System design recommendations

Cycle rate limit

R

No more than 12 starts per hour (6 when a 

soft start accessory is used) are allowed. A higher 
number would reduce the service life of the 
motor-compressor unit. If necessary, use an anti-
short-cycle timer within the control circuit. 

The system must be designed in a way that 
guarantees minimum compressor running time 
so as to provide sufficient motor cooling after 

start-up as well as proper oil return from the 
system to the compressor.
A 5-minute delay between two successive 
compressor starts is being proposed herein, 
with a 2-minute runtime after each start and a 
3-minute idle time between each stop and start.

Only during the pump-down cycle may the 
compressor run for much shorter intervals.

Liquid floodback during 
operation

Off-cycle migration

Liquid refrigerant control 
and charge limits

During normal and stable system operation, 
refrigerant will leave the evaporator in a 
superheated condition and enter the compressor 
as a superheated vapour. Normal superheat 
values at compressor suction are 5 to 30 K. 
However the refrigerant leaving the evaporator 
can contain an amount of liquid refrigerant due 
to different reasons:

•  wrong dimensioning, wrong setting or 

malfunction of expansion device

•  evaporator fan failure or frosted-up evaporator 

coils.

In these situations, liquid refrigerant will 
continuously enter the compressor. The negative 
effects from continuous liquid floodback are:

•  permanent oil dilution

•  in extreme situations with high system 

refrigerant charge and large amounts of 
floodback, liquid slugging could occur.

During system standstill and after pressure 
equalisation, refrigerant will condensate in 
the coldest part of the system which may be 
the compressor when it is placed in a cold 
environment. Ultimately, the full system 
refrigerant charge can condensate in the 
compressor crankcase. A large amount will 
dissolve in the compressor oil until the oil is 
completely saturated with refrigerant. When 

the compressor is started, the pressure in the 
crankcase decreases rapidly and refrigerant 
will violently evaporate, causing the oil to foam 
(boiling). Both dilution and foaming reduce 
the lubrication properties of the oil. In extreme 
situations liquid could enter the compressor 
cylinders with immediate compressor break-
down as a result. 

Refrigeration compressors are basically 
designed as gas compressors. Depending on the 
compressor design and operating conditions, 
most compressors can also handle a limited 
amount of liquid refrigerant. Maneurop® NTZ 
compressors have a large internal volume and 
can therefore handle relatively large amounts of 
liquid refrigerant without major problems.

However even when a compressor can handle 
liquid refrigerant, this will not be favourable to 
its service life.

Liquid refrigerant will dilute the oil, wash out the 
bearings causing wear and eventually seizure. 

Furthermore, high oil carry over will cause lack of 
oil in the sump.

Good system design can limit the amount of 
liquid refrigerant in the compressor, which will 
have a positive effect on the compressor service 
life.

R

Liquid refrigerant can enter a compressor 

in various ways, with different effects on the 
compressor as described in the following points.

With R454C/R455A, liquid migration to the 
compressor must be avoided by maintaining 
adequate superheat setting of min. 8-10K.

23

AB245486497018en-000601

Application Guidelines

Summary of Contents for Maneurop NTZ

Page 1: ...Maneurop reciprocating compressors NTZ 50 60 Hz Group 2 R404A R507A R452A Group 1 R454C R455A Application guidelines http cc danfoss com...

Page 2: ......

Page 3: ...certificates 17 Pressure equipment directive 2014 68 EU 17 Low voltage directive 2014 35 EU 17 Machinery directive 2014 30 EU 17 Internal free volume 17 Operating conditions 18 Refrigerants and lubri...

Page 4: ...to avoid safety risk This icon indicates instructions to avoid reliability risk The purpose of this guideline is informational with the intent to educate customers as to how the compressors should pr...

Page 5: ...be operated at a return gas temperature suction gas temperature of 20 C even at low evaporating temperatures A liquid injection system is not required All components are of high quality and precision...

Page 6: ...conditions R404A Evap temp 35 C Cond temp 40 C RGT 20 C SC 0K For full NTZ data details and capacity tables refer to selection software Coolselector 2 NT Z 4 L 048 A R1 B Motor voltage code Z Polyole...

Page 7: ...52 1 19 NTZ271 4 7090 6 64 9 65 1 07 8210 6 64 9 65 1 24 R452A Refrigeration Compressor model 50 Hz EN12900 ratings To 35 C Tc 40 C SC 0K SH 10K 50 Hz EN12900 ratings To 35 C Tc 40 C SC 0K RGT 20 C Co...

Page 8: ...16 3 41 0 89 1177 1 25 3 11 0 94 Compressor model 50 Hz EN12900 ratings To 35 C Tc 40 C SC 0K SH 10K 60 Hz EN12900 ratings To 35 C Tc 40 C SC 0K SH 10K Cooling capacity W Power input kW Current input...

Page 9: ...se heater 25 98 Schrader 1 4 263 333 353 NTZ068 1 Suction rotolock 1 1 4 Discharge rotolock 1 68 82 109 118 35 33 68 Suction 147 Discharge 142 159 17 17 123 39 Threaded oil sight glass 141 224 68 HM8...

Page 10: ...179 Discharge 176 252 288 413 32 Threaded oil sight glass Schrader 1 4 PTC crankcase heater 96 21 145 125 188 171 8 38 82 1 98 2 74 68 265 Suction rotolock 1 3 4 Discharge rotolock 1 1 4 Oil equalisat...

Page 11: ...02 V04 352 518 117 155 232 99 Oil equalisation 3 8 Mounting hole for PTC crankcase heater 15 15 15 246 205 155 246 Suction rotolock 1 3 4 Discharge rotolock 1 1 4 233 210 125 209 98 95 Threaded oil si...

Page 12: ...ral hours to reset and restart the compressor The trickle circuit provides the facility of heating the compressor crankcase by feeding a small current to the auxiliary winding and the run capacitor Se...

Page 13: ...ickle circuit IOL Motor protector A C Run capacitors B Start capacitor C Common S Start winding auxiliary R Run winding main IOL Motor protector A C Run capacitors B Start capacitor C Common S Start w...

Page 14: ...1 20 5 03 NTZ108 72 45 57 21 4 12 1 11 1 20 4 00 2 54 NTZ136 97 2 51 64 29 14 3 15 0 98 3 80 2 54 NTZ215 147 7 74 110 42 3 22 3 23 0 57 2 23 1 26 NTZ271 198 96 150 56 5 27 0 30 0 41 1 61 0 84 Three ph...

Page 15: ...Vavg V2 3 2 xVavg voltage unbalance x 100 Internal motor protection Voltage unbalance Motor protection Three phase compressors are internally protected by a temperature current sensing bimetallic pro...

Page 16: ...ts the settings must ensure that the compressor start up time is always less than 0 5 seconds In case of use with R454C or R455A make sure that the softstarter selected is compatible with A2L refriger...

Page 17: ...CC China Compulsory Product Certification Models with motor voltage code 4 5 NTZ271 4 is out of CCC scope EAC Eurasian conformity mark Models with motor voltage code 4 5 Approvals and certificates Pre...

Page 18: ...tions Danfoss recommends the use of these refrigerants with NTZ compressors Note that R404A has a small temperature glide It must therefore be charged in the liquid phase For most other aspects howeve...

Page 19: ...HFO Blend with similar thermodynamic properties to R404A R455A is a zeotropic refrigerant with a temperature glide of about 12K and must therefore be charged in liquid phase R455A is classified A2L wi...

Page 20: ...ollowing table A high pressure HP safety switch is required to shut down the compressor should the discharge pressure exceed the values shown in the table below This switch can be set at lower values...

Page 21: ...il in a refrigeration circuit is required to lubricate moving parts in the compressor During normal system operation small oil quantities will continuously leave the compressor with the discharge gas...

Page 22: ...condensing temperature and condensing pressure in air cooled condensors will decrease This low pressure may be insufficient to supply enough liquid refrigerant to the evaporator As a result the evapor...

Page 23: ...standstill and after pressure equalisation refrigerant will condensate in the coldest part of the system which may be the compressor when it is placed in a cold environment Ultimately the full system...

Page 24: ...e migration of refrigerant and proves effective if oil temperature is maintained 10 K above the saturated LP temperature of the refrigerant Tests must thereby be conducted to ensure that the appropria...

Page 25: ...y mounted to the base frame otherwise high vibration transmission would occur and the service life reduced Suction and discharge lines must have adequate flexibility in 3 planes Eventually vibration a...

Page 26: ...mpressor in an upright position during all handling tasks manipulating transport storage The angle off the vertical must not exceed 15 degrees System contamination is one of the main factors that affe...

Page 27: ...rge connection and the risk of an oil mist blow out via the suction connection will be minimal Whenever possible the compressor must be the last component to be integrated in the system It is advisabl...

Page 28: ...rom Step 1 When the pressure slowly increases this indicates the presence of moisture In this case Steps 2 and 3 should be repeated 4 Connect the compressor to the system by means of opening the valve...

Page 29: ...sulated on the discharge tube 10 cm far from the compressor body The maximum allowed discharge temperature is 135 C Power and current consumption shall be compared with the table values at measured ev...

Page 30: ...120F0291 120F0241 NTZ271 120F0292 120F0243 Compressor model Single pack Multi pack Industrial pack Weight kg Dimensions mm Qty Weight kg Dimensions mm Static stacking Qty Weight kg Dimensions mm Stat...

Page 31: ...8153122 Rotolock nut 1 Models with 1 rotolock connection Multipack 10 8153123 Rotolock nut 1 1 4 Models with 1 1 4 rotolock connection Multipack 10 8153124 Rotolock nut 1 3 4 Models with 1 3 4 rotoloc...

Page 32: ...PTC heater 27W All models Multipack 10 PTC27W 120Z0460 PTC heater 27W All models Industry pack 50 Type Code n Description Application Packaging Pack size CSR 7701021 Relay Capacitors run 15 10 F start...

Page 33: ...ting kit 2 cyl NTZ 096 108 Single pack 1 120Z0764 Mounting kit 2 cyl HP NTZ 136 3 4 9 Single pack 1 8156007 Mounting kit 4 cyl NTZ215 271 Single pack 1 Type Code n Description Application Packaging Pa...

Page 34: ...document The safety and reliability risk icons are added Page 8 Nominal performance data for R454C is added Page 16 Pressure equipment directive Refrigerant Group 1 is added Page 18 Operating conditi...

Page 35: ......

Page 36: ...d us as distinct variable speed technology specialists Today we operate from engineering and manufacturing facilities spread across three continents AB245486497018en 000601 Danfoss DCS CC 2021 06 Our...

Reviews: