Loosen screws 1 (Fig. 6) and remove the front cover. Route the wire through Cable entry 1 (Fig. 7);  connect contacts to the corresponding 

terminals 2. Connect the earth wire to the corresponding terminal (Fig. 7). Put the protective cover on the switch housing and tighten the 

screws 1. Fig. 6. Fasten the temperature housing to a flat surface using the supplied bracket. 

When mounted on a wall bracket, the permissible vibration of the switch housing is within the range of 0–1,000 Hz, 4 g. Install the capillary 

tube in the air duct, or in any other area where temperature control is required, using the supplied mounting plastic corners. The minimum 

length of the capillary tube in thermal contact with a controlled environment is as follows:

1

Danf

os

s

60-601.10

1

2

Danf

os

s

60-600.10

Capillary Tube Length, m

Min. Length |АВ|, m

1

0.2

2

0.25

3

0.28

4

0.35

6

0.43

11.5

0.63

Switch Version

Danf

oss

60-603

Safety Warning

Temperature switches must be used strictly for their intended purpose indicated in the technical documentation. Only personnel who have 
studied the design and safety regulations may service the device.

Acceptance and Testing

The products specified in this manual are manufactured, tested and accepted in accordance with the applicable technical documentation of 
the manufacturer.

Warranty

The supplying manufacturer guarantees the compliance of KP temperature switches with the technical requirements, provided that the 
consumer observes the conditions for handling, storage and operation. The warranty period for the operation and storage of KP temperature 
switches is 12 months from the date of shipment from the warehouse of the manufacturer or seller.

Scope of Supply

The scope of supply includes: KP 61 temperature switch, wall bracket with screws, plastic fasteners for the capillary tube with screws, user 
guide.

Marking and Packaging

Information on the manufacturer’s trademark, product designation, code number, date of manufacture and main technical characteristics are 
provided on the product’s housing and/or packaging.

Maintenance and Service

Product maintenance involves compliance with the regulations for the operation, storage and handling specified in this guide, and routine 
inspections that must be carried out in the manner established by the operating facility at least twice a year and must include visual  
examination and inspection of its functioning. It is prohibited to operate a damaged or malfunctioning product. For information about 
repairs, please contact the Danfoss service department: https://www.danfoss.com/en/contact-us/