Maintenance intervals
Object
Check/Task
Weekly Monthly Yearly
General
construction
Operation
Abnormal phenomenon, for example noise or
heating. If clearly increased, contact Danfoss
representative.
X
Mounting
Tightness of the screws. Tighten to proper
value if necessary. Applies to screws that are
presented in this user guide. See Chapter
on page 15.
X
Enclosure and
connected parts
Check cleanliness. Clean if necessary. See
on page 36.
X
Electrical system
Cables
Visual check, for example wear. Replace if
necessary.
X
Electrical
connections
Check connections. Ensure that sufficient
tightening torque is applied to cable glands.
See Chapter
on page 15.
X
Groundings
(earthings)
Check groundings (earthings). Ensure that the
connection resistance is valid. Re-connect if
necessary.
X
Cooling system
Operation
Functioning. Cooling system functions as
specified.
X
Ventilation plug
Cleanliness. Clean if necessary. See Chapter
on page 36.
X
Cooling system maintenance
The cooling system of the electric device requires regular observation and maintenance
activities. Observe weekly that the cooling system operates correctly and check monthly that there are no
leakages in the cooling system. The quality of the coolant must be checked yearly. The mixture of water
and glycol as well as the type of the glycol used must be as specified. See Chapter
on page 22.
Cleaning
Do not use pressure washer for cleaning. High water pressure may damage the gaskets
allowing water to go in to the electric device.
Never open or remove the watertight ventilation plugs. Clean them only from the outside.
Risk of electric shock if the electric device is cleaned against instructions allowing water to go
in to the electric device.
Keep the electric device clean. For cleaning, use non-abrasive and non-corrosive cleaning products. Make
sure that the detergent can be used for aluminum.