14
FR · ERC 21X user manual · DKRCC.ES.RL0.H3.02/520H9656 · ©Danfoss
–
STEP 4: select sensor type “
o06
”
The display automatically shows sensor selection parameter “
o06
”.
Press SET to select the sensor type.
The display shows the default value (eg. “
n10
” flashing).
Choose sensor type by pressing UP/DOWN (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) and press SET to confirm.
NOTE
: all sensors must be the same type.
–
STEP 5: configure DO4 output “
o36
”
The display automatically shows the “
o36
” parameter to configure “
DO4
” output. (Available only in 4 relays model).
Select light “
Lig
” or alarm “
ALA
” as per the application and press SET to confirm.
The display returns to normal display mode and the control is started.
5.3| Menu Structure
1) Parameter groups
2) Parameter name
3) Value
Scroll through the
parameter groups
SET: press for 3 seconds to access
status, setup and service
Password (if enabled)
Status input
Configuration
Main switch
Application
Sensor type
DO4 configuration
(only for 4 relays model)
Application 0
Application
1-2-3-4-5-6
Application
1-2-3-4-5-6
SET
Scroll through the
parameter names
SET