System design recommendations

Oil charge and oil 
separator

Filter driers

Suction pressure control

Suction line heat 
exchanger

In most installations the initial compressor oil 
charge will be sufficient. In installations with line 
runs exceeding 20 m, or with many oil traps or an 
oil separator, additional oil may be required. In 

installations with the risk of slow oil return such 
as in multiple evaporator or multiple condenser 
installations, an oil separator is recommended. 
Also refer to the section "Oil charge and oil level".

For new installations with NTZ compressors 
Danfoss recommends using the Danfoss DML 
100% molecular sieve, solid core filter drier. 
Molecular sieve filter driers with loose beads 
from third party suppliers shall be avoided.

For servicing of existing installations where acid 
formation is present the Danfoss DCL solid core 

filter driers containing activated alumina are 
recommended.

The drier is to be oversized rather than 
undersized. When selecting a drier, always 
take into account its capacity (water content 
capacity), the system refrigerating capacity and 
the system refrigerant charge.

An MOP-type expansion valve or suction 
pressure regulator (i.e. Danfoss KVL) must be 
used to limit suction pressure at a maximum of 
4 bar relative (-5°C).  Do not apply both of these 
devices in combination with one another.

When compressors are mounted onto a rack 
for a multi-evaporator system (i.e. supermarket) 
or when evaporators operate at different 
temperatures, use pressure regulators (Danfoss 
KVP) without an MOP expansion valve.

A suction line heat exchanger is recommended 
for low temperature applications, better 
performance and efficiency are expected. 

However in hot location this may cause high 
suction gas superheat which can result in too 
high discharge temperature.

Low ambient temperature 
operation

At low ambient temperatures, the condensing 
temperature and condensing pressure in air 
cooled condensors will decrease. This low 
pressure may be insufficient to supply enough 
liquid refrigerant to the evaporator. As a result 
the evaporating temperature will decrease, 
leading to low capacity and eventual poor oil 
return. At start-up, the compressor will pull into 
vacuum and it will be switched off by the low 
pressure protection. Depending on how the low 
pressure switch and delay timer are set, short 
cycling can occur. To avoid these problems, 
several solutions are possible, based on reducing 
condenser capacity:

In air-cooled machines, cycling the fans with 
a head pressure controller will ensure that the 
fans remain off until the condensing pressure 
has reached a satisfactory level. Variable speed 
fans can also be used to control the condensing 
pressure. In water-cooled units, the same can 
be performed using a water regulator valve 
that is also operated by head pressure, thereby 
ensuring that the water valve does not open until 
the condensing pressure reaches a satisfactory 
level.

The minimum condensing pressure must be 
set at the minimum saturated condensing 
temperature shown in the application envelopes.

Under very low ambient conditions, in which 
testing has revealed that the above procedures 
might not ensure satisfactory condensing and 
suction pressures, the use of a head pressure 
control valve is recommended. Note: This 
solution requires extra refrigerant charge, which 
can introduce other problems. A non-return 
valve in the discharge line is recommended and 
special care should be taken when designing the 
discharge line.

When the compressor is located in a low ambient 
temperature environment, increased refrigerant 
migration will occur during shut down periods. 
For such conditions an extra belt-type crankcase 
heater is strongly recommended.

Note that with 100% suction gas cooled motors, 
Maneurop® compressors can be externally 
insulated. Refer to section "Liquid refrigerant 
migration & charge limits" for more details.

AB245486497018en-000601

22

Application Guidelines

Summary of Contents for Maneurop NTZ

Page 1: ...Maneurop reciprocating compressors NTZ 50 60 Hz Group 2 R404A R507A R452A Group 1 R454C R455A Application guidelines http cc danfoss com...

Page 2: ......

Page 3: ...certificates 17 Pressure equipment directive 2014 68 EU 17 Low voltage directive 2014 35 EU 17 Machinery directive 2014 30 EU 17 Internal free volume 17 Operating conditions 18 Refrigerants and lubri...

Page 4: ...to avoid safety risk This icon indicates instructions to avoid reliability risk The purpose of this guideline is informational with the intent to educate customers as to how the compressors should pr...

Page 5: ...be operated at a return gas temperature suction gas temperature of 20 C even at low evaporating temperatures A liquid injection system is not required All components are of high quality and precision...

Page 6: ...conditions R404A Evap temp 35 C Cond temp 40 C RGT 20 C SC 0K For full NTZ data details and capacity tables refer to selection software Coolselector 2 NT Z 4 L 048 A R1 B Motor voltage code Z Polyole...

Page 7: ...52 1 19 NTZ271 4 7090 6 64 9 65 1 07 8210 6 64 9 65 1 24 R452A Refrigeration Compressor model 50 Hz EN12900 ratings To 35 C Tc 40 C SC 0K SH 10K 50 Hz EN12900 ratings To 35 C Tc 40 C SC 0K RGT 20 C Co...

Page 8: ...16 3 41 0 89 1177 1 25 3 11 0 94 Compressor model 50 Hz EN12900 ratings To 35 C Tc 40 C SC 0K SH 10K 60 Hz EN12900 ratings To 35 C Tc 40 C SC 0K SH 10K Cooling capacity W Power input kW Current input...

Page 9: ...se heater 25 98 Schrader 1 4 263 333 353 NTZ068 1 Suction rotolock 1 1 4 Discharge rotolock 1 68 82 109 118 35 33 68 Suction 147 Discharge 142 159 17 17 123 39 Threaded oil sight glass 141 224 68 HM8...

Page 10: ...179 Discharge 176 252 288 413 32 Threaded oil sight glass Schrader 1 4 PTC crankcase heater 96 21 145 125 188 171 8 38 82 1 98 2 74 68 265 Suction rotolock 1 3 4 Discharge rotolock 1 1 4 Oil equalisat...

Page 11: ...02 V04 352 518 117 155 232 99 Oil equalisation 3 8 Mounting hole for PTC crankcase heater 15 15 15 246 205 155 246 Suction rotolock 1 3 4 Discharge rotolock 1 1 4 233 210 125 209 98 95 Threaded oil si...

Page 12: ...ral hours to reset and restart the compressor The trickle circuit provides the facility of heating the compressor crankcase by feeding a small current to the auxiliary winding and the run capacitor Se...

Page 13: ...ickle circuit IOL Motor protector A C Run capacitors B Start capacitor C Common S Start winding auxiliary R Run winding main IOL Motor protector A C Run capacitors B Start capacitor C Common S Start w...

Page 14: ...1 20 5 03 NTZ108 72 45 57 21 4 12 1 11 1 20 4 00 2 54 NTZ136 97 2 51 64 29 14 3 15 0 98 3 80 2 54 NTZ215 147 7 74 110 42 3 22 3 23 0 57 2 23 1 26 NTZ271 198 96 150 56 5 27 0 30 0 41 1 61 0 84 Three ph...

Page 15: ...Vavg V2 3 2 xVavg voltage unbalance x 100 Internal motor protection Voltage unbalance Motor protection Three phase compressors are internally protected by a temperature current sensing bimetallic pro...

Page 16: ...ts the settings must ensure that the compressor start up time is always less than 0 5 seconds In case of use with R454C or R455A make sure that the softstarter selected is compatible with A2L refriger...

Page 17: ...CC China Compulsory Product Certification Models with motor voltage code 4 5 NTZ271 4 is out of CCC scope EAC Eurasian conformity mark Models with motor voltage code 4 5 Approvals and certificates Pre...

Page 18: ...tions Danfoss recommends the use of these refrigerants with NTZ compressors Note that R404A has a small temperature glide It must therefore be charged in the liquid phase For most other aspects howeve...

Page 19: ...HFO Blend with similar thermodynamic properties to R404A R455A is a zeotropic refrigerant with a temperature glide of about 12K and must therefore be charged in liquid phase R455A is classified A2L wi...

Page 20: ...ollowing table A high pressure HP safety switch is required to shut down the compressor should the discharge pressure exceed the values shown in the table below This switch can be set at lower values...

Page 21: ...il in a refrigeration circuit is required to lubricate moving parts in the compressor During normal system operation small oil quantities will continuously leave the compressor with the discharge gas...

Page 22: ...condensing temperature and condensing pressure in air cooled condensors will decrease This low pressure may be insufficient to supply enough liquid refrigerant to the evaporator As a result the evapor...

Page 23: ...standstill and after pressure equalisation refrigerant will condensate in the coldest part of the system which may be the compressor when it is placed in a cold environment Ultimately the full system...

Page 24: ...e migration of refrigerant and proves effective if oil temperature is maintained 10 K above the saturated LP temperature of the refrigerant Tests must thereby be conducted to ensure that the appropria...

Page 25: ...y mounted to the base frame otherwise high vibration transmission would occur and the service life reduced Suction and discharge lines must have adequate flexibility in 3 planes Eventually vibration a...

Page 26: ...mpressor in an upright position during all handling tasks manipulating transport storage The angle off the vertical must not exceed 15 degrees System contamination is one of the main factors that affe...

Page 27: ...rge connection and the risk of an oil mist blow out via the suction connection will be minimal Whenever possible the compressor must be the last component to be integrated in the system It is advisabl...

Page 28: ...rom Step 1 When the pressure slowly increases this indicates the presence of moisture In this case Steps 2 and 3 should be repeated 4 Connect the compressor to the system by means of opening the valve...

Page 29: ...sulated on the discharge tube 10 cm far from the compressor body The maximum allowed discharge temperature is 135 C Power and current consumption shall be compared with the table values at measured ev...

Page 30: ...120F0291 120F0241 NTZ271 120F0292 120F0243 Compressor model Single pack Multi pack Industrial pack Weight kg Dimensions mm Qty Weight kg Dimensions mm Static stacking Qty Weight kg Dimensions mm Stat...

Page 31: ...8153122 Rotolock nut 1 Models with 1 rotolock connection Multipack 10 8153123 Rotolock nut 1 1 4 Models with 1 1 4 rotolock connection Multipack 10 8153124 Rotolock nut 1 3 4 Models with 1 3 4 rotoloc...

Page 32: ...PTC heater 27W All models Multipack 10 PTC27W 120Z0460 PTC heater 27W All models Industry pack 50 Type Code n Description Application Packaging Pack size CSR 7701021 Relay Capacitors run 15 10 F start...

Page 33: ...ting kit 2 cyl NTZ 096 108 Single pack 1 120Z0764 Mounting kit 2 cyl HP NTZ 136 3 4 9 Single pack 1 8156007 Mounting kit 4 cyl NTZ215 271 Single pack 1 Type Code n Description Application Packaging Pa...

Page 34: ...document The safety and reliability risk icons are added Page 8 Nominal performance data for R454C is added Page 16 Pressure equipment directive Refrigerant Group 1 is added Page 18 Operating conditi...

Page 35: ......

Page 36: ...d us as distinct variable speed technology specialists Today we operate from engineering and manufacturing facilities spread across three continents AB245486497018en 000601 Danfoss DCS CC 2021 06 Our...

Reviews: