User Guide | Interface, EKC 366 

© Danfoss | DCS (ADAP-KOOL®) | 2015-11

DKRCI.PS.RP0.C1.02  | 2

The controller must always be used in conjunction with a pilot 

valve of the types shown here.

The most commonly used one is pilot valve CVQ in conjunction 

with main valve PM3 (sketched out above).

Valve types:

- CVQ + PM

- KVQ

- TQ

- PHTQ

- TEAQ

- CVMQ

Function

The valve constantly receives feedback of the pressure in the 

evaporator. Whatever the variations in the suction pressure from 

the compressor, this feedback will produce the result that the 

evaporating pressure is kept constant.

In conjunction with the controller, an electronic constant-pressure 

valve is thus obtained.

Inserted between the controller and the actuator is a so-called 

inner regulating loop. This loop will - via an NTC resistance - con-

stantly control the temperature in the actuator.

In an application where a PLC or similar device is used for regulat-

ing a media temperature, the regulating system will in this way be 

supplied with an outer regulating loop - which will result in great 

regulating accuracy.

System

"Q valve"

PLC

Summary of Contents for EKC 366

Page 1: ...n of the pressure in the valve and the interface module will keep this temperature constant The media temperature is regulated by a PLC or similar device Here the interface module receives a variable...

Page 2: ...suction pressure from the compressor this feedback will produce the result that the evaporating pressure is kept constant In conjunction with the controller an electronic constant pressure valve is t...

Page 3: ...tuator Ref Sundry configurations Miscellaneous External signal Here you set the signal that is to be connected to the controller 0 no signal 1 4 20 mA 2 0 20 mA 3 0 10 V 4 2 10 V o10 AI Type Frequency...

Page 4: ...conds the controller automatically returns to its setting and it again shows the valve s actual temperature Set one of the other menus 1 Push the upper button until a parameter is shown 2 Push one of...

Page 5: ...he actuator temperature cor responding to the required evaporating temperature push Set the value in the controller as mentioned under Set the valve s basic temperature reference The two curves are sh...

Page 6: ...he installation of the data communi cation cable be done correctly Cf separate literature No RC8AC Connections Supply voltage 24 V a c 15 50 60 Hz 80 VA the supply voltage is galvanically separated fr...

Page 7: ...operated from the various menu displays The programme will for example upload all the col lected tempera ture values once a day With a simple change over the values can also be shown in a trend diagr...

Page 8: ...Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessar...

Reviews: