 EKC 102A 

Instructions  RI8JT252  ©  Danfoss  05/2005 

3

English

The buttons

Set menu

1. Push the upper button until a parameter 

is shown

2. Push the upper or the lower button and 

find that parameter you want to change

3. Push the middle button until the 

parameter value is shown

4. Push the upper or the lower button and 

select the new value

5. Push the middle button again to enter 

the value.

Set temperature

1. Push the middle button until the 

temperature value is shown

2. Push the upper or the lower button and 

select the new value

3. Push the middle button to select the 

setting.

Manuel start or stop of a defrost

• Push the lower button for four seconds.

 

Light emmiting diode

 = refrigeration  / pull in relay

 = defrost

Flashes fast at alarm

Cutout alarm  / see alarm code 

• Push briefly the upper button

Start-up:

Regulation starts when the voltage is on.

Go through the survey of factory 

settings. Make any necessary changes in the 
respective parameters.

Parameters

Min.-

value

Max.-
value

Factory 

setting

Actual 

setting

Function

 Codes

Normal operation

Temperature (set point)

---

-50°C

99°C

2°C

Thermostat

Differential

r01

0,1 K

20 K

2 K

Max. limitation of setpoint setting

r02

-49°C

99°C

99°C

Min. limitation of setpoint setting

r03

-50°C

99°C

-50°C

Adjustment of temperature indication

r04

-20 K

20 K

0 K

Temperature unit (°C/°F)

r05

°C

°F

°C

Correction of the signal from Sair

r09

-10 K

10 K

0 K

Manual service(-1), stop regulation(0), start regulation (1)

r12

-1

1

1

Compressor

Min. ON-time

c01

0 min

30 min

0 min

Min. OFF-time

c02

0 min

30 min

0 min

Compressor relay must cutin and out inversely
(NC-function)

c30

OFF

On

OFF

Defrost

Defrost method (0=none / 1=natural)

d01

0

1

1

Defrost stop temperature

d02

0°C

25°C

6°C

Interval between defrost starts

d03

0 hours

48 hours

8 hours

Max. defrost duration

d04

0 min

180 min

45 min

Displacement of time on cutin of defrost at start-up

d05

0 min

240 min

0 min

Defrost sensor (0=time, 1=Sair)

d10

0

1

0

Defrost at start-up

d13

no

yes

no

Miscellaneous

Delay of output signals after start-up

o01

0 s

600 s

5 s

Access code

o05

0

100

0

Used sensor type (Pt /PTC/NTC)

o06

Pt

ntc

Pt

Refrigeration or heat (rE=refrigeration, HE=heat)

o07

rE

HE

rE

Display step = 0.5 (normal 0.1 at Pt sensor)

o15

no

yes

no

Save the controllers present settings to the programming 
key. Select your own number. 

o65

0

25

0

Load a set of settings from the programming key (previ-
ously saved via o65 function)
(Can only be set when regulation is stopped (r12=0)

o66

0

25

0

Replace the controllers factory settings with the present 
settings

o67

OFF

On

OFF

Service

Status on relay
Can be controlled manually, but only when r12=-1

u58

Fault code display

A45

Standby mode

Alarm code display

E1

Fault in controller

E29

Sair sensor error

Status code display

S0

Regulating

S2

ON-time Compressor

S3

OFF-time Compressor

S11

Refrigeration stopped by thermostat

S14

Defrost sequence. Defrosting

S20

Emergency cooling

S32

Delay of output at start-up

non

The defrost temperature cannot be 
displayed. There is no sensor

-d-

Defrost in progress / First cooling 
after defrost

PS

Password required. Set password 

SW = 1.1X

Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep upper and lower button depressed at the same time as you reconnect the supply voltage