RI5AK222 - 520H0146
3
Manual tripping
(Electrical contacts/wiring test)
LP side
HP side
TRIP
use FINGERS
ONLY!
(Do NOT use
screwdriver)
Note:
On controls with LP and/or HP man. reset, push
corresponding LP and/or HP man. reset knob during
tripping.
Manual tripping
To resume control operation after safety cut-
out, push man. reset knob as indicated.
Note:
LP man. reset is possible only after system
pressure has risen above cut-in value.
HP man. reset is possible only after system
pressure has dropped below cut-out value.
Convertible reset
KP 15, code nos.: 060-2025, 060-2028
Reset options
Turn plate to desired
LP man.
LP-auto.
LP-auto.
LP-man.
reset confi guration
HP-man. HP-man. HP-auto. HP-auto.
Adjustment spindle(s) location
KP 15
KP 15, KP 17B
KP 15, KP 17W, KP 25
A. MAN./MAN. RESET
B. AUTO/MAN. RESET
C. AUTO./AUTO. RESET