CAUTION:
Disconnect power supply before wiring connections
are made or service to avoid possible electrical shock
or damage to equipment. Do never touch live parts
with your fingers or with any tool.
P
test
max.
Standard contact
Alternating current
AC-1 : 10A, 440V
AC-3 : 6A, 440V
AC-15: 4A, 440V
Blocked rotor: 112A
Direct current:
DC-13, 12W, 220V
Voltage
FL
LR
Resist.
load
Pilot
duty
AC
DC
A
A
240
—
6
36
8A
3A
120
—
8
48
10A
—
240
—
—
—
12W
Listed refrigeration
controller 61B5
Use copper wire only
Tightening torque 20 lb. in.
2
IC.PI.P10.D5.02 / 520B5862 .
© Danfoss A/S (AC-MCI/jmn), 2013-11
Type
Range
Diff.
KPI 34
-0.2 − 3 bar
0.5 − 1.25 bar
KPI 35
-0.2 − 8 bar
0.4 − 2 bar
KPI 36
4 − 12 bar
0.5 − 1.6 bar
KPI 38
8 − 28 bar
1.8 − 6 bar
Please note:
No maintenance is required for the
switches after final installation.
KPI 34, KPI 35, KPI 36, KPI 38
t
1
min. -40 °C
t
1
max. 65 °C
t
2
min. -40 °C
t
2
max. 100 °C
KPI 34: 18 bar
KPI 35: 18 bar
KPI 36: 18 bar
KPI 38: 30 bar
Please note:
scale in KP units is indicative only.
For accurate setting or when using according to FM
aproval use additional pressure gauge to set the unit.