Assignments
Assignments of inputs and outputs
S2 Application
S2A
Application to be controlled with Sensor
C. (nC=Not Connected, Sco= Temp control,
EuA= Evap temp, Con=Cond temp {condenser
cleaning})
nC
Con -
nc
DO1 configuration
o1C Relay output 1. compressor (CoP)
2. Heater HeT
CoP
HeT
-
CoP
Password level1
PS1
Shop owner Most common parameters
0
999
-
0
Password level2
PS2
Service technician all parameters with read
permission and possibility to change a
number of parameters
0
999
-
0
Service
Service
Voltage value
uAC Current main power supply voltage
0
270
Vac
-
Relay 1 counter
rL1
Thousands of cycles of compressor relay since
manufacture
0
999
1000
-
Interval counter
int
Compressor run time since last defrost
0
999
min
-
Defrost time counter
dnt
Duration of last defrost cycle [min]
0
999
min
-
Firmware version
Fir
Danfoss software version number
-
-
-
-
Hardware version
HAr
Danfoss hardware version number
-
-
-
-
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifica-
tions already agreed. All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Parameters
Problem solving
Menu
Parameters
Cod Description
Min
Max Unit
De-
fault
Setpoint
Stp
Setpoint
-50
80
C
2
Thermostat
tHE
Thermostat settings
Setpoint adjustment
ratio
SPr
Current setpoint adjustment value diF * SPr
0.0
1.0
-
0.0
Differential
diF
Thermostat differential
0.0
20.0 K
2.0
Air temperature
adjust
tAD
Air Temp Adjust
0.0
20.0 K
0
Alarm
ALA Alarm setting
High temperature
alarm
HAt
Alarm is activated above this temperature
(Celsius )
-50.0 80.0 C
15.0
Low temperature
alarm
LAt
Alarm is activated below this temperature
(Celsius )
-50.0 80.0 C
-50.0
Compressor
CoP Compressor Setting
Min run time
Crt
Minimum time compressor must run 0-30
minutes
0
30
min
0
Min Stop time
CSt
Minimum time compressor must idle 0-30
minutes
0
30
min
0
Max OFF time
Cot
Maximum time compressor must idle 0-480
minutes
0
480
min
0
Error run time
Ert
Compressor run time if temperature sensor is
not working (0-60 minutes )
0
60
min
0
Error stop time
ESt
Compressor stop time if temperature sensor is
not working (0-60 minutes )
0
60
min
0
Minimum cut-in
voltage
uLi
When compressor is OFF:
lowest compressor start voltage (0-270 V)
0
270
Vac
0
Minimum cut-out
voltage
uLo
When compressor is ON:
lowest operation voltage (0-270 V)
0
270
Vac
0
Maximum voltage
uHi
When compressor is ON:
highest operation voltage (0-270 V)
0
270
Vac
270
Power ON delay
Pod
Delay in seconds between power ON &
compressor being activated
0
300
Sec
180
Defrost
dEF
Defrost Setting
Defrost type
dFt
No: defrost function is disabled,
nat: OFF-cycle defrost (natural defrost)
no
nat
-
nat
Terminating temp
dtt
Temp at which defrost stop
(evap temperature or cabinet temperature)
0
25
C
7
Def Min Interval
dii
The minimum time in hours between the start
of each defrost cycle
0
96
hours 6
Def Max Interval
dAi
The maximum time in hours between the
start of each defrost cycle
0
96
hours 7
Def Min time
dit
The minimum duration of a defrost cycle
in minutes
0
240
min
10
Def Max time
dAt
The maximum duration of a defrost cycle
in minutes
0
480
min
30
Condenser
Protection
Con Condenser protection settings
Condenser Alarm
Limit
CAL If condenser sensor exceeds this temperature,
alarm is activated
0
85
C
75
Condens er Block
Lim it
CbL
If this temperature is exceeded, compressor
will be stopped
0
85
C
85
Condenser OK limit
CoL
Temperature at which compressor may start
after a stop due to exceeding CbL
0
85
C
60
Condenser Low Temp
CLL
Temperature below which the compressor is
not allowed to start
-50
20
C
-5
Display
diS
Display setting
Lock-time After
defrost
dLt
Display lock time after defrost [0-60 min]
0
60
min
5
Problem
Probable cause
Remedy
Compressor does not start
Waiting for compressor delay timer
Check CoP->CSt
Line voltage to compressor too low or too high Check CoP->uLi, uLo, uHi
E01 or E02 is shown on display
E01: Sensor "S1" defective
Replace sensor
E02: Sensor "S2" defective
Display alternates between "Con" and
temperature
Condenser temperature exceeds the
temperature set in condenser settings menu
Clean condenser,
Check Con->CAL, CbL
Display alternates between "Hi" and
temperature
Temperature too high
Check ALA->HAt
Display alternates between "Lo" and
temperature
Temperature too low
Check ALA-> LAt