background image

© 

Danfoss 

A/S 

   RI.5D.A2.22 

 DKRCC.PI.C0A.A1.22-520H2749   

 

 

3

Adjustment spindles location

Note!
Remove lockplate before thermostat
adjustment. Replace lockplate after
adjustment (if desired).

RANGE 

DIFFERENTIAL

See printed instruction on top of control 

See printed instruction on top of control

 

increase temp. (warmer): turn CW 

 

Increase: turn CW

 

decrease temp. (colder): turn CCW 

 

decrease: turn CCW

(use adjustment knob) 

(use adjustment knob or screwdriver)

Determination of diff erential

For KP w/ vapor charge and auto. reset (KP 61, KP 62, KP 63, KP 68, KP 69): Use graphs to determine correct diff erential

Example:
HSP = +45°F (+5.6°C) 

=> 

DIFF (from graph):

LSP = +32°F (0°C 

 

13°F (7.2°C) (value which has to be

 

 

set on diff . scale).

For KP w/ adsorption charge (KP 71, KP 73, KP 75, KP 77, KP 79, KP 81):
The diff erential will be HSP less LSP

Example: HSP 

– 

 

LSP 

 

DIFF.

 45°F 

– 

35°F 

10°F

 
 (7°C) 

 

(5°C) 

(2°C)

Note:
(Load Option A)  

 

(Load Option B)

CUT-IN 

=   HSP  or 

CUT-IN 

=   LSP

CUT-OUT =   LSP   

CUT-OUT  =   HSP

See “Wiring” 