Checking GFCI
It is important that the GFCI has been 
checked for correct installation and function. 

To check the GFCI: Testing can only be 
performed if the thermostat has a heat-
ing demand. Adjust the set point until the 
heating symbol (SSS) appears, use the (   ), 
to increase the heating demand. Wait 10 
secs. to let the thermostat work according to 
the new set point. Press the button “TEST”. 
The test is conclusive if the red light on the 
thermostat lightens, and the display signs 
disappear. If this does not occur, check the 
installation. Press on RESET button to reset 
the GFCI. The red light should disappear and 

the display will return to normal appearance. 
If the test fails, check your heating cable and 
the thermostat. The GFCI test should be car-
ried out monthly.

If the GFCI trips in normal operation, without 
pressing the TEST button, there could be a 
ground fault! To check whether it is a ground 
fault or a nuisance tripping, press RESET. If 
this cause the red light to shot off and not 
comes on again, it was a nuisance tripping 
and the system is functioning. If this cannot 
be done there is a ground fault! Check your 
heating cable, the sensor cable and the ther-
mostat. Exchange the defective part. 

3. Reset to factory setting

Press the pin button for 3 secs. and the thermostat returns to factory 
settings. 

Factory settings

With fl oor sensor

Built-in sensor

77˚F / 25˚C

68˚F / 20˚C

68˚F / 20˚C

59˚F / 15˚C

 SCALE

˚F

˚F

4. Failure codes
E0 

=  Internal failure, replace thermostat

E1 =  

Built-in sensor short-circuit or dis-
connected, replace thermostat

E2 =  

External sensor short-circuit or 
disconnected

5. Technical data
Supply:    120/240 Vac 50/60 Hz
Load:     16A maximum (resistive load)
Power:     1.920 W at 120 Vac
                3.840 W at 240 Vac
GFCI:     Class A (5 mA trip level)

Temperature range:  

 +5 to +40°C, 
+40 to +104˚F

Amb. Temperature range:

Thermostat:  

 0 to +40°C, 
+32 to +104˚F

GFCI:    

-35 to +65°C, 

 

 

 

-31 to +149˚F

Summary of Contents for LX 420

Page 1: ...Table of contents English 2 Fran ais 5 USER MANUAL LX 420 421 088L3353 01 01 57470...

Page 2: ...erature of the floor and not the temperature within the room The thermostat type LXstat 421 has a built in temperature sensor In this configuration the thermostat controls the temperature of the room...

Page 3: ...Night Setback temperature To change the temperature press UP or DOWN to increase or decrease the tempera ture The display will flash for 5 seconds and will then show the new temperature setpoint OFF T...

Page 4: ...tton there could be a ground fault To check whether it is a ground fault or a nuisance tripping press RESET If this cause the red light to shot off and not comes on again it was a nuisance tripping an...

Page 5: ...stat LXstat 421 est dot d un capteur de temp rature int gr Dans cette configuration le thermostat con tr le la temp rature de la pi ce Le thermostat dispose de deux points de consigne r glables un pou...

Page 6: ...p rature appuyez sur les touches de d filement vers le haut ou vers le bas respectivement pour lever ou abaisser la temp rature L affichage clignotera pendant cinq secondes puis indiquera le nouveau p...

Page 7: ...rmale Si le test choue v rifiez le c ble chauffant et le ther mostat Le test du disjoncteur de fuite la terre devrait tre effectu mensuellement Si le disjoncteur se d clenche en mode de fonctionnement...

Page 8: ...ermostat de 0 40 C 32 104 F GFCI 35 65 C 31 149 F Danfoss can accept no responsibility for possible errors in catalogues brochures and other printed material Danfoss reserves the right to alter its pr...

Reviews: