Applications
Pre-defined applications
The purpose of the pre-defined applications is to give the user an easy and fast way to configure the controller to a
specific application based on storage temperature (LT, MT, HT), defrost type (none, natural, electrical) and defrost
method (terminated on time or temperature).
When user select specific application based on their requirements, the controller will load a specific set of parameter
values and will hide parameters that are not relevant for the selected application. Adjustment of the set of
parameters value will be still possible at any time.
In addition to pre-defined applications, all controller versions have two standard applications, one with full list of
parameters and another with simplified list of parameters, that allows the user to make their own customized
parameter settings (AP0 and AP5 in case of ERC 211 and AP0 and AP6 in case of ERC 213 / ERC 214).
ERC 211 controller
Table 1: Pre-defined application table of ERC 211 controller
APP
Description
Temp. range
Defrost end
DO1
AI1
DI1
(1)
AP0
Fully Configurable Standard Application (Cooling / Heating)
AP1
MT, No defrost
4 – 20 °C
NA
Sair
DI1
AP2
MT, Natural defrost
2 – 6 °C
Time
Sair
DI1
AP3
MT, Natural defrost, defrost stop by Sair
2 – 6 °C
Sair temp
Sair
DI1
AP4
Heating Thermostat
30 – 70 °C
NA
Sair
DI1
AP5
Fully configurable simplified application (Cooling / Heating)
(1)
The digital inputs DI1 can be configured for multiple functions (refer parameter “o02”).
(1)
The digital inputs DI1 can be configured for multiple functions (refer parameter “o02”).
ERC 213 controller
Table 2: Pre-defined application table of ERC 213 controller
APP
Description
Temp.
range
Defrost
end
DO1
DO2
DO3
AI1
AI2
DI1
(1)
DI2
AP0
Fully Configurable Standard Application (Cooling / Heating)
AP1
MT, Natural defrost, Alarm, fan
2 – 6 °C
By time
Sair
NC
DI1/Sc
DI2
AP2
MT, Electrical defrost, Fan
0 – 4 °C
By time
Sair
NC
DI1/Sc
DI2
AP3
LT, Electrical defrost, fan
-24 – -18 °C
By time
Sair
NC
DI1/Sc
DI2
AP4
MT, Electrical defrost, Fan
0 – 4 °C
By
temp(S5)
Sair
S5
DI1/Sc
DI2
AP5
LT, Electrical defrost, Fan
-26 – -20 °C
By
temp(S5)
Sair
S5
DI1/Sc
DI2
AP6
Fully configurable simplified application (Cooling / Heating)
AP7
Heating Thermostat
30 – 70 °C
NA
Sair
NC
DI1
DI2
(1)
The digital inputs DI1 and DI2 can be configured for multiple functions (refer Parameters “o02” and “o37”).
(1)
The digital inputs DI1 and DI2 can be configured for multiple functions (refer Parameters “o02” and “o37”).
NC = Not configured
© Danfoss | Climate Solutions | 2023.01
BC194286421698en-000901 | 11
Electronic refrigeration control, type ERC 21X