Danfoss MCX15B2 Installation Manual Download Page 1

Installation Guide

Electronic controller

MCX15B2/20B2

080R9340

AN320819413085en-000401

© Danfoss | DCS (vt) | 2020.10

AN320819413085en-000401 | 1

General features:

MCX15B2/MCX20B2 is an electronic controller that stands on the top of the MCX range, 
thanks to the large number of its inputs and outputs, the enhanced CPU capabilities and 
connectivity features.
It holds all the typical functionalities of MCX controllers: programmability, connection to the 
CANbus local network,   up to two Modbus RS485 serial interfaces with galvanic isolation.

Furthermore, it is fitted with an ultra wide range (24/110/230 V AC) power supply in the 
same product variant, with USB and Ethernet connection for embedded Web server and IP 
protocols management. 
It is available in several models, with or without graphic LCD display and with 15 or 20 digital 
output.

MCX15B2

MCX20B2

ANALOG INPUTS

NTC, 0/1 V, 0/5 V, 0 / 10 V PT1000, selectable via software

4

6

Universal NTC, Pt1000, 0/1 V, 0/5 V, 0/10 V, ON/OFF, 0/20 mA, 4/20 mA, selectable via 
software

6

10

Total number

10

16

DIGITAL INPUTS

Voltage free contact/24V AC sensing

18

18

24/230 V AC optoinsulated

4

4

Total number

22

22

ANALOG OUTPUTS

0/10 V DC optoinsulated

6

6

0/10 V, PWM, PPM selectable via software

2

2

Total number

6

6

DIGITAL OUTPUTS

SPDT relay 16 A (changeover contacts)

2

2

SPST relay 5 A (normally open contacts)

13

18

Total number

15

20

OTHERS

Power supply 24-110-230 V AC / 40-230 V DC

Connection for programming key and for remote display and keyboard

Buzzer

-

-

RTC clock

Modbus RS485 serial interface

x1

x2

CANbus

Ethernet for Webserver/Modbus TCP

USB for firmware/application software update and datalogging

Dimensions (DIN modules)

16

16

Mounting

DIN rail

DIN rail

Summary of Contents for MCX15B2

Page 1: ...several models with or without graphic LCD display and with 15 or 20 digital output MCX15B2 MCX20B2 ANALOG INPUTS NTC 0 1 V 0 5 V 0 10 V PT1000 selectable via software 4 6 Universal NTC Pt1000 0 1 V 0...

Page 2: ...ntains live electrical components therefore all the service and maintenance operations must be performed by qualified personnel The device can t be used as a safety device Liability for injury or dama...

Page 3: ...outputs All power outputs are protected against short circuit and have an automatic recovery from overload condition Digital inputs Total number 22 Digital Input type selectable via software between...

Page 4: ...racteristics of each relay 15 280 Vrms 0 5 A UL 0 5 A resistive 240 V AC 30 000 cycles Interface Use Connector label Technical data CANbus Fieldbus for connection to user interfaces MCX controllers se...

Page 5: ...INPUT DI1 DI4 24 V 230 V OR OR N L N L N L 24 V VOLTAGE FREE VOLTAGE FREE or 24 V DIGITAL INPUT DI5 DI22 e g DIGITAL INPUT 5 e g DIGITAL INPUT 1 MCX20B2 only TOP BOARD BOTTOM BOARD NOTE connection has...

Page 6: ...tal input 14 17 connector 5 way screw plug in connector type pitch 5 mm section cable 0 2 2 5 mm Digital input 18 22 connector 6 way screw plug in connector type pitch 5 mm section cable 0 2 2 5 mm Bo...

Page 7: ...standard kit connectors LCD Display No Display LCD Display display mode STN blue transmissive back light white LED back light adjustable via software display format 128 x 64 dots active visible area...

Page 8: ...age of the additional NC14 signal of MCX20B2 The Analogue Outputs AO in MCX15 20B2 are internally powered therefore you must not connect the L1 signal 24 V DC power supply is not supported by MCX15 20...

Page 9: ...nection direct connection Phoenix MSTB MCX20B2 connectors Phoenix FKIC Wires Wiring kit MCX20B2 board 1 2 3 4 5 6 7 8 9 10 Danfoss 80G466 1 1 1 1 Phoenix FKIC 1910720 1 C16 1 2 NO16 2 1 NC15 3 C15 3 2...

Page 10: ...FKIC 1910717 1 AO1 1 1 AO1 AO1 6 8 ways 2 AO2 2 2 AO2 3 AO3 3 3 AO3 4 AO4 4 4 AO4 5 L1 5 5 AO5 6 N1 6 6 AO6 7 AOC Phoenix FKIC 1910694 8 AOC 1 AO6 1 2 AO5 2 3 N1 3 4 N1 4 AI15 16 4 ways AI15 16 AO1 4...

Page 11: ...1 NC14 1 5 C14 2 C14 2 6 NO14 3 NO14 3 DIGITAL INPUT DI4 3 ways DI4 DI5 8 5 ways DI5 8 DI2 3 ways DI2 DI3 3 ways DI3 DO13 3 ways DO15 3 ways DO14 15 6 ways DO14 15 DO14 3 ways DI1 3 ways DI1 DO6 8 6 w...

Page 12: ...5 AO5 6 N1 6 6 AO6 7 AOC Phoenix FKIC 1910720 8 AOC 1 AO6 1 2 COM 2 3 AO5 3 AO1 4 6 ways AO1 6 AO5 6 4 ways AI11 14 7 ways AI11 14 AI15 16 4 ways AI15 16 AI1 6 11 ways AI1 6 AI7 10 6 ways AI7 10 DI9...

Page 13: ...C11 6 4 NO10 7 C11 7 5 C11 8 NO11 8 6 NO11 9 NC12 9 7 C12 10 C12 10 8 NO12 NO13 10 11 NO12 11 9 C13 Phoenix FKIC 1910681 1 NC13 1 2 C13 2 3 NO13 3 DO9 12 11 ways DO9 13 10 ways DO9 13 DO13 3 ways Exte...

Page 14: ...rrors in catalogues brochures and other printed material Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alterations c...