Function
Code
Min.
Max.
Unit
AP0
AP1
AP2
AP3
AP4
AP5
AP6
AP7
Fan during defrost
d09
OFF
on
on
on
OFF
OFF
OFF
OFF
OFF
-
Defrost stop sensor non=None (Time), Air = Sair
temp. sensor, dEF= S5 Defrost sensor
d10
non
dEF
non
non
non
dEF
non
-
Accumulated Compressor runtime to start defrost
(0=OFF)
d18
0
96
hour
0
0
0
0
0
0
-
-
Defrost on demand (20=OFF)
d19
0.0
20.0
K
20.0
20.0
20.0
20.0
-
-
Defrost delay after pull down cycle
d30
0
960
min
0
0
0
0
0
0
-
-
(1)
This option is a default setting in the controller and cannot be changed.
(1)
This option is a default setting in the controller and cannot be changed.
Fan control
Table 25: Fan control
Function
Code
Min.
Max.
Unit
AP0
AP1
AP2
AP3
AP4
AP5
AP6
AP7
Fan control
F--
Fan at compressor cutout (FAo=Fan always ON;
FFC=Fan follow compressor; FPL= Fan Pulsating)
F01
Fao
FPL
FAo
FAo
FAo
FAo
FAo
FAo
FAo
FAo
Fan stop evap. Temperature
F04
-50.0
50.0
°C
50.0
-
-
-
50.0
50.0
50.0
-
Fan ON Cycle
F07
0
180
min
2
2
2
2
2
2
(1)
2
2
Fan OFF cycle
F08
0
180
min
2
2
2
2
2
2
2
(1)
This option is a default setting in the controller and cannot be changed.
(1)
This option is a default setting in the controller and cannot be changed.
Compressor
Table 26: Compressor
Function
Code
Min.
Max.
Unit
AP0
AP1
AP2
AP3
AP4
AP5
AP6
AP7
Compressor
c--
Compressor / Heater minimum ON time
C01
0
30
min
0
0
0
0
0
0
0
0
Compressor /Heater minimum OFF time
C02
0
30
min
2
2
2
2
2
2
2
2
Compressor OFF delay at open door
C04
0
900
Sec
900
900
900
900
900
900
60
(1)
900
Zero crossing selection (YES / no)
C70
no
YES
YES
YES
YES
YES
YES
YES
YES
YES
(1)
This option is a default setting in the controller and cannot be changed.
(1)
This option is a default setting in the controller and cannot be changed.
Others
Table 27: Others
Function
Code
Min.
Max.
Unit
AP0
AP1
AP2
AP3
AP4
AP5
AP6
AP7
Others
o--
Delay of outputs at startup
o01
0
600
sec
10
10
10
10
10
10
10
(1)
10
DI1 configuration
nC= Not configured; Sdc = Status display output,
doo = Door alarm with resumption, doA = Door
alarm without resumption, SCH = Main switch, nig
= Day/ Night mode, rFd = Reference displasement,
EAL = External alarm, dEF = Defrost, Pud = Pull
down; Sc = Condensor Sensor
o02
nC
Sc
nC
nC
nC
nC
nC
nC
nC
nC
Serial address
o03
0
247
No
0
0
0
0
0
0
-
0
Password
o05
0
999
No
0
0
0
0
0
0
0
0
Sensor type (n5=NTC 5K, n10=NTC10K, ptc=PTC,
pt1=PT1000)
o06
(2)
n5
ptc
n10
n10
n10
n10
n10
n10
n10
n10
Cooling/Heating (rE=Cooling, Ht= Heating)
o07
rE
Ht
rE
rE
rE
rE
Ht
Display Resolution
o15
0.1
1.0
0.1
0.1
0.1
0.1
0.1
0.1
0.1
DI2 configuration
nC= Not configured; Sdc = Status display output,
doo = Door alarm with resumption, doA = Door
alarm without resumption, SCH = Main switch, nig
= Day/Night mode, rFd = Reference displasement,
EAL = External alarm, dEF = Defrost, Pud = Pull
down
o37
nC
Pud
nC
nC
nC
nC
nC
nC
nC
nC
Electronic refrigeration control, type ERC 21X
© Danfoss | Climate Solutions | 2023.01
BC194286421698en-000901 | 26