© Danfoss | DCS (ADAP-KOOL®) | 2018-11
Quick Start Guide
ERC 213
DKRCE.PD.RL0.A3.02 | 1
Overview
The ERC 213 is designed to be an easy, universal replacement control. We encourage users to employ one of five predefined applications that meet the
needs of most systems. If users need to modify specific parameters, it should be done after installing the predefined application that most closely meets
system needs.
For more information, including detailed instructions, error codes, parameters, and more,
visit www.danfoss.com/erc or download the Koolcode app from iTunes or Google Play.
For a video guide of the quick set-up, visit http://bit.ly/ERC213 or use the QR code located to the right.
STEP
Action
Screen Display
STEP 1 Wire control, to include power and sensors
STEP 2
Power up control
Energize control
Control turns on, goes through start up,
then shows the current temperature reading
STEP 3
Enter Quick Configuration Menu and Select app
Press ”<” for more than three seconds within one minute of power up to enter Quick Configuration Menu. o61 appears on screen
Press “set” while o61 is on screen
AP0 flashes on screen
Select appropriate app using App Selection section below by pressing “ ” or “ ”, then press “set”.
o06 appears on screen
STEP 4
Select Sensor
Press “set” while o06 is on screen
n10 flashes on screen
If using included sensor, leave default value “n10”. If using another sensor, select using Sensor Resistance
section on opposing page or cycle through steps 2 – 4 changing the sensor type until the temperature reading
on the main screen is accurate. As above, cycle between options by pressing “ ” or “ ” and press “set” to save.
o06 appears on screen, then control resets
STEP 5
Set Temperature
From main screen, quickly press “set” (1 second).
Current temp. setting appears on screen
Cycle to intended temperature by pressing “ ” or “ ” and press “set” to save.
Screen returns to main screen
Quick Set-up
Control
Application
Code
Application
Defrost
Type*
Defrost
Termination
Sensors
Default
Temp. [°F]
[r00]
Temp. Range
min. / max.
[°F]
[r02/r03]
Default Dif.
[°F] [r01]
Defrost
Interval
[hrs]
[d03]
Max.
Defrost
Time [mins]
[d04]
Defrost
Termination
Temp. [°F]
[d02]
AP0 (Default)
No preset application - full menu
2
36
-31
/
22
4
6
30
43
AP1
Refrigeration
Natural
Time
1
39
36
/
43
4
4
30
–
AP2
Refrigeration
Electric
Time
1
36
32
/
39
4
6
15
–
AP3
Freezing
Electric
Time
1
-11
-15
/
-4
4
6
15
–
AP4
Refrigeration
Electric
Temp.
2
36
32
/
39
4
6
30
43
AP5
Freezing
Electric
Temp.
2
-11
-15
/
-4
4
6
30
43
AP6
No preset application - simplified menu
2
36
-31 – 122
4
6
30
43
* Hot gas defrost is an option available in full menu (d01).
Key Functions
Press and hold at power up:
FACTORY RESET (“FAC” is
displayed)
Press for one second: UP
Press and hold: ON
/
OFF
Press for one second: DOWN
Press and hold: DEFROST
Press for one second: BACK
Press and hold: PULL-DOWN
Press for one second: TEMP. SETPOINT
/
OK
Press and hold: MENU
SET
Display Icons
Night mode (Energy saving)
Fan running
Compressor running (Flashes
in pull-down mode)
Active alarm
Defrost
°C
Unit (°C or °F)
Key Functions and Display Icons
– Sair
Control sensor
– S5
Defrost (evaporator) sensor
– SC
Condenser sensor
– DI1
Digital input – configurable to the functions listed under
menu code o02
– DI2
Digital input – configurable to the functions listed under
menu code o37
Connection Diagram
DO1
1
2
Sair
S5
Sc/DI1
DI2
DO2 DO3
GND
GND
Programming key – EKA 183B (080G9741)
3L
4N
5
6
7
8
9
10
15
16
17
18
11
12
13
14
~
~
~
~
Power supply
(according to the product code number)
GND TX RX +5V
App Selection
Select application based on application and wiring configuration (i.e., refrigeration vs. freezing, and number of temperature sensors). The Typical Wiring
Configurations diagram on the reverse side of this document may be used to assist with selection. All parameters can be modified using the full menu.
Some parameters have min and max set points which may need to be changed for less common configurations.