background image

© Danfoss | Climate solutions | 2023.07

Technical specification

EKE100 1V 

EKE100 2V 

Code number

IP00: 080G5050

IP20: 080G5051

IP20 + display: 080G5052

IP00: 080G5055

IP20: 080G5056

IP20 + display: 080G5057

Supply Voltage

24 V AC/DC* 50/60 Hz, SELV **

24 V AC/DC* 50/60 Hz, SELV **

Battery backup Input (Danfoss 

recommends EKE 2U)

24V DC

24V DC

Number of valve outputs

1 stepper motor valve

2 stepper motor valves

Valve type

Bipolar stepper valve

Bipolar stepper valve

Modbus RS485 RTU

Yes (Isolated)

Yes (Isolated)

Baud rate (default setting)

19200

19200

Mode (default setting)

8E1

8E1

No of temperature sensors

1 (S2A)

2 (S2A,S2B)

Type of temperature sensors

PT 1000/NTC 10K

PT 1000/NTC 10K

No of Pressure sensors

1 (PeA)

2 (PeA,PeB)

Type of pressure sensors

Ratiometric 0.5 - 4.5 V DC

Current 4-20mA

Ratiometric 0.5 - 4.5 V DC

Current 4-20mA

No of digital input

1 (DI1)

2 (DI1,DI2)

Use of digital input (software 

selectable)

Start/Stop regulation

Heat/Cool mode

Battery backup signal (SOH)

Start/Stop regulation

Heat/Cool mode

Battery backup signal (SOH)

Digital  output

1 output: D0 (open collector), 

max sink current  

10 mA

1 output: D0 (open collector), 

max sink current 10 mA

PC suite 

KoolProg

KoolProg

Service Tools

EKA 200 + EKE 100 service cable

EKA 200 + EKE 100 service 

cable

Mounting (DIN rail)

35 mm DIN rail

35 mm DIN rail

Storage temperature 

-30 – 80 °C / -22 – 176 °F

-30 – 80 °C / -22 – 176 °F

Operating temperature

-20 – 70 °C / -4 – 158 °F

-20 – 70 °C / -4 – 158 °F

Humidity

<90% RH, non-condensing

<90% RH, non-condensing

Enclosure

Available in IP00, IP20 and IP20 

with integrated display. 

Available in IP00, IP20 and IP20 

with integrated display.

Note:

* The unit is suitable for use on a circuit capable of delivering not more than 50A RMS symmetrical  

   Amperes

** For US and Canada, use class 2 power supply

AN433741508202en-000203 | 3 

Summary of Contents for EKE

Page 1: ...atible valves ETS 6 ETS 8M Bipolar ETS C KVS C ETS L ETS 500 800P CCMT L CCMT CCM CTR Basic application Introduction EKE 100 1V SH control EKE 100 2V SH control Danfoss R64 3033 10 Danfoss R64 3033 10...

Page 2: ...GND GND GND GN GND GN GN GN ND GND GN GND N GND G GND GND GND GN GN GN N ND GN GND GN N N GN GND N N GN GN N ND ND N ND ND D N ND N ND N ND 70 mm 110 mm BAT BAT AC AC PE SV SV DO PeA PeB S2A S2B D11 D...

Page 3: ...metric 0 5 4 5 V DC Current 4 20mA No of digital input 1 DI1 2 DI1 DI2 Use of digital input software selectable Start Stop regulation Heat Cool mode Battery backup signal SOH Start Stop regulation Hea...

Page 4: ...Ext GND Ground for driver signal input GND Ground Comm for I O signals DO Digital Output PeA Pressure signal for A circuit Driver analog signal for A circuit S2A Temperature signal for A circuit DI1 D...

Page 5: ...ed by gently pulling the stirrup located in the base of the housing 1 2 3 Click Driver input Terminal to use signal Input A Terminal to use signal Input B Voltage A Voltage B Ext GND PeA Ext GND PeB C...

Page 6: ...porator 1 3 2 Evaporator outlet Conductive paste Important Note Mount the sensor on a clean paint free surface Remember to use heat conducting paste andinsulate the sensor For precise measurements mou...

Page 7: ...KE 100 2 Connect terminal BAT to 5V 3 Connect EKE 100 to power 4 Now Modbus communication options are reset to factory default Address 1 19200 baud mode 8E1 A B Not in use GND Danfoss 93Z9023 Modbus i...

Page 8: ...24 12 0 34 2 5 mm2 Torque 0 5 0 56Nm Analog inputs Max 10m AWG 24 16 0 14 1 5mm2 Sensor Max 10m AWG 24 16 0 14 1 5mm2 Stepper valve Max 30m AWG 24 16 0 14 1 5mm2 Torque 0 22 0 25Nm Digital input Max...

Page 9: ...Warning 2 Sec 1 Sec 0 Sec 1 Valve closed 2 Valve closing 3 Valve idle on target 4 Valve idle on target 5 Valve opening 6 Valve open Valve open circuit or valve driver heat problem Normal valve operat...

Page 10: ...e device to continuous water sprays or to a relative humidity greater than 90 Do not exposure to corrosive or pollutant gases natural elements environments where explosives or mixes of flammable gases...

Page 11: ...cer Available with ratiometric and 4 20 mA NSK Ratiometric pressure probe XSK Pressure probe 4 20 mA Stepper motor valves M12 cable Backup power module EKE is compatible with Danfoss stepper motor val...

Reviews: