Danfoss EKC 223 User Manual Download Page 27

Compressor

Table 17: Compressor

Code

Text on network

Description

c--

Compressor

c01

c01 Min. On time

Compressor minimum ON time

This parameter determines the minimum number of minutes the compressor must run before a cut-out can take effect

based on temperature. This is to avoid sudden switching ON and OFF of the compressor.

c02

c02 Min.Off time

Compressor minimum OFF time

This parameter determines the minimum number of minutes the compressor must switched OFF before a cut-in can take

effect based on temperature. This is to avoid sudden switching OFF and ON of the compressor.

c04

c04 Cmp Del Door

Compressor OFF delay at door open

This parameter sets the delay in seconds before the compressor stops when the door is opened. If set to zero, the function

is disabled.

c70

c70 Zero Cross

Zero crossing selection

This feature will increase the relay life time, reduce the contact welding and switching noise by switching ON at Zero cross-

ing. Disable zero crossing when external relay is used.

Miscellaneous

Table 18: Miscellaneous

Code

Text on network

Description

o--

Miscellaneous / Other

o01

o01 DelayOfOutp.

Delay of outputs at power-up

After power-up the controller functions can be delayed by the time delay defined here so that overloading of the electricity

supply network is avoided.

o02

(1)

o02 DI1 Config.

DI1 configuration

Here you can configure the DI1 to one of the functions listed below.

• (0) 

oFF

 = not used

• (1) 

Sdc

 = status display output

• (2) 

doo

 = door function

When the door is opened the compressor and fan are stopped after “C04 Compressor door open delay”. If the door

alarm delay expires an alarm is generated and cooling is resumed.

• (3) 

doA

 = door alarm

When the door is opened the compressor and fan are stopped after “C04 Compressor door open delay”. If the door

alarm delay expires an alarm is generated (cooling is not resumed).

• (4) 

SCH

 = main switch

Regulation is carried out when the input is short-circuited, and regulation is stopped when the input is put in position

OFF.

• (5) 

nig

 = day/night mode

When the input is short-circuited, there will be regulation for night operation.

• (6) 

rFd

 = reference displacement

Value in “r40” is added to the reference “r00” when the input is short-circuited.

• (7) 

EAL

 = external alarm

Alarm will be given when the input is short-circuited.

• (8) 

dEF

 = defrost

Defrost is initiated when the input is short-circuited. Edge triggering is used. Defrost exit can take place by time, tem-

perature or by manually pressing defrost push button on the front panel.

• (9) 

Pud

 = pull down

Pull down is initiated when the input is short-circuited. Edge triggering is used. It will come out of pull down based on

time and temperature defined under parameter “r96” and “r97” or can be stopped manually by pressing pull down

push button on front panel.

• (10) 

Sc

 = condenser sensor

o03

(1)

o03 Unit Addr

Network address for Modbus fieldbus

Data communication is possible through external EKA 206 to RS-485 adapter.

The network address must be set in the range between 1 – 120 to be integrated on a Modbus fieldbus.

Note:

 Network address must be set to 0, when connected to KoolProg through KoolKey.

o05

o05 Acc Code

Access code

If the settings in the controller are to be protected with an access code you can set a numerical value between 0 and 999. If

not, you can cancel the function with setting 0.

o06

(1)

o06 SensorConfig

Sensor type selection

This parameter is for defining type of temperature sensors connected to the controller. All the mounted sensors (Sair, S5

and Sc) must be of same type.

• (0) 

n5

 = NTC 5k (Danfoss type EKS211)

• (1) 

n10

 = NTC 10k (Danfoss type EKS 221)

• (2) 

Pt

 = Pt1000 (Danfoss type AKS11, AKS12, AKS21)

• (3) 

Ptc

 = PTC 1000 (Danfoss type EKS 111)

o15

o15 Disp Step

Display resolution

This parameter defines the steps in which the temperature must be displayed by 0.1 or 0.5 or 1

o16

o16 MaxHoldTime

Max. standby time after coordinated defrost

When a controller has completed a defrost it will wait for a signal which tells that the refrigeration may be resumed. If this

signal fails to appear for one reason or another, the controller will itself start the refrigeration when this standby time has

elapsed.

© Danfoss | Climate Solutions | 2023.05

BC432222569027en-000201 | 27

Case controller, type EKC 223 and EKC 224

Summary of Contents for EKC 223

Page 1: ...User Guide Case controller Type EKC 223 and EKC 224 SW Ver 1 0x For refrigerated display cabinets cold storage rooms and simple heating applications...

Page 2: ...r contact function 9 Defrost 9 Start of defrost 9 Coordinated defrost via network 10 Defrost on demand 10 Applications 11 EKC 224 applications 11 EKC 223 applications 11 Wiring diagrams 12 EKC 224 12...

Page 3: ...iguration 23 Thermostat 24 Alarm settings 24 Defrost 25 Fan 26 Compressor 27 Miscellaneous 27 Polarity 28 Service 29 EKC 223 224 display menu 29 Configuration 29 Thermostat 30 Alarm settings 30 Defros...

Page 4: ...rdering 36 Certificates declarations and approvals 37 Certificates declarations and approvals 37 Online support 38 Case controller type EKC 223 and EKC 224 Danfoss Climate Solutions 2023 05 BC43222256...

Page 5: ...buttons a big display easy and intuitive menu structure and pre defined applications ensure ease of use Controller is loaded with energy efficiency features like smart evaporator fan management day n...

Page 6: ...line programming of the EKC controllers It can also perform production line programming of multiple controllers and show on line trend curves on selected parameters Finally KoolProg can also load cont...

Page 7: ...mpressor can be initiated based on this temperature Voltage protection The voltage protection ensures that the compressor motor is operating within safe voltage ranges If the power supply voltage gets...

Page 8: ...high condensing temperature Sc temperature C Sc temperature C Manual reset Block limit Pre alarm limit Pre alarm OK Compressor Pre alarm Block alarm T1 T2 T3 T4 Danfoss 80G8376 Change of temperature r...

Page 9: ...is used to control a solenoid that lets the hot gas flow through the evaporator The compressor is kept running to generate hot gas Start of defrost A defrost can be started in different ways Interval...

Page 10: ...and 1 Based on compressor runtime when the aggregate compressor runtime has passed a set time a defrost will be started Figure 11 Based on compressor runtime Danfoss 80G8459 Defrost start t 2 Based on...

Page 11: ...DI1 and DI2 can be configured for multiple functions and DI1 can also be configured for a condenser temperature sensor Sc 1 The digital inputs DI1 and DI2 can be configured for multiple functions and...

Page 12: ...DO1 1 Sair S5 Sc DI1 DI2 DO2 DO3 DO4 GND GND Danfoss 80G8433 5 6 7 3L 4N 10 11 12 13 14 8 9 2L 115 230 V 115 230 V 3 DO1 1 Sair S5 Sc DI1 DI2 DO2 DO3 DO4 GND GND Danfoss 80G8434 5 6 7 3L 4N 10 11 12 1...

Page 13: ...es in to the connectors allowed tightening torque and wire sizes are Power connectors wire size 0 5 1 5 mm2 max tightening torque 0 4 Nm Low voltage signal connectors wire size 0 15 1 5 mm2 max tighte...

Page 14: ...is ON but via the parameter P75 the alarm relay action can be inverted DO3 3L 6 Digital output signal Fan and Light There is connection between terminal 3L and 6 when the function is ON DO4 3L 7 Digi...

Page 15: ...r when the compressor is stopped and to the need of liquid receivers before the compressors Your local Danfoss agent will be pleased to assist with further advice etc Integration into network systems...

Page 16: ...st be plugged into the RS 485 adapter Figure 15 Connection of RS 485 adapter Danfoss 80G8451 Wiring The Modbus cable must be wired as shown in Figure 16 Figure 16 Modbus cable Danfoss 80G8440 B MODBUS...

Page 17: ...e network For the EKC controllers the system manager can via internal schedules control the day night status light status and defrost including coordinated defrost among multiple controllers Table 6 O...

Page 18: ...may be a defect in the installation A alarms will not become visible until the set time delay has expired E alarms on the other hand will become visible the moment the error occurs Here are the messag...

Page 19: ...in drip off delay S10 Control has been stopped by r12 Main switch S11 Compressor is stopped due to thermostat cut out S14 Defrost cycle is in progress S15 Fan delay after defrost S17 Door is open S20...

Page 20: ...lways operative The display keys will be locked automatically when not used for some time and the keyboard must be unlocked by pressing the arrow up and arrow down keys at the same time Key operations...

Page 21: ...is in progress Pud A temperature pulldown cycle has been initiated Err The temperature cannot be displayed due to a sensor error Shown in top of display The parameter value has reached max Limit Show...

Page 22: ...tion and select the function associated to digital input 2 see DI input configuration Press SET Open the o62 Quick setting parameter and select the presetting that fits with the application in use see...

Page 23: ...ering is used It will come out of pull down based on time and temperature defined under parameter r96 and r97 or can be stopped manually by pressing pull down push button on front panel 10 Sc condense...

Page 24: ...so be accomplished with the external switch function connected to a DI input Stopped refrigeration will give a Standby alarm 1 ON Start 0 OFF Stop 1 SEr Manual control of outputs allowed r13 r13 Night...

Page 25: ...roller contains a timer function that is zeroset after each defrost start The timer function will start a defrost if when the interval time is passed The timer function starts after voltage is connect...

Page 26: ...becomes larger than required Here you set how large a slide of the S5 temperature can be allowed When the value is passed a defrost will start The function can only be used in 1 1 systems when the eva...

Page 27: ...mode When the input is short circuited there will be regulation for night operation 6 rFd reference displacement Value in r40 is added to the reference r00 when the input is short circuited 7 EAL exte...

Page 28: ...ays on 1 dAn day night 2 doo based on door action 3 nEt Network signal from system manager o39 o39 Light remote Light remote Parameter used by the network system manager to control the light status On...

Page 29: ...olenoid valve Status on relay for cooling u59 u59 Fan relay Fan relay Status on relay for fan u60 u60 Def Relay Defrost relay Status on relay for defrost u62 u62 Alarm relay Alarm relay Status on rela...

Page 30: ...K R W r02 Max limitation of setpoint setting r03 105 0 50 0 C R W r03 Min limitation of setpoint setting 40 0 r02 35 0 C R W r04 Adjustment of the display s temperature readout 10 0 10 0 0 0 K R W r0...

Page 31: ...is set to 0 Fan Table 25 Fan Code Short text manual Min Max De fault Unit R W EKC 224 Appl EKC 223 Appl 1 2 3 4 1 2 3 4 F Fan F01 Fan at stop of compressor 0 FFC Follow comp 1 Fao ON 2 FPL Fan pulsin...

Page 32: ...st stop on time 6 Room MT El defrost stop on temp 7 Room LT El defrost stop on temp 0 7 0 R W o67 Replace the controllers factory settings with the present set tings 0 No 1 Yes 0 No R W o91 Display at...

Page 33: ...relay 0 Off 1 On 0 Off R u63 Light relay 0 Off 1 On 0 Off R u80 Firmware version readout R u82 Controller code no R u84 Heat relay 0 Off 1 On 0 Off R U09 Sc Condenser temperature 100 0 200 0 0 0 R Da...

Page 34: ...g range 40 105 C 40 221 F Controller accuracy 1 K below 35 C 0 5 K between 35 25 C 1 K above 25 C Type of action 1B relay Output DO1 Relay 1 16 A 16 16 A EN 60730 1 10 FLA 60 LRA at 230 V UL60730 1 16...

Page 35: ...ear side of the panel Slide the clips towards mounting surface until controller is firmly fixed To remove the controller unlatch the snapping tab and pull the clips backwards Dimensions Figure 24 Dime...

Page 36: ...AC 3 relays 084B4054 084B4154 EKC 224 Danfoss 80G8446 SET V V V S M pack 115 V AC 4 relays 084B4055 084B4155 S M pack 230 V AC 4 relays 084B4056 084B4156 EKA 206 Danfoss 80G8461 RS 485 Network adapter...

Page 37: ...have any questions Certificates declarations and approvals Table 32 Certificates declarations and approvals Controller Certification Mark Country EKC 223 224 EMC LVD RoHS CE EU EKC 223 224 UL recogni...

Page 38: ...ations manuals and guides 3D models and drawings case stories brochures and much more Start searching now at www danfoss com en service and support documentation Danfoss Learning Danfoss Learning is a...

Reviews: