background image

© Danfoss | DCS (ADAP-KOOL®) | 2018-11

Quick Start Guide 

 

ERC 213 

DKRCE.PD.RL0.A3.02 | 1

Overview

The ERC 213 is designed to be an easy, universal replacement control. We encourage users to employ one of five predefined applications that meet the 

needs of most systems. If users need to modify specific parameters, it should be done after installing the predefined application that most closely meets 

system needs.
For more information, including detailed instructions, error codes, parameters, and more, 

visit www.danfoss.com/erc or download the Koolcode app from iTunes or Google Play.
For a video guide of the quick set-up, visit http://bit.ly/ERC213 or use the QR code located to the right.

STEP

Action

Screen Display

STEP 1 Wire control, to include power and sensors

STEP 2

Power up control

Energize control

Control turns on, goes through start up, 

then shows the current temperature reading

STEP 3

Enter Quick Configuration Menu and Select app

Press ”<” for more than three seconds within one minute of power up to enter Quick Configuration Menu. o61 appears on screen

Press “set” while o61 is on screen

AP0 flashes on screen

Select appropriate app using App Selection section below by pressing “ ” or “ ”, then press “set”.

o06 appears on screen

STEP 4

Select Sensor

Press “set” while o06 is on screen

n10 flashes on screen

If using included sensor, leave default value “n10”. If using another sensor, select using Sensor Resistance 
section on opposing page or cycle through steps 2 – 4 changing the sensor type until the temperature reading 
on the main screen is accurate. As above, cycle between options by pressing “ ” or “ ” and press “set” to save.

o06 appears on screen, then control resets

STEP 5

Set Temperature

From main screen, quickly press “set” (1 second).

Current temp. setting appears on screen

Cycle to intended temperature by pressing “ ” or “ ” and press “set” to save.

Screen returns to main screen

Quick Set-up

Control 

Application 

Code

Application

Defrost 

Type*

Defrost 

Termination

Sensors

Default 

Temp. [°F] 

[r00]

Temp. Range 

min. / max. 

[°F] 

[r02/r03]

Default Dif. 

[°F] [r01]

Defrost 

Interval 

[hrs] 

[d03]

Max. 

Defrost 

Time [mins] 

[d04]

Defrost 

Termination 

Temp. [°F] 

[d02]

AP0 (Default)

No preset application - full menu

2

36

-31

 

/

 

22

4

6

30

43

AP1

Refrigeration

Natural

Time

1

39

36

 

/

 

43

4

4

30

AP2

Refrigeration

Electric

Time

1

36

32

 

/

 

39

4

6

15

AP3

Freezing

Electric

Time

1

-11

-15

 

/

 

-4

4

6

15

AP4

Refrigeration

Electric

Temp.

2

36

32

 

/

 

39

4

6

30

43

AP5

Freezing

Electric

Temp.

2

-11

-15

 

/

 

-4

4

6

30

43

AP6

No preset application - simplified menu

2

36

-31 – 122

4

6

30

43

* Hot gas defrost is an option available in full menu (d01).

Key Functions

Press and hold at power up:

FACTORY RESET (“FAC” is 

displayed)

Press for one second: UP

Press and hold: ON

 

/

 

OFF

Press for one second: DOWN

Press and hold: DEFROST

Press for one second: BACK

Press and hold: PULL-DOWN

Press for one second: TEMP. SETPOINT

 

/

 

OK

Press and hold: MENU

SET

Display Icons

Night mode (Energy saving)

Fan running

Compressor running (Flashes 

in pull-down mode)

Active alarm

Defrost

°C

Unit (°C or °F)

Key Functions and Display Icons

 

– Sair

 Control sensor

 

– S5

  Defrost (evaporator) sensor

 

– SC

  Condenser sensor

 

– DI1

  Digital input – configurable to the functions listed under 

     

menu code o02

 

– DI2

  Digital input – configurable to the functions listed under 

     

menu code o37

Connection Diagram

DO1

1

2

Sair

S5

Sc/DI1

DI2

DO2        DO3

GND

GND

Programming key – EKA 183B (080G9741)

3L

4N

5

6

7

8

9

10

15

16

17

18

11

12

13

14

~

~

~

~

Power supply

(according to the product code number)

GND         TX          RX         +5V

App Selection

Select application based on application and wiring configuration (i.e., refrigeration vs. freezing, and number of temperature sensors). The Typical Wiring 

Configurations diagram on the reverse side of this document may be used to assist with selection. All parameters can be modified using the full menu. 

Some parameters have min and max set points which may need to be changed for less common configurations.

Summary of Contents for ERC 213

Page 1: ...ress set to save Screen returns to main screen Quick Set up Control Application Code Application Defrost Type Defrost Termination Sensors Default Temp F r00 Temp Range min max F r02 r03 Default Dif F r01 Defrost Interval hrs d03 Max Defrost Time mins d04 Defrost Termination Temp F d02 AP0 Default No preset application full menu 2 36 31 22 4 6 30 43 AP1 Refrigeration Natural Time 1 39 36 43 4 4 30 ...

Page 2: ... AC DO2 DO3 DO1 DO3 DO2 DO1 DO3 DO2 ERC 213 APP 1 ERC 213 APP 2 3 ERC 213 APP 4 5 Troubleshooting Power Supply Code Description Remedy applicable parameter code in parenthesis Common Alarm Error Codes A01 High temperature alarm Bring down temperature or increase high limit alarm limit A13 A02 Low temperature alarm Increase temperature or low temperature alarm limit A14 E27 Defrost sensor error Ver...

Page 3: ...A14 C 100 200 30 30 DI1 delay A27 min 0 240 30 30 DI2 delay A28 min 0 240 30 30 Condenser High temp alarm A37 C 0 200 80 80 Condenser High block limit A54 C 0 200 85 85 Voltage protection A72 No No Min cut in voltage A73 V 0 270 0 0 Min cut out voltage A74 V 0 270 0 0 Max voltage A75 V 0 270 270 270 Defrost Method d01 Electric Electric Defrost stop temperature d02 C 0 50 6 6 5 Defrost Interval d03...

Page 4: ...ty P74 no no Invert alarm relay P75 Normal Normal Keyboard lock P76 No No Main switch r12 Off On Controller status u00 S25 S20 Air temperature Sair u01 C 321 Present regulation reference u02 0 Evaporator temperature S5 u09 C 0 DI1 status u10 Off Off Night mode u13 Off Off DI2 status u37 Off Off Condenser temperature Sc U09 0 Compressor relay status u58 Off Off Fan relay status u59 Off On Defrost r...