NB!

Please note the values available within the different standard groups of resistors:
E12: Closest standard value is 470

, creating an input of 449.9

 and 8.997V.

E24: Closest standard value is 510

, creating an input of 486.4

 and 9.728V.

E48: Closest standard value is 511

, creating an input of 487.3

 and 9.746V.

E96: Closest standard value is 523

, creating an input of 498.2

 and 9.964V.

Analog inputs - terminal X42/1-6

Parameter group for read out: 18-3*. See also 

 Programming Guide.

Parameter groups for set-up: 26-0*, 26-1*, 26-2* and 26-3*. See also 

 Programming Guide.

3 x Analog inputs

Operating range

Resolution

Accuracy

Sampling

Max load

Impedance

Used as

temperature
sensor input

-50 to +150 °C

11 bits

-50 °C

±1 Kelvin

+150 °C

±2 Kelvin

3 Hz

-

-

Used as

voltage input

0 - 10 VDC

10 bits

0.2% of full
scale at cal.

temperature

2.4 Hz

+/- 20 V

continuously

Approximately

5 k

When used for voltage, analog inputs are scalable by parameters for each input.

When used for temperature sensor, analog inputs scaling is preset to necessary signal level for specified temperature span.

When analog inputs are used for temperature sensors, it is possible to read out feedback value in both 

°

C and 

°

F.

When operating with temperature sensors, maximum cable length to connect sensors is 80 m non-screened / non-twisted wires.

Analog outputs - terminal X42/7-12

Parameter group for read out and write: 18-3*. See also 

 Programming Guide

Parameter groups for set-up: 26-4*, 26-5* and 26-6*. See also 

 Programming Guide

3 x Analog outputs

Output signal level

Resolution

Linearity

Max load

Volt

0-10 VDC

11 bits

1% of full scale

1 mA

Analog outputs are scalable by parameters for each output.

The function assigned is selectable via a parameter and have same options as for analog outputs on control card.

For a more detailed description of parameters, please refer to the 

 Programming Guide

.

Real-time clock (RTC) with back-up

The data format of RTC includes year, month, date, hour, minutes and weekday.

Accuracy of clock is better than 

±

 20 ppm at 25 

°

C.

The built-in lithium back-up battery lasts on average for minimum 10 years, when frequency converter is operating at 40 

°

C ambient temperature. If

battery pack back-up fails, analog I/O option must be exchanged.

1 Analog I/O Option MCB109

MCB109 Instruction

4

MI.38.B2.02 - VLT

®

 is a registered Danfoss trademark

1  

Summary of Contents for MCB109

Page 1: ...nalog I O Option MCB109 3 Introduction 3 Ordering Code Numbers 5 Mounting Guidelines 5 Mounting of Option Modules in Slot B 5 Index 7 MCB109 Instruction Contents MI 38 B2 02 VLT is a registered Danfoss trademark 1 ...

Page 2: ...1 Analog I O Option MCB109 MCB109 Instruction 2 MI 38 B2 02 VLT is a registered Danfoss trademark 1 ...

Page 3: ... PID controllers with I Os for set point inputs transmitter sensor inputs and outputs for actuators Illustration 1 1 Principle diagram for Analog I O mounted in frequency converter Analog I O configuration 3 x Analog Inputs capable of handling following 0 10 VDC OR 0 20 mA voltage input 0 10V by mounting a 510Ω resistor across terminals see NB 4 20 mA voltage input 2 10V by mounting a 510Ω resisto...

Page 4: ...span When analog inputs are used for temperature sensors it is possible to read out feedback value in both C and F When operating with temperature sensors maximum cable length to connect sensors is 80 m non screened non twisted wires Analog outputs terminal X42 7 12 Parameter group for read out and write 18 3 See also Programming Guide Parameter groups for set up 26 4 26 5 and 26 6 See also Progra...

Page 5: ...move the knock out in the extended frame delivered in the option set so that the option will fit under the extended frame Fit the extended frame and terminal cover Fit the or blind cover in the extended frame Connect power to the frequency converter Set up the input output functions in the corresponding parameters as mentioned in this document For A5 B1 B2 B4 C1 C2 C3 C4 D E and F enclosures Remov...

Page 6: ...A2 A3 and B3 enclosures A5 B1 B2 B4 C1 C2 C3 C4 D E and F enclosures 1 Analog I O Option MCB109 MCB109 Instruction 6 MI 38 B2 02 VLT is a registered Danfoss trademark 1 ...

Page 7: ... 3 Building Management System 3 I I os For Set Point Inputs 3 M Mcb 109 0 Multi zone Control 3 N Ni1000 Temperature Sensor 3 O Outputs For Actuators 3 P Principle Diagram 3 Pt1000 Temperature Sensor 3 R Real time Clock rtc 4 T Transmitter sensor Inputs 3 MCB109 Instruction Index MI 38 B2 02 VLT is a registered Danfoss trademark 7 ...

Reviews: