If these instructions are not followed during installation, operation and maintenance, Danfoss heat pumps liability according to the ap-
plicable warranty is not binding. Danfoss heat pumps retains the right to make changes to components and specifications without prior
notice.
3.2.5
UK-specific appendix
Important information/Safety regulations
N
For important information and safety regulations, please read the
Danfoss DWH installation/maintenance manual.
N
Hard Water Areas; In areas where exceptional water conditions prevail,
consideration may need to be given to the fitting of a device capable
of inhibiting scale. In such circumstances the advice of the local water
authority should be sought.
N
Leave this document with the end-user.
This document is an integral and essential part of the product. It should be kept with the appliance so that it can be consulted by the
user and our authorised personnel. Please read carefully the instructions and notices about the appliance contained in this manual, as
they provide important information regarding the safe installation, use and maintenance of the water heater.
Manufacturer labels
The water heaters are marked with durable, permanently fixed labels.
Additional label
This label will ensure that this product conforms to the requirements of United Kingdom Building Regulations. The information is entire-
ly valid in a UK specific installation.
Product *)
Weight when full (kg)
DWH-200
285
DWH-300
410
DWH
Maximum water supply pressure
10 bar
Pressure reducing valve
3 bar
Expansion valve
6 bar
Expansion vessel charge pressure
3 bar
Operating pressure
5.5 bar
Installation Guide
DWH
Danfoss Heating Solutions
VMBNB82J
15
Summary of Contents for DWH 200
Page 1: ...MAKING MODERN LIVING POSSIBLE Installation Guide DWH www heating danfoss com...
Page 25: ...Installation Guide DWH Danfoss Heating Solutions VMBNB82J 25...
Page 26: ...Installation Guide DWH VMBNB82J Danfoss Heating Solutions 26...
Page 27: ...Installation Guide DWH Danfoss Heating Solutions VMBNB82J 27...