Installation guide

Pressure switch

 

KPU 

06

0R

976

7

06

0R

976

7

© Danfoss | DCS (jmn) | 2016.11

DKRCC.PI.CD0.F4.22 | 520H11543 | 1

Application

KPU pressure switches are for use on commercial  

refrigeration and air conditioning systems to give protection 

against excessively low suction pressure or excessively  

high discharge pressure. 
They are also used for starting and stopping refrigeration 

compressors and fans on air-cooled condensers.

KPU pressure switches are fitted with the Single-Pole Single-

Throw (SPST) or Single-Pole Double-Throw (SPDT) switches, 

suitable for direct as well as indirect (with a contactor) control.
KPU pressure switches are available in several pressure ranges 

and are compatible with refrigerants listed below. KPU 6W and 

KPU 6B are fail safe switches for high pressure refrigerants. 

Standard enclosure is ~NEMA 1.

Product Specification

Application

Type

Code number

Reset

Contact system

Regulating 

range 

[inHg] [psig]

Differential  

∆p

[psi]

Max.  

working 

pressure 

[psig]

Max. 

testing 

pressure

[psig]

Ambient  

temp.

[°F]

¼ in 

male flare

36 in. cap. 

tube w. ¼ 

in flare nut

Type

Switch 

action

Low Pressure 

Switch Cut Out 

on pressure 

fall

KPU 1

060-5231

060-5233

Auto.

SPDT

6 in. – 108

10 – 60

250

290

-40 – 122

(175 for 

max.  

2 hours)

KPU 1

060-5236

Auto.

SPST(NO) close High open Low

6 in. – 108

10 – 60

250

290

KPU 2

060-5237

060-5235

Auto.

SPST(NO) close High open Low

6 in. – 73

6 – 30

250

290

KPU 2

060-5239

060-5240

Auto.

SPDT

6 in. – 73

6 – 30

250

290

KPU1B 060-5232

060-5234

Man (Min.)

SPDT

28 in. – 100

10 fixed

250

290

Fan switch

KPU 5

060-5241

060-5242

Auto.

SPST(NO) close High open Low

100 – 465

25 – 85

510

530

High Pressure 

Switch 

Cut Out on 

pressure rise

KPU 6W 060-5243

060-5245

Auto.

SPDT

100 – 600

58 – 145

675 / 610*

725

KPU 

6B

060-5244

060-5246

Man. (Max.)

SPDT

100 – 600

60 fixed

675 / 610*

725

* 610psig - MWP for products used according to 97/23/EG PED directive.

Refrigerants:

R22, R134a, R404A, R407A, R407C, R407F, R410A*), R422B, 

R422D, R438A, R448A, R449A, R450A, R452A, R507A, R513A

For complete list of approved refrigerants, go to 

http://products.danfoss.com/all-products/
*) R410A only for KPU 6W and KPU 6B

Installation

Select an accessible location, where the switch and pressure  connection line will not be subject to damage.

IMPORTANT:

Mount the pressure switch in a position that 

will allow drainage of liquids away from switch 

bellows. Pressure connection of the switch 

must always be located on the top side of the 

refrigerant line. 

This reduces the possibility of oil, liquids, or 

sediment collecting in the bellows, which could 

cause the switch malfunction.

IMPORTANT:

Ensure the ambient temperature for the pressure 

switch is higher than the refrigeration line as that 

will prevent liquid migration and accumulation in 

the bellows.

Summary of Contents for KPU Series

Page 1: ...lose High open Low 6 in 108 10 60 250 290 KPU 2 060 5237 060 5235 Auto SPST NO close High open Low 6 in 73 6 30 250 290 KPU 2 060 5239 060 5240 Auto SPDT 6 in 73 6 30 250 290 KPU1B 060 5232 060 5234 Man Min SPDT 28 in 100 10 fixed 250 290 Fan switch KPU 5 060 5241 060 5242 Auto SPST NO close High open Low 100 465 25 85 510 530 High Pressure Switch Cut Out on pressure rise KPU 6W 060 5243 060 5245 ...

Page 2: ...switch NOTE After installing the pressure switch evacuate the plant in accordance with applicable EPA and other regulations to remove air moisture and other contaminants Screws for bracket mounting Mounting holes for flat surfaces 120 V AC 24 FLA 144 LRA make only 240 V AC 24 FLA 144 LRA make only 240 V DC 12 W pilot duty Wiring Electrical ratings according to UL regulations European electrical ra...

Page 3: ... its components when checking pressure switch operation or operating the controlled equipment Do not adjust pointers beyond the highest or lowest indicator marks on the scale plate as this may cause inaccurate switch operation A Manual trip Press the lever up USE FINGERS ONLY B Manual reset button available only for contols with manual reset function C Terminal block D Grounding screw A Differenti...

Page 4: ...ressure rise with automatic reset Scale plate directly indicates the Cut Out and the Differential set points 1 Set Cut Out by adjusting range screw Turn the screw clockwise to lower the set point 2 Then set Differential by adjusting differential screw Turn the screw clockwise to decrease the Differential 3 The Cut In setting equals the Cut Out less the Differential CUT IN CUT OUT DIFFERENTIAL Adju...

Reviews: