Bellows

Bellows

DKRCC.PI.C00.E1.22 / 520H6070 

© Danfoss A/S (AC-MCI / jmn), 2012-11

CAUTION:

Disconnect power supply before wiring connections are made or service to avoid possible electrical shock  

or damage to equipment. Do never touch live parts with your fingers or with any tool. 

Wiring

All wiring should conform 

 to the National Electrical Code  

and local regulations.

Terminal block

CAUTION

:

Use terminal screws furnished  

in the contact block.

Use tightening torque 20 lb. in (2.3 Nm).

Use copper wire only.

Contact load ratings

Load Option A

CUT-OUT on pressure drop

Wire terminals 1-4: 

CUT-IN     = High Set Point (HSP) 

see “Setting”

CUT-OUT = Low Set Point (LSP) 

see “Setting”

Load Option B

CUT-OUT on pressure rise

Wire terminals 1-2: 

CUT-IN     = Low Set Point (LSP) 

see “Setting”

CUT-OUT = High Set Point (HSP) 

see “Setting”

Example:

  

CUT-IN = 30 psig

CUT-OUT = 10 psig

This means

 : 

CUT-IN = HSP = 30 psig

CUT-OUT = LSP = 10 psig

Example:

  

CUT-IN = 250 psig

CUT-OUT = 350 psig

This means

 : 

CUT-IN = LSP = 250 psig

CUT-OUT = HSP = 350 psig

Bellows movement  

on pressure rise

The free terminal can be 

used for signal purpose.

120 V a.c.

16 FLA, 96 LRA

240 V a.c.

8 FLA, 48 LRA

240 V d.c.

12 W pilot duty

Terms 1-4 close on pressure rise

Terms 1-4 open on pressure drop

Terms 1-2 close on pressure drop

Terms 1-2 open on pressure rise

Bellows movement  

on pressure drop

Note:

Note:

KP 1, man. reset is possible only 

after a pressure rise  

of 10 psi (0.7 bar). KP 5 and KP 7B, 

man. reset is possible  

only after a pressure drop  

of respectively 43 psi (3.0 bar)  

and 58 psi (4.0 bar)

Note:

KP 1, KP 5 and KP 7B with man. reset:

Push manual reset knob during 

manual tripping.

TRIP (main lever)  

use FINGERS ONLY!

(Do NOT use screwdriver)

To resume control operation 

after safety cutout,  

push reset knob as indicated.

Adjustment spindle(s) location

Type

Differential

KP 1

10 psi (0.7 bar)

KP 5

43 psi (3 bar)

KP 7B

58 psi (4 bar)

Auto reset KP 1, KP 2, KP 5, KP 7W

Manual reset KP 1, KP 5, KP 7B

A: 

Range

B: 

Differential

A: 

Range

B: 

Differential

Manual trip function

(Electrical contacts / wiring test)

Manual reset