CAUTION:

Disconnect power supply before wiring connections 

are made or service to avoid possible electrical shock 

or damage to equipment. Do never touch live parts 

with your fingers or with any tool. 

P

test

 max.

Standard contact 
Alternating current

AC-1 :    10A, 440V
AC-3 :        6A, 440V
AC-15:       4A, 440V
Blocked rotor: 112A

Direct current:

DC-13, 12W, 220V

Voltage

FL

LR

Resist.

load

Pilot

duty

AC

DC

A

A

240

6

36

8A

3A

120

8

48

10A

240

12W

Listed refrigeration

controller 61B5

Use copper wire only
Tightening torque 20 lb. in.

IC.PI.P10.D5.02 / 520B5862 .  

© Danfoss A/S (AC-MCI/jmn), 2013-11

Type

Range

Diff.

KPI 34

-0.2 − 3 bar

0.5 − 1.25 bar

KPI 35

-0.2 − 8 bar

0.4 − 2 bar

KPI 36

4 − 12 bar

0.5 − 1.6 bar

KPI 38

8 − 28 bar

1.8 − 6 bar

Please note:

 No maintenance is required for the 

switches after final installation.

KPI 34, KPI 35, KPI 36, KPI 38

t

1

 min. -40 °C

t

1

 max. 65 °C

t

2

 min. -40 °C

t

2

 max. 100 °C

KPI 34: 18 bar

KPI 35: 18 bar

KPI 36: 18 bar

KPI 38: 30 bar

Please note:

 scale in KP units is indicative only. 

For accurate setting or when using according to FM 

aproval use additional pressure gauge to set the unit.