EKC 102A
Instructions RI8JT252 © Danfoss 05/2005
3
English
The buttons
Set menu
1. Push the upper button until a parameter
is shown
2. Push the upper or the lower button and
find that parameter you want to change
3. Push the middle button until the
parameter value is shown
4. Push the upper or the lower button and
select the new value
5. Push the middle button again to enter
the value.
Set temperature
1. Push the middle button until the
temperature value is shown
2. Push the upper or the lower button and
select the new value
3. Push the middle button to select the
setting.
Manuel start or stop of a defrost
• Push the lower button for four seconds.
Light emmiting diode
= refrigeration / pull in relay
= defrost
Flashes fast at alarm
Cutout alarm / see alarm code
• Push briefly the upper button
Start-up:
Regulation starts when the voltage is on.
Go through the survey of factory
settings. Make any necessary changes in the
respective parameters.
Parameters
Min.-
value
Max.-
value
Factory
setting
Actual
setting
Function
Codes
Normal operation
Temperature (set point)
---
-50°C
99°C
2°C
Thermostat
Differential
r01
0,1 K
20 K
2 K
Max. limitation of setpoint setting
r02
-49°C
99°C
99°C
Min. limitation of setpoint setting
r03
-50°C
99°C
-50°C
Adjustment of temperature indication
r04
-20 K
20 K
0 K
Temperature unit (°C/°F)
r05
°C
°F
°C
Correction of the signal from Sair
r09
-10 K
10 K
0 K
Manual service(-1), stop regulation(0), start regulation (1)
r12
-1
1
1
Compressor
Min. ON-time
c01
0 min
30 min
0 min
Min. OFF-time
c02
0 min
30 min
0 min
Compressor relay must cutin and out inversely
(NC-function)
c30
OFF
On
OFF
Defrost
Defrost method (0=none / 1=natural)
d01
0
1
1
Defrost stop temperature
d02
0°C
25°C
6°C
Interval between defrost starts
d03
0 hours
48 hours
8 hours
Max. defrost duration
d04
0 min
180 min
45 min
Displacement of time on cutin of defrost at start-up
d05
0 min
240 min
0 min
Defrost sensor (0=time, 1=Sair)
d10
0
1
0
Defrost at start-up
d13
no
yes
no
Miscellaneous
Delay of output signals after start-up
o01
0 s
600 s
5 s
Access code
o05
0
100
0
Used sensor type (Pt /PTC/NTC)
o06
Pt
ntc
Pt
Refrigeration or heat (rE=refrigeration, HE=heat)
o07
rE
HE
rE
Display step = 0.5 (normal 0.1 at Pt sensor)
o15
no
yes
no
Save the controllers present settings to the programming
key. Select your own number.
o65
0
25
0
Load a set of settings from the programming key (previ-
ously saved via o65 function)
(Can only be set when regulation is stopped (r12=0)
o66
0
25
0
Replace the controllers factory settings with the present
settings
o67
OFF
On
OFF
Service
Status on relay
Can be controlled manually, but only when r12=-1
u58
Fault code display
A45
Standby mode
Alarm code display
E1
Fault in controller
E29
Sair sensor error
Status code display
S0
Regulating
S2
ON-time Compressor
S3
OFF-time Compressor
S11
Refrigeration stopped by thermostat
S14
Defrost sequence. Defrosting
S20
Emergency cooling
S32
Delay of output at start-up
non
The defrost temperature cannot be
displayed. There is no sensor
-d-
Defrost in progress / First cooling
after defrost
PS
Password required. Set password
SW = 1.1X
Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep upper and lower button depressed at the same time as you reconnect the supply voltage