Pressure Controls

KP 15, KP 17W, KP 17B, KP 25

©Danfoss 

A/S 

      

RI5AK222 

520H0146

060R9747

060R9747

Instructions

Types

 

The controls can be used with CFC, HFC, HCFC refrigerants.

CAUTION: Do not install these controls on 
ammonia systems

KP 15 man. (LP) / man. (HP) reset 

KP 15, KP 17B auto. (LP) / man. (HP) reset 

KP 15, KP 17W, KP 25 auto. (LP) / auto (HP) reset

Ambient temperatures 

Test pressure (p

TEST

)

 

p

test

 max.

505 psig
(35 bar p

e

)

p

test

 max.

285 psig
(20 bar p

e

)

t

1

 min.  KP 15, KP 25: 

–40°F (–40°C)

 

KP 17W, KP 17B: 

–13°F (–25°C)

t

1

 max.   

150°F (65°C)

CAUTION: Do not mount the control in a position where dirt, sediment,
or oil will aff ect the operation of the control.

Enclosure

CAUTION: The mounting panel must be plane to avoid damage of control.

Summary of Contents for KP 15

Page 1: ...P reset KP 15 KP 17B auto LP man HP reset KP 15 KP 17W KP 25 auto LP auto HP reset Ambient temperatures Test pressure pTEST ptest max 505 psig 35 bar pe ptest max 285 psig 20 bar pe t1 min KP 15 KP 25 40 F 40 C KP 17W KP 17B 13 F 25 C t1 max 150 F 65 C CAUTION Do not mount the control in a position where dirt sediment or oil will affect the operation of the control Enclosure CAUTION The mounting pa...

Page 2: ...n LP drop See label for current wiring inside cover Controls with low pressure LP and high pressure HP signal KP 15 and KP 17W Only code nos 060 2024060 2027 060 2030 060 2026060 2029 060 2031 stamped on top of control Terminal block CAUTION Use terminal screws furnished in the contact block Use tightening torque 20 lb in 2 3 Nm Use copper wire only Low pressure LP side A C close on LP rise A C op...

Page 3: ...cut out push man reset knob as indicated Note LP man reset is possible only after system pressure has risen above cut in value HP man reset is possible only after system pressure has dropped below cut out value Convertible reset KP 15 code nos 060 2025 060 2028 Reset options Turn plate to desired LP man LP auto LP auto LP man reset configuration HP man HP man HP auto HP auto Adjustment spindle s lo...

Page 4: ...TIAL DIFF 2 DIFFERENTIAL DIFF spindle to desired is fixed is fixed DIFFERENTIAL Value printed on Value printed on DIFF value scale plate scale plate CUT IN minus DIFFERENTIAL equals CUT IN equals CUT OUT plus CUT OUT minus DIFFERENTIAL equals CUT OUT DIFFERENTIAL CUT IN Example Example Example CUT IN DIFF CUT OUT CUT OUT DIFF CUT IN CUT OUT DIFF CUT IN 30 psig 10 psi 20 psig 12 psig 10 psi 22 psig 2...

Reviews: