4 Parameter Setup

4.1 Introduction to Parameter Setup

The parameters included in this Operating Guide are extracts from the drive-specific programming guides. Refer to these
Programming Guides for full parameter descriptions.

4.2 5-** Digital In/Out

4.2.1 Parameter Group 5-1* Digital Inputs

The digital inputs are used for selecting various functions in the drive. Refer to 

table 7

 to see which functions can be assigned to digital

inputs.

Functions in group 1 have higher priority than the functions in group 2.

Group 1

Reset, coast stop, reset, and coast stop, quick stop, DC brake, stop, and the [Off] key.

Group 2

Start, latched start, reversing, start reversing, jog, and freeze output.

Table 7: Digital Input Functions

Digital input function

Select

Terminal

No operation

[0]

All, terminal 32, 33

Reset

[1]

All

Coast inverse

[2]

All, terminal 27

Coast and reset inverse

[3]

All

Quick stop inverse

[4]

All

DC brake inverse

[5]

All

Stop inverse

[6]

All

Start

[8]

All, terminal 18

Latched start

[9]

All

Reversing

[10]

All, terminal 19

Start reversing

[11]

All

Enable start forward

[12]

All

Enable start reverse

[13]

All

Jog

[14]

All, terminal 29

Preset reference on

[15]

All

Preset ref bit 0

[16]

All

Preset ref bit 1

[17]

All

Preset ref bit 2

[18]

All

Freeze reference

[19]

All

Freeze output

[20]

All

Parameter Setup

Operating Guide  | VLT® Extended Relay Card MCB 113

AQ322553864968en-000101 / 130R0353| 15

Danfoss A/S © 2020.01

Summary of Contents for MCB 113

Page 1: ...Operating Guide VLT Extended Relay Card MCB 113 VLT HVAC Drive FC 102 VLT Refrigeration Drive FC 103 VLT AQUA Drive FC 202 VLT Au tomationDrive FC 301 FC 302...

Page 2: ......

Page 3: ...3 2 4 Galvanic Isolation 13 4 Parameter Setup 15 4 1 Introduction to Parameter Setup 15 4 2 5 Digital In Out 15 4 2 1 Parameter Group 5 1 Digital Inputs 15 4 2 2 Parameter Group 5 2 Digital Inputs 31...

Page 4: ...5 4 EMC 50 6 Appendix 51 6 1 Abbreviations 51 6 2 Conventions 51 Contents Operating Guide VLT Extended Relay Card MCB 113 AQ322553864968en 000101 4 Danfoss A S 2020 01...

Page 5: ...ent version Remarks AQ322553864968 version 0101 Option now also applicable for VLT HVAC Drive FC 102 VLT Refrigeration Drive FC 103 and VLT AQUA Drive FC 202 1 4 Additional Resources More information...

Page 6: ...ng kit includes a fan for VLT Motion Control MCO 305 and is only to be mounted if MCO 305 is used Table 2 Mounting Kits for Book style Enclosures Enclosure sizes Order number A2 and A3 40 mm for 1 C o...

Page 7: ...ification for the drive are on the nameplate of the drive For more information contact the local Danfoss office or partner Introduction Operating Guide VLT Extended Relay Card MCB 113 AQ322553864968en...

Page 8: ...ss WARNING DISCHARGE TIME The drive contains DC link capacitors which can remain charged even when the drive is not powered High voltage can be present even when the warning indicator lights are off F...

Page 9: ...34 10 hp 11 75 kW 15 100 hp 525 600 0 75 7 5 kW 1 10 hp 11 75 kW 15 100 hp 525 690 1 5 7 5 kW 2 10 hp 11 75 kW 15 100 hp WARNING LEAKAGE CURRENT HAZARD Leakage currents exceed 3 5 mA Failure to ground...

Page 10: ...Jum per toacti vate Safe Sto p 12 13 18 19 27 29 32 33 20 1 2 130bb457 11 Illustration 1 Installation of VLT Extended Relay Card MCB 113 Exploded View If only 1 C option is used use the 40 mm mounting...

Page 11: ...1 DIN3 DIN5 DIN7 DIN9 DIN11 DIN13 Ext Ext 24 VDC X45 X58 X46 Relay 6 Relay 5 Relay 4 Relay 3 X47 Rin 4kW e30ba746 11 NOTICE The connections of these relays differ from the standard relays of the drive...

Page 12: ...24 V DC Par 5 00 24 V NPN 0 V PNP e30ba765 11 Illustration 3 Programming Digital Inputs Installation Operating Guide VLT Extended Relay Card MCB 113 AQ322553864968en 000101 130R0353 12 Danfoss A S 202...

Page 13: ...olation The VLT Extended Relay Card MCB 113 can be connected to an 24 V external supply on X58 to ensure galvanic isolation between the drive and the option card If galvanic isolation is not needed th...

Page 14: ...0 11 12 Live part Live part PELV Live part Live part Live part PELV PELV PELV PELV PELV e30bb443 11 Illustration 5 Valid Connections for Galvanic Isolation Installation Operating Guide VLT Extended Re...

Page 15: ...and the Off key Group 2 Start latched start reversing start reversing jog and freeze output Table 7 Digital Input Functions Digital input function Select Terminal No operation 0 All terminal 32 33 Res...

Page 16: ...stop inverse 41 18 19 External interlock 51 DigiPot increase 55 All DigiPot decrease 56 All DigiPot clear 57 All DigiPot hoist 58 All Counter A up 60 29 33 Counter A down 61 29 33 Reset Counter A 62...

Page 17: ...inverse 116 18 32 33 Touch sensor 117 18 32 33 Touch sensor inverse 118 18 32 33 Speed mode 119 All Power limit mot 231 All Power limit gen 232 All Power limit both 233 All Light load evacuation 234...

Page 18: ...t for DC brake NC Stops motor by energizing it with a DC current for a certain time period See parameter 2 01 DC Brake Current to parameter 2 03 DC Brake Cut In Speed RPM The function is only active w...

Page 19: ...n external reference and preset reference It is assumed that 1 External preset has been se lected in parameter 3 04 Reference Function Logic 0 external reference active logic 1 1 of the 8 preset refer...

Page 20: ...0 26 Precise stop inv Sends an inverted stop signal when the precise stop function is activated in parameter 1 83 Precise Stop Func tion Precise stop inverse function is available for terminals 18 or...

Page 21: ...e Flanks 34 Ramp bit 0 Enables a selection between 1 of the 4 ramps available according to table 13 35 Ramp bit 1 Same as 34 Ramp bit 0 Table 13 Preset Ramp Bit Preset ramp bit 1 0 Ramp 1 0 0 Ramp 2 0...

Page 22: ...nly if parameter 1 00 Configuration Mode is set to 6 Surface Winder 7 Extended PID Speed OL or 8 Extended PID Speed CL 73 PID reset I part When enabled this option resets the I part of the process PID...

Page 23: ...ls see the description of 96 Mains loss NOTICE Only available for pulse inputs at terminals 32 33 98 Start edge trig gered Edge triggered start command Keeps the start command alive It can be used for...

Page 24: ...ive positioning The option is valid for the next position ing command 113 Enable refer ence NOTICE This option is available only with IMC software version 48 XX Positioning mode The drive activates th...

Page 25: ...available only with IMC software version 48 XX Select the speed mode when 9 Positioning or 10 Synchronization is selected in parameter 1 00 Configu ration Mode Speed reference is set by reference reso...

Page 26: ...XX Normally closed contact Serves as input for follower marker signal during marker synchronization based on the option selected in parameter 3 33 Sync Mode Start Behavior 231 Power limit mot Serves...

Page 27: ...Speed up 22 Speed down 23 Set up select bit 0 24 Set up select bit 1 28 Catch up 29 Slow down 34 Ramp bit 0 35 Ramp bit 1 44 Restart drive 51 External interlock 55 DigitPot increase 56 DigiPot decrea...

Page 28: ...get inverse 108 Enable master offset 109 Start virtual master 110 Start homing 111 Activate touch 112 Relative position 113 Enable reference 114 Sync to pos mode 115 Home sensor 116 Home sensor inv 11...

Page 29: ...ation 1 Reset 2 Coast inverse 3 Coast and reset inv 4 Quick stop inverse 5 DC brake inverse 6 Stop inverse 8 Start 9 Latched start 10 Reversing 11 Start reversing 12 Enable start forward 13 Enable sta...

Page 30: ...r B 70 Merch brake feedb 71 Mech brake feedb inv 72 PID error inverse 73 PID reset I part 74 PID enable 75 MCO specific 78 Reset maint word 80 PTC card 1 91 PROFIdrive OFF2 92 PROFIdrive OFF3 94 Light...

Page 31: ...tion 0 No operation This parameter is active when option module VLT Extended Relay Card MCB 113 is installed in the drive Functions are described in parameter group 5 1 Digital Inputs Table 19 Paramet...

Page 32: ...gital Outputs 1 Option Function 0 No operation Default for all digital outputs and relay outputs 1 Control ready The control card is ready for example Feedback from a drive controlled by a 24 V extern...

Page 33: ...and there is no overtemperature warning 23 Remote ready no TW The drive is ready for operation and is in auto on mode There is no overtemperature warning 24 Ready voltage OK The drive is ready for op...

Page 34: ...from the option 54 24V encoder sim Digital outputs 27 and 29 simulate a single signal HTL encoder Select source for the signal genera tion in parameter 5 78 Term 27 29 Encoder Sim NOTICE Option 54 24...

Page 35: ...ig out C high is executed The output goes low whenever the smart logic action 34 Set dig out C low is executed 83 SL digital output D See parameter 13 52 SL Controller Action The output goes high when...

Page 36: ...cur lim alarm is active the output is 1 152 ATEX ETR freq alarm Selectable if parameter 1 90 Motor Thermal Protection is set to 20 ATEX ETR or 21 Advanced ETR If Alarm 166 ATEX ETR freq lim alarm is...

Page 37: ...FC 302 Positioning is completed and the on target signal is sent when the actual position is within parame ter 3 05 On Reference Window for the duration of parameter 3 09 On Target Time and the actua...

Page 38: ...s 9 Alarm An alarm activates the output No warnings 10 Alarm or warning An alarm or a warning activates the output 11 At torque limit The torque limit set in parameter 4 16 Torque Limit Motor Mode or...

Page 39: ...current for the coil in the brake Usually solved by connecting an external relay to the selected digital output 33 Safe stop active Indicated that the Safe Torque Off on terminal 37 has been activated...

Page 40: ...ic Control If logic rule 1 in SLC is true the output goes high Oth erwise it is low 72 Logic rule 2 See parameter group 13 4 Smart Logic Control If logic rule 2 in SLC is true the output goes high Oth...

Page 41: ...Hand off 1 0 Auto off 0 0 Auto 0 1 Table 29 Parameter 5 40 Relays 2 Option Function 121 Remote ref active Output is high when parameter 3 13 Reference Site 1 Remote or 0 Linked to hand auto while the...

Page 42: ...p 0 See parameter group 13 1 Comparators 193 RS Flipflop 1 See parameter group 13 1 Comparators 194 RS Flipflop 2 See parameter group 13 1 Comparators 195 RS Flipflop 3 See parameter group 13 1 Compar...

Page 43: ...MCO 305 0 20 mA 53 MCO 305 4 20 mA 100 Output frequency 0 20 mA 0 Hz 0 mA 100 Hz 20 mA 101 Reference 0 20 mA Parameter 3 00 Reference Range 0 Min Max 0 0 mA 100 20 mA Parameter 3 00 Reference Range 1...

Page 44: ...le is VLT Max 100 Motor Norm 38 4 100 22 175 134 Torque lim 4 20 mA The torque setting is related to the setting in parameter 4 16 Torque Limit Motor Mode 135 Torque nom 4 20 mA The torque setting is...

Page 45: ...required at maximum output 100 calculate the percentage value as follows example where required maximum output is 10 mA RANGE mA DESIRED MAX mA 100 20 4 mA 10 mA 100 160 e30ba877 11 mA 0 20 0 4 100 C...

Page 46: ...give a lower current than 20 mA at full scale or 20 mA at an output below 100 of the maximum signal value If 20 mA is the required output current at a value between 0 100 of the full scale output pro...

Page 47: ...Example Input 18 corresponds to bit number 5 0 no signal 1 connected signal Bit 6 works in the opposite way 0 on 1 off safe stop input Bit 0 Digital input term 33 Bit 1 Digital input term 32 Bit 2 Di...

Page 48: ...0 Table 44 Parameter 16 71 Relay Output bin Range Function 0 000 N A 0 511 N A View the settings of all relays Bit 0 Relay 9 Bit 1 Relay 8 Bit 2 Relay 7 Bit 3 Relay 2 Bit 4 Relay 1 Bit 5 Relay 6 Bit 6...

Page 49: ...ut value at terminal X45 1 The value shown reflects the selection in parameter 6 70 Terminal X45 1 Output Table 46 Parameter 16 79 Analog Out X45 3 mA Range Function 0 0 30 Shows the actual output val...

Page 50: ...1 unused relay in between 5 2 Digital Inputs Number 7 Range 0 24 V Mode PNP NPN Input impedance 4 k Low trigger level 6 4 V High trigger level 17 V 5 3 Analog Outputs Number 2 Range 0 4 20 mA Resolut...

Page 51: ...procedures Bulleted and dashed lists indicate listings of other information where the order of the information is not relevant Bolded text indicates highlighting and section headings Italicized text i...

Page 52: ...nting kit 6 N NAMUR 13 O Order numbers 6 P Purpose of the manual 5 Q Qualified personnel 5 R Retrofit 6 S Safety instructions 10 Switches Disconnect 8 U UL certification 6 Unintended start 8 V Voltage...

Page 53: ...Operating Guide VLT Extended Relay Card MCB 113 AQ322553864968en 000101 130R0353 53 Danfoss A S 2020 01...

Page 54: ...der provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the respective companies D...

Reviews: