6 AO6 7 AOC Phoenix FKIC 1910720 8 AOC 1 AO6 1 2 COM 2 3 AO5 3 AO1 4 6 ways AO1 6 AO5 6 4 ways AI11 14 7 ways AI11 14 AI15 16 4 ways AI15 16 AI1 6 11 ways AI1 6 AI7 10 6 ways AI7 10 DI9...

Page 13: ...C11 6 4 NO10 7 C11 7 5 C11 8 NO11 8 6 NO11 9 NC12 9 7 C12 10 C12 10 8 NO12 NO13 10 11 NO12 11 9 C13 Phoenix FKIC 1910681 1 NC13 1 2 C13 2 3 NO13 3 DO9 12 11 ways DO9 13 10 ways DO9 13 DO13 3 ways Exte...

Page 14: ...rrors in catalogues brochures and other printed material Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alterations c...

Reviews: