User Guide | Stepper Valve Extension Module, Type EKE 1P

© Danfoss | DCS (vt) | 2020.03

BC320219567793en-000201 | 9

Valve config

Any changes made to parameters in this group will only take effect after a restart of the 
controller, e.g. by a power cycle or by toggling the main switch.

Valve configuration

Application 1: Set from AK-PC except if the valve type is set to User Defined in AK-PC, 
then it is according to below list (see Application mode 2). 
Application 2: 
0 = no valve, 1 = UserDef,
2 = ETS 12C, 3 = ETS 24C, 4 = ETS 25C, 5 = ETS 50C, 6 = ETS 100C,
7 = ETS 6, 8 = ETS 12.5, 9 = ETS 25, 10 = ETS 50, 11 = ETS 100, 
12 = ETS 250, 13 = ETS 400,
14 = KVS 2C, 15 = KVS 3C, 16 = KVS 5C,
17 = KVS 15, 18 = KVS 42,
19 = CCMT 0, 20 = CCMT 1,
21 = CCMT 2, 22 = CCMT 4, 23 = CCMT 8,
24 = CCMT 16, 25 = CCMT 24,
26 = CCMT 30, 27 = CCMT 42,
28 = CCM 10, 29 = CCM 20, 30 = CCM 30, 31 = CCM 40,
32 = CTR 20
33 = CCMT 3L, 34 = CCMT 5L, 35 = CCMT 8L

Fac: no valve

Valve fallback OD

During fail-safe mode in application 1 (e.g. CANBUS signal lost), the valve will apply this 
opening degree. 

0 – 100% 
Fac: 0%

Valve motor type

Define a type of motor used in the stepper valve (Unipolar/Bipolar).

Unipolar / Bipolar 
Fac: Unipolar

Valve drive current

The current applied to each phase of the stepper motor during actual valve movement. 
Entered as a peak value.

10 – 1000 mA 
Fac: 10 mA

Valve step 
positioning

Read-out of the valve opening degree in number of steps.

Valve total steps

The number of steps that correspond to changing the valve position from 0 – 100% OD. 1 – 8000 steps 

Fac: 1 step

Valve speed

The desired valve drive rate in steps per second. 
Please note that a higher valve speed will produce a lower torque. If the valve is used in 
systems having high differential pressure, it is better to operate the valve with a lower 
step rate.

10 – 400 pps 
Fac: 10 pps

Valve start speed

This is used to limit the starting speed of the valve in order to provide higher motor 
torque at start-up to prevent the valve from potential step loss.

1 – 100% 
Fac: 20%

Valve emengency 
speed

During power failure conditions, the valve can be driven at higher speed when required 
to close faster. This function requires a back-up battery connected to the EKE.

50 – 200% 
Fac: 100%

Valve acceleration 
current

These features are used with valves running at higher speed i.e 300 pps and above. 
Typically, at start-up high torque is required to operate the valve. The high torque at 
start-up can be maintained by using acceleration current as required.

100 – 150% 
Fac: 100%

Valve acceleration 
time

10 – 150 ms 
Fac: 10 ms

Valve holding current The percent of the programmed Max Phase Current that should be applied to each 

phase of the stepper output when the valve is stationary. If required, this current 
ensures that the valve maintains its last programmed position.

0 – 300% 
Fac: 0

Valve step mode

Stepper motor can be driven with various step excitation methods, depending on valve 
requirements and operating conditions. 
The valves can be driven in full step 1/1, half step 1/2, or in microsteps (1/4, 1/8, 1/16).

Full, Half, 1/4, 1/8, 1/16 
Fac: 1/8

Valve duty cycle

The required valve duty cycle can be set between 5-100% using this parameter.

5 – 100% 
Fac: 100%

Valve OD during stop The valve will apply this opening degree if the control is stopped (main switch off).

0 – 100% 
Fac: 0%

Start backlash

The parameter defines the operation of the start backlash function. The valve will 
normally open from this point onwards.

0 – 50% 
Fac: 0.0%

Compensation 
backlash

This setting is used to correct for mechanical hysteresis of the valve’s designs including a 
reduction gear. To ensure that the gear backlash is at a minimum, the motor will drive a 
number of extra steps every time the direction of the motor is changed.

0-10% 
Fac: 0.0%

Overdrive

When the overdrive is enabled and the block timer has expired, next time the valve 
closes to 0% OD, it will close with some extra steps according to this setting.

0 – 20% 
Fac: 5.0%

Overdrive enable OD After being closed, the valve opening degree must exceed this value before the 

overdrive function is enabled again.

0 – 100% 
Fac: 0%

Overdrive block time After an overdrive has occurred, the overdrive function may not occur again within this 

time.

0 – 1440 min. 
Fac: 10 min.

Valve excitation time 
after stop

The time that the drive current is applied after the motor has stopped before going to 
holding current. This will make sure that the valve has achieved the final position before 
going to holding current.

0 – 1000 ms 
Fac: 10 ms

Summary of Contents for EKE 1P

Page 1: ...User Guide Stepper Valve Extension Module Type EKE 1P ADAP KOOL Refrigeration Control System www danfoss com...

Page 2: ...03 Introduction 3 Application 1 4 Application 2 4 User Interface 5 End user overview with graphical display 7 Service and commissioning with graphical display 7 Menu 8 Alarm list 11 ERR31 12 Connecti...

Page 3: ...guage only Two sets of LEDs on the EKE 1P indicate the EKE 1P application confirmation valve status and alarm condition see details further below Data communication The controller has a built in CANBU...

Page 4: ...lve will close in this case Application 2 Valve configuration The valve type can be selected from an extensive list of Danfoss standard valve types When a standard type is selected only a few paramete...

Page 5: ...G Configured as HP module will blink for 30 sec after power up 3 Receiver module 0s 2s 1s R R R R G G G G Configured as receiver module will blink for 30 sec after power up 0s 2s 1s R R R R G G G G R...

Page 6: ...fully closed V2 Valve closing 0s 2s 1s R R R R R R R R Flashing red 2 Hz valve closing V3 Valve idle 0s 2s 1s Running on target Both Red and Green off V4 Valve opening 0s 2s 1s G G G G G G G G Flashi...

Page 7: ...d outputs and will depend on how the set up is made application mode Click on the to view e g the following images Service and commissioning with graphical display To access the parameter menu press a...

Page 8: ...emperature and Pressure unit Metric C bar Imperial F psig Fac Metric C bar Backlight time out If no buttons have been pushed for a specific period of time the light in the display will be minimised Th...

Page 9: ...connected to the EKE 50 200 Fac 100 Valve acceleration current These features are used with valves running at higher speed i e 300 pps and above Typically at start up high torque is required to operat...

Page 10: ...tting of the CANBUS baudrate 20k 50k 125k 250k 500k 1M Fac 50k Service Actual OD Read out of the valve opening degree in percentage Actual step Read out of the valve opening degree in number of steps...

Page 11: ...oning set Half step operation is possible Correct either I029 or I064 Valve speed too fast Number of micro steps sec is too high higher than 12800 micro step sec Reduce valve speed or use less micro s...

Page 12: ...rner The software version must be 1 13 or newer Once the display s software version has been checked check the display s settings as follows 1 Hold the Enter key and the X key down for 5 seconds until...

Page 13: ...le Stepper motor Bipolar unipolar 1 Stepper valves A1 A2 B1 B2 Bipolar and unipolar stepper motor output Danfoss CCMT 3L CCMT 8L CCMT 0 CCMT 42 CCM 10 CCM 40 ETS 6 ETS 400 CTR 20 Other valves speed 10...

Page 14: ...inst voltage surges Category II Software class and structure Class A Approvals CE compliance This product is designed to comply with the following EU standards Low voltage guideline 2014 35 EU Electro...

Page 15: ...mounting only IP20 Type Function Operation Supply voltage Code no EKE 1P Stepper Valve Extension Module Via AK PC or MMIGRS2 24 V 080G0325 EKE 2U Back up power module 24 V 080G5555 AK PC 572 Capacity...

Page 16: ...Danfoss DCS vt 2020 03 BC320219567793en 000201 16 ADAP KOOL...

Reviews: