background image

1.  Adjust range spindle to  

  desired CUT-IN value

2.  Adjust differential 

  spindle to desired 

  DIFFERENTIAL (DIFF.)  

 value

1.   Adjust range    

  spindle to desired  

  CUT-OUT value.

2.   DIFFERENTIAL (DIFF.)  

  is fixed. Value printed  

  on scale plate.

 DKRCC.PI.CD0.B2.02 / 520H8364  

© Danfoss A/S (AC-MCI /jmn), 2014-01

Caution:

Disconnect power supply before wiring connections are made or service to avoid possible electrical shock or 

damage to equipment. Do never touch live parts with your fingers or with any tool. 

Electrical connections

Setting

CONTROL side setting 

SAFETY side setting

CUT-IN equals CUT-OUT minus 

CUT-IN equals CUT-OUT plus 

DIFFERENTIAL    

DIFFERENTIAL

Example:  

 

 

 

Example:

CUT-OUT –  DIFF.   =  CUT-IN 

CUT-OUT  +  DIFF.    =   CUT-IN 

8 bar (116 psi)  –  2 bar (29 psi)  =  6 bar  (87 psi) 

4 bar (58 psi)  +  1 bar (15 psi)  =  5 bar (73 psi)  

Adjustment

 

Control side setting  

Control side differential

 

 

Safety side setting

Note:

Remove lockplate before adjustment

Replace lockplate after adjustment (if desired).

When used acc. to UL regulations

Listed refrigeration
controller 61B5

Voltage

FL

A

LR

A

Resist.

load

Pilot

duty

AC

DC

240
120

8

48

8 A

3 A

16

96

16 A

240

12 W

Use copper wire only
Tightening torque 20 lb.in.

AC 1: 16 A

400 V

AC 3: 16 A
AC 15: 10 A
DC 13: 12 W

220 V

Electrical ratings