11
Installation Guide
GreenCon RC-C2/C4
GB
Danfoss Heating Solutions
VIE2C32P
9. Parameter setting
Long press “
M
” for 6 seconds to enter param-
eter setting mode.Then, short press “
M
” to
select parameter; press
“
<
” or “
>
”
to adjust
value.
Parameter
Definition
Setting range
Factory
setting
P01
Programming
function On/Off
01: Off
;
02:5/2
days 4 event
01
P02
Timer ON/OFF
01
:
ON
;
02
:
OFF
01
P03
Maximum room
temperature
setting
5-35°C
30°C
P04
Minimum room
temperature
setting
5-35°C
5°C
P05
Frost protection
01: ON; 02: OFF
01
P06
Frost protection
temperature
5-17°C
5°C
P07
Default heating
temperature
5-35°C
20°C
P08
Default cooling
temperature
5-35°C
25°C
P09
Default heating
temperature for
ECO mode
5-35°C
15°C