Adjustment:  
Low Pressure Switch 

Cut out on pressure fall  
with automatic reset.

Scale plate directly indicates  
the Cut In and the Differential  
set points.

1. 

Set Cut In by adjusting range screw.  

Turn the screw clockwise to lower the set point.

2.

 Then set Differential by adjusting differential screw. Turn the 

screw clockwise to increase the Differential.

3. 

The Cut Out setting equals the Cut In  

less the Differential: CUT OUT = CUT IN - DIFFERENTIAL

Adjustment:  
Condenser Fan Cycling

Scale plate directly indicates  
the Cut In and the Differential  
set points.

1. 

Set Cut In by adjusting range screw.  

Turn the screw clockwise to lower the set point.

2.

 Then set Differential by adjusting differential screw. Turn the 

screw clockwise to increase the Differential.

3.

The Cut Out setting equals the Cut In less  

the Differential: CUT OUT = CUT IN - DIFFERENTIAL

Adjustment:  
Low Pressure Switch

Cut out on pressure fall  
with manual reset.

Scale plate directly indicates the Cut 
Out set point. There is no pointer for 
the Differential. 
The Differential pressure value is 
fixed and printed on the scale plate.

Adjustment:  
High Pressure Switch 

Cut Out on pressure  
rise with automatic reset.

Scale plate directly indicates  
the Cut Out and the Differential  
set points.

1. 

Set Cut Out by adjusting range screw.  

Turn the screw clockwise to lower the set point.

2.

 Then set Differential by adjusting differential screw. Turn the 

screw clockwise to decrease the Differential.

3. 

The Cut In setting equals the Cut Out  

less the Differential: CUT IN = CUT OUT - DIFFERENTIAL

Adjustment:  
High Pressure Switch

Cut Out on pressure  
rise with manual reset.

Scale plate directly indicates  
the Cut Out set point. 
There is no pointer for the 
Differential. 
The Differential pressure value is 
fixed and printed on the scale plate.

1. 

Set Cut Out by adjusting range screw.  

Turn the screw clockwise to lower the set point.

2.

 The Cut In setting equals the Cut Out  

less the Differential: CUT IN = CUT OUT - 60 psi

1. 

Set Cut Out by adjusting range screw.  

Turn the screw clockwise to lower the set point.

2.

 The Cut In setting equals the Cut Out plus  

the Differential: CUT IN = CUT OUT + 10 psi

NOTE: 

Cut Out set point must be above absolute vacuum!  
If the Differential is set too high then the switch  
will not stop the compressor. 

IMPORTANT:

The scale plate is only for reference and for more 
precise setting a pressure gauge should be used.

IMPORTANT:

After installing and adjusting pressure switch run the 
controlled equipment several times (at least three 
cycles) at normal operating conditions.