background image

 DKRCI.PI.GB0.A7.77 / 520H0444 

© Danfoss A/S (MWA), 2015-01

ENGLISH

Installation

Refrigerants

Applicable to all common non-flammable 

refrigerants, including R717 and non-

corrosive gases/liquids dependent on 

sealing material compatability.

As standard the float ball is designed for 

R717 with a density of 500 through to 

700 kg/m

3

. For refrigerants, which have a 

density outside this range please contact 

Danfoss. 

Flammable hydrocarbons are not 

recommended. The valve is only 

recommended for use in closed circuits. For 

further information please contact Danfoss.

Temperature range

HFI : –50/+80°C (–58/+176°F)

Pressure range

The float valves are designed for a max. 

working pressure of 25 bar g(363 psi g).

Strength test without floatball.

Installation

Mount the float valve horizontally with the 

outlet connection pos. A (fig. 1) vertically 

downwards. 

The flow direction has to be from the 

flanged inlet connection as indicated with 

the arrows (fig. 1).

The valve is designed to withstand a high 

internal pressure. However, the piping 

system should be designed to avoid liquid 

traps and reduce the risk of hydraulic 

pressure caused by thermal expansion. It 

must be ensured that the valve is protected 

from pressure transients like “liquid 

hammer” in the system.       

Welding

Remove the float assembly before welding 

as follows:

-  Dismount the end cover and remove the 

transport packing.

  After welding and assembly, the 

transport packing should be put back 

into place, until the final destination of 

the unit is reached.

-  Unscrew the screw pos. C (fig. 1) and lift 

up the float assembly from the outlet.

-  Weld the outlet connection pos. A (fig. 1) 

into the plant as shown in fig. 2.

Only materials and welding methods, 

compatible with the valve housing 

material, must be welded to the valve 

housing. The valve should be cleaned 

internally to remove welding debris on 

completion of welding and before the 

valve is reassembled. 

Avoid welding debris and dirt in the 

housing.

NB!

 When demand is heavy at low 

temperature operation, we recommend to 

check the velocity in the outlet branch. If 

necessary the diameter of the pipe which is 

welded on to the outlet branch pos. A  

(fig. 1) can be increased.

The valve housing must be free from 

stresses (external loads) after installation.

Assembly

Remove welding debris and any dirt from 

pipes and valve body before assembly. 

Replace float assembly in the outlet branch 

and tighten the screw pos. C (fig 3). Check 

that the float assembly has gone all the 

way down the outlet connection and that 

the float ball is positioned in the middle of 

the housing, so it can move without any 

restriction.

End cover with purge valve and pipe is 

remounted in the housing.

NB! 

The ventilating pipe pos. E (fig 3) has to 

be placed vertically up-wards.

In case an insert with a slide (version before 

2007) replaced by a present version, an 

extra threaded hole needs to be made in 

the outlet connection A to fix the screw 

(fig.1)

Tightening

Use a torque wrench to tighten the screws 

pos. F (fig. 3). Tighten with torque of 183 

Nm (135 Lb-feet).

Colours and identification

The HFI valves are painted with a red oxide 

primer in the factory. The external surface 

of the valve housing must be prevented 

against corrosion with a suitable protective 

coating after installation and assembly.

Protection of the ID plate when repainting 

the valve is recommended.

Maintenance

Purging of incondensable gases

Incondensable gases might accumulate 

in the upper part of the float valve. Purge 

these gases by means of the purge valve 

pos. G (fig. 4).

Replacement of complete float assembly 

(adjusted from factory), follow the steps 

below:

1) 

NB!

 Before openening up the float 

valve, the system must be evacuated 

and the pressure equalized to 

atmospheric pressure by using the 

purge valve pos. G (fig. 4)

2)  Remove the end cover

3)  Remove float valve assembly by 

untightening the screw pos. C (fig. 5) 

and lifting up the complete float valve 

assembly.

4)  Place new float assembly in the outlet 

connection pos. A and tighten the screw 

pos. C (fig. 5)

5)  End cover with purge valve and pipe is 

remounted on the housing. 

 

NB!

 Ventilating pipe pos. E (fig. 5) has to 

be placed vertically upwards.

6)  Use a torque wrench to tighten the 

screws pos. F (fig. 5). Tighten with 

torque of 183 Nm (135 LB-feet).

NB!

 Check that the purge valve is closed 

before you pressurize the float valve.

Use only original Danfoss parts for 

replacement. Materials of new parts are 

certified for the relevant refrigerant. 

In cases of doubt, please contact Danfoss. 

Danfoss accepts no responsibility for 

errors and omissions. Danfoss Industrial 

Refrigeration reserves the right to make 

changes to products and specifications 

without prior notice.

Reviews: