Adjustment spindles location
Note!
Remove lockplate before thermostat
adjustment. Replace lockplate after
adjustment (if desired).
RANGE
DIFFERENTIAL
See printed instruction on top of control
See printed instruction on top of control
increase temp. (warmer): turn CW
Increase: turn CW
decrease temp. (colder): turn CCW
decrease: turn CCW
(use adjustment knob)
(use adjustment knob or screwdriver)
Determination of diff erential
For KP w/ vapor charge and auto. reset (KP 61, KP 62, KP 63, KP 68, KP 69): Use graphs to determine correct diff erential
Example:
HSP = +45°F (+5.6°C)
=>
DIFF (from graph):
LSP = +32°F (0°C
13°F (7.2°C) (value which has to be
set on diff . scale).
For KP w/ adsorption charge (KP 71, KP 73, KP 75, KP 77, KP 79, KP 81):
The diff erential will be HSP less LSP
Example: HSP
–
LSP
=
DIFF.
45°F
–
35°F
=
10°F
(7°C)
(5°C)
(2°C)
Note:
(Load Option A)
(Load Option B)
CUT-IN
= HSP or
CUT-IN
= LSP
CUT-OUT = LSP
CUT-OUT = HSP
See “Wiring”