Contact function test (Manual trip)

When the electrical leads are connected the contact function 

can be manually tested regardless of pressure condition in 

the system. The manual trip lever is located in the left side 

of the KPU. It must be operated with fingers only. Do not use 

screwdriver as it will damage the switch.

NOTE: 

While operating the manual trip on KPU  

switches with manual reset it is necessary  

to push the reset knob.

NOTE: 

Adjust the pressure switch with settings specified by the 

manufacturer of the controlled quipment. 

Do not exceed the pressure ratings of the controlled 

equipment or any of its components when checking 

pressure switch operation or operating the controlled 

equipment.

Do not adjust pointers beyond the highest or lowest 

indicator marks on the scale plate, as this may cause

inaccurate switch operation.

A: Manual trip. Press the lever up. USE FINGERS ONLY!

B: Manual reset button  

(available only for contols with manual reset function)

C: Terminal block

D: Grounding screw

A: Differential adjusting screw

B: Locking plate

C: Range adjusting screw

D: Cover screw

Adjustment

Before adjustment, loosen the locking plate.

For setting use the Universal Refrigeration Wrench.

Wire dimensions: 10 AWG max.

Cable entry: 

7

/

8

 in. cable entry for ½ in. male pipe thread 

connection (conduit boss) or similar (Pg13.5 or Pg16) screwed 

cable entry.

Wiring Option A:

– Low Pressure Switch Cut Out on pressure fall

– Condenser Fan Cycling

Wiring Option B:

– High Pressure Switch Cut Out on pressure rise

Load

~Line

Summary of Contents for KPU Series

Page 1: ...lose High open Low 6 in 108 10 60 250 290 KPU 2 060 5237 060 5235 Auto SPST NO close High open Low 6 in 73 6 30 250 290 KPU 2 060 5239 060 5240 Auto SPDT 6 in 73 6 30 250 290 KPU1B 060 5232 060 5234 Man Min SPDT 28 in 100 10 fixed 250 290 Fan switch KPU 5 060 5241 060 5242 Auto SPST NO close High open Low 100 465 25 85 510 530 High Pressure Switch Cut Out on pressure rise KPU 6W 060 5243 060 5245 ...

Page 2: ...switch NOTE After installing the pressure switch evacuate the plant in accordance with applicable EPA and other regulations to remove air moisture and other contaminants Screws for bracket mounting Mounting holes for flat surfaces 120 V AC 24 FLA 144 LRA make only 240 V AC 24 FLA 144 LRA make only 240 V DC 12 W pilot duty Wiring Electrical ratings according to UL regulations European electrical ra...

Page 3: ... its components when checking pressure switch operation or operating the controlled equipment Do not adjust pointers beyond the highest or lowest indicator marks on the scale plate as this may cause inaccurate switch operation A Manual trip Press the lever up USE FINGERS ONLY B Manual reset button available only for contols with manual reset function C Terminal block D Grounding screw A Differenti...

Page 4: ...ressure rise with automatic reset Scale plate directly indicates the Cut Out and the Differential set points 1 Set Cut Out by adjusting range screw Turn the screw clockwise to lower the set point 2 Then set Differential by adjusting differential screw Turn the screw clockwise to decrease the Differential 3 The Cut In setting equals the Cut Out less the Differential CUT IN CUT OUT DIFFERENTIAL Adju...

Reviews: